background image

9

 CAUTION:

The unit should never be operated without a 
fi lter in the return air system. Replace disposable 
fi lters with the same type and size.

•  Do not attempt to add additional oil to motors 

unequipped with oil tubes. The compressor is 
hermetically sealed at the factory and does not require 
lubrication.

REPLACEMENT PARTS

Replacement parts are available through all Nordyne distributors. 
Please have the complete model and serial number of the unit 
when ordering replacement parts.

ELECTRICAL:

Capacitors

Temperature Limit Switches

Compressors

Thermostats

Contactors

Time Delay Relays

Pressure Switches

Transformers

Relays

MOTORS:

Blower Motor

Fan Motor

COMPONENTS:

Blower Assembly

Fan Grille

Cabinet Panels

Filter/Driers

Expansion Valves

expansion device and refrigerant charging procedures 
for proper and effi cient system operation.

•  The refrigerant charge can be checked and adjusted 

through the service ports provided external to the 
outdoor unit. Use only gage line sets which have a 
“Schrader” depression device present to actuate the 
valve.

Charging an R-22 system in AC mode at outdoor tem-
peratures above 55° F for optimized sub-cooling of 10° 
F - 12° F.
1.  With the system operating at steady-state, measure 

the liquid refrigerant pressure (in psig) at the outdoor 
unit service valve.

2.  Measure the liquid refrigerant temperature (in 

Fahrenheit) at the service valve.

3.  Determine the required liquid refrigerant pressure 

from Table 4.

• If the pressure measured in Step 1 is greater than 

the required liquid refrigerant pressure determined in 
Step 3, then there is too much charge in the system. 
Remove refrigerant and repeat Steps 1 through 3 
until the system is correctly charged.

• If the pressure measured in Step 1 is less than the 

required liquid refrigerant pressure determined in 
Step 3, there is too little charge in the system. Add 
refrigerant and repeat Steps 1 through 3 until the 
system is correctly charged.

Figure 4. Unit Dimensions

Model Number

JS5BD-

Height

-H-

Width

-W-

Depth

-D-

024

23"

22 3/4"

22 3/4"

D

W

H

DO NOT OBSTRUCT TOP OF UNIT

Allow adequate clearance for airflow

AIR CONDITIONER MAINTENANCE

 WARNING:

To prevent electrical shock, personal injury, or 
death, disconnect all electrical power to the unit 
before performing any maintenance or service. 
The unit may have more than one electrical 
supply.

Proper maintenance is important to achieve optimum 
performance from the air conditioner. The ability to properly 
perform maintenance on this equipment requires certain 
mechanical skills and tools. If you do not possess these 
skills, contact your dealer for maintenance. Consult your 
local dealer about the availability of maintenance contracts. 
Routine maintenance should include the following:
•  Inspect and clean or replace air fi lters at the beginning 

of each heating and cooling season, or more frequently 
if required.

•  Inspect the condensate drain and outdoor coil at the 

beginning of each cooling season. Remove any debris. 
Clean the outdoor coil and louvers as necessary using 
a mild detergent and water. Rinse thoroughly with water.

•  Inspect the electrical connections for tightness at the 

beginning of each heating and cooling season. Service 
as necessary.

Содержание JS5BD

Страница 1: ...minate the problem call your servicing contractor The Installation Instructions are primarily intended to assist qualified individuals experiencedintheproperinstallationofthisappliance Somelocalcodesr...

Страница 2: ...nits 13 Figure 6 JS5BD 024KB 2 Ton Units 14 Figure 7 JS5BD 030KB 2 5 Ton Units 14 Figure 8 JS5BD 036KB 3 Ton Units 15 Figure 9 JS5BD 042 3 5 Ton Units 15 Figure 10 JS5BD 048 4 Ton Units 16 Figure 11 J...

Страница 3: ...tem will not operate regardless of the temperature selector setting Figure 1 Digital Thermostat Fan Mode Temperature Selector System Mode AIR CONDITIONER MAINTENANCE Propermaintenanceismostimportantto...

Страница 4: ...s unit uses refrigerant R 22 DO NOT use any other refrigerant in this unit Use of another refrigerant will damage the unit WARNING The information listed below must be followed during the installation...

Страница 5: ...be carefully inspected for damage prior to installing the equipment at the job site Verify coil fins are straight If necessary comb fins to remove flattened or bent fins Claims for damage apparent or...

Страница 6: ...able local codes and ordinances and with the current revision of the National Electric Code ANSI NFPA 70 For Canadian installations the electrical connections and grounding shall comply with the curre...

Страница 7: ...ical Code Use the grounding lug provided in the control box for grounding the unit Thermostat Connections Thermostatconnectionsshouldbemadeinaccordance with the instructions supplied with the thermost...

Страница 8: ...thermostat s system mode to HEAT and the temperature mode above room temperature 2 Verify the optional heating equipment furnace or electric heat and indoor blower energize Feel the air being circula...

Страница 9: ...s greater than therequiredliquidrefrigerantpressuredeterminedin Step 3 then there is too much charge in the system Remove refrigerant and repeat Steps 1 through 3 until the system is correctly charged...

Страница 10: ...42 208 144 223 145 84 182 146 195 148 211 148 225 150 239 151 86 199 151 213 153 227 154 241 156 256 157 88 216 157 230 158 243 160 258 161 272 163 90 220 160 233 162 247 164 260 165 274 166 92 237 16...

Страница 11: ...180 130 196 137 212 144 78 165 130 180 137 198 142 214 149 230 156 80 184 140 199 147 216 153 232 160 248 167 82 203 151 218 158 234 164 250 171 266 178 84 206 154 222 161 237 168 252 175 268 182 86 2...

Страница 12: ...202 156 212 155 222 154 83 197 159 205 160 214 159 224 158 234 158 85 209 163 217 163 226 163 236 162 246 162 87 221 167 229 167 238 166 248 166 258 165 89 224 170 233 171 242 170 250 170 260 169 91 2...

Страница 13: ...160 217 160 78 175 166 189 166 204 165 219 165 234 165 80 193 169 207 170 221 169 236 169 251 169 82 210 173 224 173 238 173 253 173 267 173 84 213 177 227 177 241 177 255 177 269 177 86 231 181 245 1...

Страница 14: ...d refrigerant when below curve JS5BD 024KB SERIES CHARGING CHART Remove refrigerant when above curve Figure 7 Charging Chart for 2 5 Ton Units with Microchannel Coil 140 160 180 200 220 240 260 280 30...

Страница 15: ...sure psig Add refrigerant when below curve JS5BD 036KB SERIES CHARGING CHART Remove refrigerant when above curve Figure 9 Charging Chart for 3 5 Ton Units 140 160 180 200 220 240 260 280 300 320 340 3...

Страница 16: ...Add refrigerant when below curve JS5BD 048 SERIES CHARGING CHART Remove refrigerant when above curve Figure 11 Charging Chart for 5 Ton Units 140 160 180 200 220 240 260 280 300 320 340 360 380 400 7...

Страница 17: ...it If desired ASCT is factory installed on select models only or may be field installed as shown using manufacturer s approved kit If not present connect Yellow and Black wires per Note 6 8 DO NOT use...

Страница 18: ...18...

Страница 19: ...19...

Страница 20: ...7092410 Replaces 7092340 Specifications illustrations subject to change without notice or incurring obligations O Fallon MO Printed in U S A 08 10 709241...

Отзывы: