START UP & ADJUSTMENTS

Pre-Start Check List

  Verify the indoor unit is level and allows proper 

condensate drainage.

  Verify the outdoor coil and top of the unit are free from 

obstructions and debris, and all equipment access/
control panels are in place.

  Verify air fi lters are cleaned and properly installed.

  Verify duct work is sealed to prevent air leakage. 

  Verify line voltage power leads are securely connected 

and the unit is properly grounded.

   Verify low voltage wires are securely connected to the 

correct leads on the low voltage terminal strip.

  Verify power supply branch circuit overcurrent protection 

is sized properly.

  Verify the thermostat is wired correctly.

Start-Up Procedures

The thermostat's function mode should be set to OFF and 
the fan mode should be set to AUTO. Close all electrical 
disconnects to energize the system.

Air Circulation - Indoor Blower
1.  Set the thermostat system mode on OFF and the fan 

mode to ON.

2.  Verify the blower runs continuously. Check the air 

delivery at the supply registers and adjust register 
openings for balanced air distribution. If insuffi cient 
air is detected, examine ductwork for leaks or 
obstructions.

3.  Set the thermostat fan mode to AUTO and verify the 

blower stops running.

System Cooling
1.  Set the thermostat’s system mode to COOL and the 

fan mode to AUTO. Gradually lower the thermostat 
temperature setpoint below room temperature and 
verify the outdoor unit and indoor blower energize.

2.  Verify blower wheel is spinning in direction indicated 

by arrow. Feel the air being circulated by the indoor 
blower and verify that it is cooler than ambient 
temperature. Listen for any unusual noises. If unusual 
sounds occur, determine the source of the noise and 
correct as necessary.

3.  Verify HI and LO refrigerant pressures.
4.  Allow the system to operate for several minutes 

and then set the temperature selector above room 
temperature. Verify the fan and compressor cycle off 
with the thermostat. 

NOTE:

 The blower should also 

stop unless fan mode is set to the ON position.

System Heating (optional)
1.  Set the thermostat's system mode to HEAT and the 

temperature mode above room temperature.

2.  Verify the optional heating equipment (furnace or 

electric heat) and indoor blower energize. Feel the air 
being circulated by the indoor blower and verify that 
it is warmer than ambient temperature. Listen for any 
unusual noises. If unusual sounds occur, determine 
the source of the noise and correct as necessary.

Refrigerant Charging

 WARNING:

JS5BD Split System Air Conditioners leave the 
factory with a nitrogen holding charge. 

DO NOT 

operate any unit while it contains a Nitrogen 
holding charge. Doing so may damage the 
units compressor. 

Follow these charging 

instructions for maximum unit performance and 
effi ciency. Some local codes require licensed 
installation/service personnel to service this 
type of equipment. Refrigerant charging must be 
done by qualifi ed personnel familiar with safe and 
environmentally responsible refrigerant handling 
procedures. Under no circumstances should 
the owner attempt to install and/or service this 
equipment. Failure to comply with this warning 
could result in property damage, personal injury, 
or death.

To properly charge these units:
1.  Read all Installation Instructions fi rst.
2.  Complete any brazing operations. (e.g. Split system 

line-sets)

3.  Leak check and evacuate the whole system using 

proper methods.

4.  Purge the nitrogen holding charge.
5.  Evacuate the unit to 350-500 microns.
6.  Allow the unit to remain under vacuum for at least 30 

min.

7.  Weigh-In the proper amount of new (or reclaimed) 

R-22 refrigerant. Refer to the units rating label or see 
Table 4 to determine the correct amount of charge.

•  Refrigerant charging charts are applicable only to 

matched assemblies of NORDYNE equipment and 
listed airfl ows for the indoor coil. Refer to Figures 5 - 
11 or Tables 5-11 (pages 10 - 16) for correct system 
charging.

•  JS5BD outdoor units with indoor coils not listed are 

not recommended. Deviations from rated airfl ows or 
non-listed combinations may require modifi cation to the 

Table 4. Refrigerant Metering Device

for 13 SEER Split System Air Conditioner 

Model

Number

Restrictor Bore

Size (inches)

System charge

R-22 (oz.)

1.5 ton

0.053

78

2.0 ton (-KB)

0.060

53

2.5 ton (-KB)

0.065

56

3.0 ton (-KB)

0.075

68

3.5 ton

0.078

122

4.0 ton

0.089

126

5.0 ton

0.099

160

Содержание JS5BD

Страница 1: ...minate the problem call your servicing contractor The Installation Instructions are primarily intended to assist qualified individuals experiencedintheproperinstallationofthisappliance Somelocalcodesr...

Страница 2: ...nits 13 Figure 6 JS5BD 024KB 2 Ton Units 14 Figure 7 JS5BD 030KB 2 5 Ton Units 14 Figure 8 JS5BD 036KB 3 Ton Units 15 Figure 9 JS5BD 042 3 5 Ton Units 15 Figure 10 JS5BD 048 4 Ton Units 16 Figure 11 J...

Страница 3: ...tem will not operate regardless of the temperature selector setting Figure 1 Digital Thermostat Fan Mode Temperature Selector System Mode AIR CONDITIONER MAINTENANCE Propermaintenanceismostimportantto...

Страница 4: ...s unit uses refrigerant R 22 DO NOT use any other refrigerant in this unit Use of another refrigerant will damage the unit WARNING The information listed below must be followed during the installation...

Страница 5: ...be carefully inspected for damage prior to installing the equipment at the job site Verify coil fins are straight If necessary comb fins to remove flattened or bent fins Claims for damage apparent or...

Страница 6: ...able local codes and ordinances and with the current revision of the National Electric Code ANSI NFPA 70 For Canadian installations the electrical connections and grounding shall comply with the curre...

Страница 7: ...ical Code Use the grounding lug provided in the control box for grounding the unit Thermostat Connections Thermostatconnectionsshouldbemadeinaccordance with the instructions supplied with the thermost...

Страница 8: ...thermostat s system mode to HEAT and the temperature mode above room temperature 2 Verify the optional heating equipment furnace or electric heat and indoor blower energize Feel the air being circula...

Страница 9: ...s greater than therequiredliquidrefrigerantpressuredeterminedin Step 3 then there is too much charge in the system Remove refrigerant and repeat Steps 1 through 3 until the system is correctly charged...

Страница 10: ...42 208 144 223 145 84 182 146 195 148 211 148 225 150 239 151 86 199 151 213 153 227 154 241 156 256 157 88 216 157 230 158 243 160 258 161 272 163 90 220 160 233 162 247 164 260 165 274 166 92 237 16...

Страница 11: ...180 130 196 137 212 144 78 165 130 180 137 198 142 214 149 230 156 80 184 140 199 147 216 153 232 160 248 167 82 203 151 218 158 234 164 250 171 266 178 84 206 154 222 161 237 168 252 175 268 182 86 2...

Страница 12: ...202 156 212 155 222 154 83 197 159 205 160 214 159 224 158 234 158 85 209 163 217 163 226 163 236 162 246 162 87 221 167 229 167 238 166 248 166 258 165 89 224 170 233 171 242 170 250 170 260 169 91 2...

Страница 13: ...160 217 160 78 175 166 189 166 204 165 219 165 234 165 80 193 169 207 170 221 169 236 169 251 169 82 210 173 224 173 238 173 253 173 267 173 84 213 177 227 177 241 177 255 177 269 177 86 231 181 245 1...

Страница 14: ...d refrigerant when below curve JS5BD 024KB SERIES CHARGING CHART Remove refrigerant when above curve Figure 7 Charging Chart for 2 5 Ton Units with Microchannel Coil 140 160 180 200 220 240 260 280 30...

Страница 15: ...sure psig Add refrigerant when below curve JS5BD 036KB SERIES CHARGING CHART Remove refrigerant when above curve Figure 9 Charging Chart for 3 5 Ton Units 140 160 180 200 220 240 260 280 300 320 340 3...

Страница 16: ...Add refrigerant when below curve JS5BD 048 SERIES CHARGING CHART Remove refrigerant when above curve Figure 11 Charging Chart for 5 Ton Units 140 160 180 200 220 240 260 280 300 320 340 360 380 400 7...

Страница 17: ...it If desired ASCT is factory installed on select models only or may be field installed as shown using manufacturer s approved kit If not present connect Yellow and Black wires per Note 6 8 DO NOT use...

Страница 18: ...18...

Страница 19: ...19...

Страница 20: ...7092410 Replaces 7092340 Specifications illustrations subject to change without notice or incurring obligations O Fallon MO Printed in U S A 08 10 709241...

Отзывы: