background image

9

blower Speed

 caution:

to avoid personal injury or property damage, 

make certain that the motor leads cannot 

come into contact with any uninsulated metal 

components of the unit.

The blower speed is preset at the factory for operation 

at the same speed for heating and cooling. These 

factory settings are listed in 

Table 5

.For optimum system 

performance and comfort, it may be necessary to change 

the factory set speed.

Fixed Torque ECM Motor

1. Shut off all electrical power to the unit and remove 

the blower panel. Locate the orange and red wires 

terminated to the blower motor. 

note:

 The orange wire 

controls cooling operation while the red wire controls 

heating operation.

2. Verify the required speed from the airflow data found 

i

Table 5

. Place appropriate wire on the correct motor 

speed tap for the required airflow point.

table 3. thermostat Wire gauge

tHerMoStat

Wire gauge

recoMMended t-Stat Wire

lengtH (unit to t-Stat)

2-Wire

(Heating)

5-Wire

(Heating/cooling)

24

55

25

22

90

45

20

140

70

18

225

110

kW/H

btu/H

5

17,060

8

27,297

9

30,709

10

34,121

15

51,182

20

68,242

table 4. kW & btu/h ratings

Model

nuMber

P8Se -

eXternal Static PreSSure droP - incHeS Water coluMn

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

X36

Tap T1**

1091 28.96 1031 30.64

995 31.75

929 34.01

871 36.27

774

41

704

45

629

50

Tap T2*

1296 24.38 1244 25.40 1169 27.03 1153 27.40 1089 29.01 1030 30.67

961 32.88

863 36.61

Tap T3

1525 20.72 1499 21.08 1448 21.82 1391 22.71 1338 23.61 1264 25.00 1221 25.88 1159 27.26

Tap T4

1641 19.25 1590 19.87 1543 20.48 1489 21.22 1444 21.88 1386 22.80 1345 23.49 1285 24.59

Tap T5

1791 17.64 1740 18.16 1659 19.04 1610 19.62 1555 20.32 1521 20.77 1467 21.54 1414 22.34

X48

Tap T1**

1264 25.00 1183 26.71 1126 28.06 1051 30.06

954 33.12

848 37.26

774 40.82

716 44.13

Tap T2

1462 21.61 1397 22.62 1322 23.90 1240 25.48 1181 26.75 1133 27.89 1006 31.41

888 35.58

Tap T3*

1776 17.79 1717 18.40 1654 19.10 1573 20.09 1533 20.61 1484 21.29 1422 22.22 1369 23.08

Tap T4

2127 14.85 2037 15.51 2008 15.73 1957 16.14 1865 16.94 1801 17.54 1743 18.13 1690 18.69

Tap T5

2419 13.06 2355 13.42 2311 13.67 2267 13.94 2194 14.40 2150 14.69 2085 15.15 2027 15.59

X60

Tap T1**

1209 26.13 1145 27.59 1106 28.57 1020 30.97

928 34.05

843 37.48

776 40.71

709 44.56

Tap T2

1629 19.39 1550 20.38 1479 21.36 1435 22.02 1369 23.08 1300 24.30 1244 25.40 1139 27.74

Tap T3*

1847 17.11 1800 17.55 1718 18.39 1668 18.94 1611 19.61 1556 20.30 1497 21.10 1449 21.80

Tap T4

2128 14.85 2059 15.34 1992 15.86 1961 16.11 1887 16.74 1828 17.28 1779 17.76 1718 18.39

Tap T5

2500 12.64 2444 12.93 2417 13.07 2345 13.47 2285 13.83 2228 14.18 2172 14.55 2109 14.98

noteS:

* Denotes factory set cooling speed
** Denotes factory set electric heating speed
Calculations made using 10kW heater kit.

table 5. P86e Series blower curves

Содержание P8SE Series

Страница 1: ...n sense plays an important role as well Pay attention to all safety warnings and any other special notes highlighted in the manual Improper installation of the furnace or failure to follow safety warn...

Страница 2: ...ced 3 Phase Supply Voltage 8 Grounding 8 Thermostat Connections 8 Blower Speed 9 Fixed Torque ECM Motor 9 Optional Outdoor Thermostat 10 Optional Electric Heater Kits 10 START UP SYSTEM CHECK 10 Pre S...

Страница 3: ...nit uses refrigerant R 410A DO NOT use any other refrigerant in this unit Use of another refrigerant may damage the unit WARNING The safety information listed below must be followed during the install...

Страница 4: ...des NFPA publications are avaialable by writing to National Fire Protection Association Batterymarch Park Quincy ME 02269 or visit www NFPA org on the web Design the duct work according to methods des...

Страница 5: ...filter pressure drop must not exceed 0 08 inches WC When replacing the air filters a suitable air filter must be installed upstream of the evaporator coil of the return air system DownflowInstallatio...

Страница 6: ...return air panel Hint Loosen the unit s top panel screws near the top edge of the access panel The access panel was designed to be captured underneath the top panel 2 Slide the first filter between bo...

Страница 7: ...Make all electrical connections in accordance with all applicable codes and ordinances Overcurrent protection must be provided at the branch circuit distribution panel and sized as shown on the unit...

Страница 8: ...14 15 4 6 8 12 20 4 6 8 10 25 4 4 6 10 30 3 4 6 8 35 3 4 6 8 40 2 3 4 6 45 2 3 4 6 50 2 3 4 6 55 1 2 3 4 60 Wire Size based on N E C for 60 type copper conductors Table 2 Copper Wire Size lead from th...

Страница 9: ...6 24 38 1244 25 40 1169 27 03 1153 27 40 1089 29 01 1030 30 67 961 32 88 863 36 61 Tap T3 1525 20 72 1499 21 08 1448 21 82 1391 22 71 1338 23 61 1264 25 00 1221 25 88 1159 27 26 Tap T4 1641 19 25 1590...

Страница 10: ...the low voltage wires are securely connected to the correct leads on the low voltage terminal strip Verify that the outdoor fan turns freely Verify that the power supply branch circuit overcurrent pr...

Страница 11: ...the circulating air blower and the outdoor fan are pre lubricated at the factory No further oiling is required for the life of this product Refrigerant Charging WARNING Single Packaged Air Conditione...

Страница 12: ...stem contains refrigerant under high pressure Always use safe and environmen tallysoundmethodswhenhandlingrefrigeranthandling or servicing the unit Review the factory literature and safety warnings pr...

Страница 13: ...ove refrigerant if above curve Add refrigerant if below curve Figure 8 Charging Chart for 5 Ton Units 75 80 85 90 95 100 105 110 115 120 125 130 Liquid Pressure psig Liquid Temperature F P8SE X48 Char...

Страница 14: ...hipping weight Top View 24 9 13 5 16 12 13 3 13 5 16 12 CG A 47 5 75 NPT Female Drain Connector B DOWNFLOW SUPPLY DUCT OPENING DOWNFLOW RETURN DUCT OPENING 23 5 Back View 131 2 16 13 7 10 13 1 2 16 12...

Страница 15: ...1 Stage Cool 1 Stage Heat Typical Wiring Field Supplied for 2 Stage Cool 1 Stage Heat with an Optional Outdoor Thermostat Figure 10 Typical Air Conditioner Thermostat Connections 208 230V Optional Ou...

Страница 16: ...de plus de 150V a la terre 711034o 1 2 3 4 5 6 7 8 9 5 4 3 2 1 9 8 7 6 5 4 3 2 1 9 8 7 6 5 4 3 2 1 9 8 7 6 5 4 3 2 1 9 8 7 6 3 AMP FUSE CCH COMPRESSOR OUTDOOR FAN MOTOR HEATER PLUG BLOWER RELAY DUAL C...

Страница 17: ...17...

Страница 18: ...18...

Страница 19: ...19...

Страница 20: ...____________ INSTALLER NAME CITY__________________________________ STATE________________________ Unit Installed Minimum clearances shown on page 4 YES NO Has the owner s information been reviewed with...

Отзывы: