background image

5

AIR CONDITIONER INSTALLATION

General Information

The JS5BD series air conditioner is designed only for 
outdoor rooftop or ground level installations. This unit has 
been tested for capacity and effi ciency in accordance with 
A.H.R.I. Standards and will provide many years of safe 
and dependable comfort, providing it is properly installed 
and maintained. Abuse, improper use, and/or improper 
maintenance can shorten the life of the appliance and 
create unsafe hazards.

To achieve optimum performance and minimize equipment 
failure, it is recommended that periodic maintenance be 
performed on this unit. The ability to properly perform 
maintenance on this equipment requires certain 
mechanical skills and tools.

Before You Install this Unit

  The cooling load of the area to be conditioned must be 

calculated and a system of the proper capacity selected. 
It is recommended that the area to be conditioned be 
completely insulated and vapor sealed.

  Check the electrical supply and verify the power supply 

is adequate for unit operation. The system must be wired 
and provided with circuit protection in accordance with 
local building codes. If there is any question concerning 
the power supply, contact the local power company.

  The indoor section (air handler, furnace, etc) should be 

installed before routing the refrigerant tubing. Refer to 
the indoor unit's installation instructions for installation 
details.

  All units are securely packed at the time of shipment and 

upon arrival should be carefully inspected for damage 
prior to installing the equipment at the job site. Verify 
coil fi ns are straight. If necessary, comb fi ns to remove 
fl attened or bent fi ns. Claims for damage (apparent or 
concealed) should be fi led immediately with the carrier.

  Please consult your dealer for maintenance information 

and availability of maintenance contracts. Please read 
all instructions before installing the unit.

18"

18"

18"

18"

DO NOT

OBSTRUCT

TOP OF UNIT

Figure 2. Clearance Requirements

Locating the Air Conditioner

•  Survey the job site to determine the best location for 

mounting the outdoor unit. See Figure 5 (page 12) for 
unit dimensions.

•  Overhead obstructions, poorly ventilated areas, and 

areas subject to accumulation of debris should be 
avoided.

• Suffi cient clearance for unobstructed airfl ow through the 

outdoor coil must be maintained in order to achieve rated 
performance. See Figure 2 for minimum clearances to 
obstructions.

•  Consideration should be given to availability of electric 

power, service access, noise, and shade.

Packaging Removal
NOTE: 

To prevent damage to the tubing connections, 

carefully remove the carton and user’s manual from the 
equipment. Discard the shipping carton.

Ground Level

Ground level installations must be located according to 
local building codes or ordinances and these requirements:
•  Clearances must be in accordance with those shown 

in Figure 2.

•  A suitable mounting pad (Figure 3) must be provided 

and separate from the building foundation. The pad 
must be level and strong enough to support the weight 
of the unit. The slab height must be a minimum of 2” 
(5 cm) above grade and with adequate drainage.

2”

Figure 3. Ground Level Installation

Содержание JS5BD

Страница 1: ...minate the problem call your servicing contractor The Installation Instructions are primarily intended to assist qualified individuals experiencedintheproperinstallationofthisappliance Somelocalcodesr...

Страница 2: ...nits 13 Figure 6 JS5BD 024KB 2 Ton Units 14 Figure 7 JS5BD 030KB 2 5 Ton Units 14 Figure 8 JS5BD 036KB 3 Ton Units 15 Figure 9 JS5BD 042 3 5 Ton Units 15 Figure 10 JS5BD 048 4 Ton Units 16 Figure 11 J...

Страница 3: ...tem will not operate regardless of the temperature selector setting Figure 1 Digital Thermostat Fan Mode Temperature Selector System Mode AIR CONDITIONER MAINTENANCE Propermaintenanceismostimportantto...

Страница 4: ...s unit uses refrigerant R 22 DO NOT use any other refrigerant in this unit Use of another refrigerant will damage the unit WARNING The information listed below must be followed during the installation...

Страница 5: ...be carefully inspected for damage prior to installing the equipment at the job site Verify coil fins are straight If necessary comb fins to remove flattened or bent fins Claims for damage apparent or...

Страница 6: ...able local codes and ordinances and with the current revision of the National Electric Code ANSI NFPA 70 For Canadian installations the electrical connections and grounding shall comply with the curre...

Страница 7: ...ical Code Use the grounding lug provided in the control box for grounding the unit Thermostat Connections Thermostatconnectionsshouldbemadeinaccordance with the instructions supplied with the thermost...

Страница 8: ...thermostat s system mode to HEAT and the temperature mode above room temperature 2 Verify the optional heating equipment furnace or electric heat and indoor blower energize Feel the air being circula...

Страница 9: ...s greater than therequiredliquidrefrigerantpressuredeterminedin Step 3 then there is too much charge in the system Remove refrigerant and repeat Steps 1 through 3 until the system is correctly charged...

Страница 10: ...42 208 144 223 145 84 182 146 195 148 211 148 225 150 239 151 86 199 151 213 153 227 154 241 156 256 157 88 216 157 230 158 243 160 258 161 272 163 90 220 160 233 162 247 164 260 165 274 166 92 237 16...

Страница 11: ...180 130 196 137 212 144 78 165 130 180 137 198 142 214 149 230 156 80 184 140 199 147 216 153 232 160 248 167 82 203 151 218 158 234 164 250 171 266 178 84 206 154 222 161 237 168 252 175 268 182 86 2...

Страница 12: ...202 156 212 155 222 154 83 197 159 205 160 214 159 224 158 234 158 85 209 163 217 163 226 163 236 162 246 162 87 221 167 229 167 238 166 248 166 258 165 89 224 170 233 171 242 170 250 170 260 169 91 2...

Страница 13: ...160 217 160 78 175 166 189 166 204 165 219 165 234 165 80 193 169 207 170 221 169 236 169 251 169 82 210 173 224 173 238 173 253 173 267 173 84 213 177 227 177 241 177 255 177 269 177 86 231 181 245 1...

Страница 14: ...d refrigerant when below curve JS5BD 024KB SERIES CHARGING CHART Remove refrigerant when above curve Figure 7 Charging Chart for 2 5 Ton Units with Microchannel Coil 140 160 180 200 220 240 260 280 30...

Страница 15: ...sure psig Add refrigerant when below curve JS5BD 036KB SERIES CHARGING CHART Remove refrigerant when above curve Figure 9 Charging Chart for 3 5 Ton Units 140 160 180 200 220 240 260 280 300 320 340 3...

Страница 16: ...Add refrigerant when below curve JS5BD 048 SERIES CHARGING CHART Remove refrigerant when above curve Figure 11 Charging Chart for 5 Ton Units 140 160 180 200 220 240 260 280 300 320 340 360 380 400 7...

Страница 17: ...it If desired ASCT is factory installed on select models only or may be field installed as shown using manufacturer s approved kit If not present connect Yellow and Black wires per Note 6 8 DO NOT use...

Страница 18: ...18...

Страница 19: ...19...

Страница 20: ...7092410 Replaces 7092340 Specifications illustrations subject to change without notice or incurring obligations O Fallon MO Printed in U S A 08 10 709241...

Отзывы: