Nortek P8SE Series Скачать руководство пользователя страница 4

4

•  The  unit  should  be  located  with  consideration  of 

minimizing the length of the supply and return ducts. If 

practical, place the air conditioner and its ducts in an 

area where they will be shaded from the afternoon sun, 

when the heat load is greatest.

•  The length of the supply and return ducts should be 

kept to a minimum with no sharp radius bends.

•  Overhead  obstructions,  poorly  ventilated  areas,  and 

areas subject to accumulation of debris should be 

avoided. The hot condenser air must be discharged 

up and away from the home, and if possible, in a 

direction with the prevailing wind. Do not place the unit 

in a confined space. See 

Figure 9, (page 14)

 for unit 

dimensions.

•  Sufficient  clearance  for  unobstructed  airflow  through 

the outdoor coil must be maintained in order to achieve 
rated performance.

•  Consideration  should  also  be  given  to  availability  of 

electric power, service access, noise, and shade.

Minimum clearance requirements

P8SE units are certified as cooling equipment for outdoor 

installation only. 

Figure 1

 displays the minimum clearances 

to obstructions for downflow and Horizontal discharge.

Units may be installed on Class A, B, or C roof covering 

material when used with bottom supply and return air 

ducts. If using bottom discharge with return air ducts, a 

roof curb must be installed prior to unit installation. See 

Rigging and Hoisting section for setting of the unit.
Sufficient clearance for unobstructed airflow through the 

outdoor coil must be maintained in order to provide room 

for proper servicing and achieve rated performance. See 

Figure 1

 for minimum clearances to obstructions.

Service Access Clearances

Blower access panel side ..........................................36”

Electrical compartment access panel side ................36”

Clearance between overhang & top of unit ...............72”

Clearance around condenser coil area to wall or

shrubs (excludes duct panel side) .............................36”

Duct Clearances

Supply and return air ducts .........................................0”

Duct connection side ...................................................0”

air ducts

This unit is designed only for use with a supply and return 

duct. Air ducts should be installed in accordance with the 

standards of the National Fire Protection Association 

Standard for Installation of Air Conditioning Systems 

(NFPA 90A), Standard for Installation of Residence Type 

Warm Air Heating and Air Conditioning Systems (NFPA 

90B), and all applicable local codes. NFPA publications 

are avaialable by writing to: National Fire Protection 

Association, Batterymarch Park, Quincy, ME 02269 or 

visit www.NFPA.org on the web.

•  Design the duct work according to methods described 

by the Air Conditioning Contractors of America (ACCA). 

•  The ducts must be properly sized and not exceed .2” 

W.C. pressure drop at 400 scfm per nominal ton of 

cooling capacity.

general inForMation

Packaged air conditioner units are ready for easy and 

immediate installation on rooftops or ground level slabs. 

Units are shipped for horizontal duct connections and 

can be easily converted for downflow applications. This 

air conditioner is designed only for outdoor installations.
This unit has been designed and tested for capacity 

and efficiency in accordance with AHRI Standards. This 

unit will provide many years of safe and dependable 

comfort, providing it is properly installed and maintained. 

With regular maintenance, this unit will operate reliably 

year after year. Abuse, improper use, and/or improper 

maintenance can shorten the life of the appliance and 

create unsafe hazards.

before You install this unit

  The cooling load of the area to be conditioned must be 

calculated and a system of the proper capacity selected. 

It is recommended that the area to be conditioned be 

completely insulated and vapor sealed.

  Check the electrical supply and verify the power supply 

is adequate for unit operation. If there is any question 

concerning the power supply, contact the local power 

company.

  All units are securely packed at the time of shipment and 

upon arrival should be carefully inspected for damage 

prior to installing the equipment at the job site. Verify 

coil fins are straight. If necessary, comb fins to remove 

flattened or bent fins. Claims for damage (apparent or 

concealed) should be filed immediately with the carrier.

  Please consult your dealer for maintenance information 

and availability of maintenance contracts. Please read 

all instructions before installing the unit.

locating the air conditioner

•  Survey the job site to determine the best location for 

mounting the outdoor unit. Select a solid, level position, 

preferably on a concrete slab, slightly above the grade 

level, and parallel to the home. If possible, select a site 

for the unit that is as close as possible to the proposed 

return grille location. DO NOT PLACE UNIT UNDER 

THE HOME.

Minimum Required 

Clearances to Obstructions

0"

36"

36"

36"

TOP OF UNIT

TO

 BE

UNOBSTR

UCTED

36” For Coil Only

Figure 1. clearance requirements

Содержание P8SE Series

Страница 1: ...n sense plays an important role as well Pay attention to all safety warnings and any other special notes highlighted in the manual Improper installation of the furnace or failure to follow safety warn...

Страница 2: ...ced 3 Phase Supply Voltage 8 Grounding 8 Thermostat Connections 8 Blower Speed 9 Fixed Torque ECM Motor 9 Optional Outdoor Thermostat 10 Optional Electric Heater Kits 10 START UP SYSTEM CHECK 10 Pre S...

Страница 3: ...nit uses refrigerant R 410A DO NOT use any other refrigerant in this unit Use of another refrigerant may damage the unit WARNING The safety information listed below must be followed during the install...

Страница 4: ...des NFPA publications are avaialable by writing to National Fire Protection Association Batterymarch Park Quincy ME 02269 or visit www NFPA org on the web Design the duct work according to methods des...

Страница 5: ...filter pressure drop must not exceed 0 08 inches WC When replacing the air filters a suitable air filter must be installed upstream of the evaporator coil of the return air system DownflowInstallatio...

Страница 6: ...return air panel Hint Loosen the unit s top panel screws near the top edge of the access panel The access panel was designed to be captured underneath the top panel 2 Slide the first filter between bo...

Страница 7: ...Make all electrical connections in accordance with all applicable codes and ordinances Overcurrent protection must be provided at the branch circuit distribution panel and sized as shown on the unit...

Страница 8: ...14 15 4 6 8 12 20 4 6 8 10 25 4 4 6 10 30 3 4 6 8 35 3 4 6 8 40 2 3 4 6 45 2 3 4 6 50 2 3 4 6 55 1 2 3 4 60 Wire Size based on N E C for 60 type copper conductors Table 2 Copper Wire Size lead from th...

Страница 9: ...6 24 38 1244 25 40 1169 27 03 1153 27 40 1089 29 01 1030 30 67 961 32 88 863 36 61 Tap T3 1525 20 72 1499 21 08 1448 21 82 1391 22 71 1338 23 61 1264 25 00 1221 25 88 1159 27 26 Tap T4 1641 19 25 1590...

Страница 10: ...the low voltage wires are securely connected to the correct leads on the low voltage terminal strip Verify that the outdoor fan turns freely Verify that the power supply branch circuit overcurrent pr...

Страница 11: ...the circulating air blower and the outdoor fan are pre lubricated at the factory No further oiling is required for the life of this product Refrigerant Charging WARNING Single Packaged Air Conditione...

Страница 12: ...stem contains refrigerant under high pressure Always use safe and environmen tallysoundmethodswhenhandlingrefrigeranthandling or servicing the unit Review the factory literature and safety warnings pr...

Страница 13: ...ove refrigerant if above curve Add refrigerant if below curve Figure 8 Charging Chart for 5 Ton Units 75 80 85 90 95 100 105 110 115 120 125 130 Liquid Pressure psig Liquid Temperature F P8SE X48 Char...

Страница 14: ...hipping weight Top View 24 9 13 5 16 12 13 3 13 5 16 12 CG A 47 5 75 NPT Female Drain Connector B DOWNFLOW SUPPLY DUCT OPENING DOWNFLOW RETURN DUCT OPENING 23 5 Back View 131 2 16 13 7 10 13 1 2 16 12...

Страница 15: ...1 Stage Cool 1 Stage Heat Typical Wiring Field Supplied for 2 Stage Cool 1 Stage Heat with an Optional Outdoor Thermostat Figure 10 Typical Air Conditioner Thermostat Connections 208 230V Optional Ou...

Страница 16: ...de plus de 150V a la terre 711034o 1 2 3 4 5 6 7 8 9 5 4 3 2 1 9 8 7 6 5 4 3 2 1 9 8 7 6 5 4 3 2 1 9 8 7 6 5 4 3 2 1 9 8 7 6 3 AMP FUSE CCH COMPRESSOR OUTDOOR FAN MOTOR HEATER PLUG BLOWER RELAY DUAL C...

Страница 17: ...17...

Страница 18: ...18...

Страница 19: ...19...

Страница 20: ...____________ INSTALLER NAME CITY__________________________________ STATE________________________ Unit Installed Minimum clearances shown on page 4 YES NO Has the owner s information been reviewed with...

Отзывы: