HEATER KIT INSTALLATION INSTRUCTIONS

IMPORTANT

ATTENTION INSTALLERS:

These instructions are primarily intended to assist qualified individuals experienced in the proper 
installation of this appliance. Some local codes require licensed installation/service personnel 
for this type of equipment. All installations must be in accordance with these instructions and 
with all applicable national and local codes and standards.
Please read all instructions carefully before starting the installation. Return these instructions 
to the customer’s package for future reference.

DO NOT DESTROY. PLEASE READ CAREFULLY AND KEEP IN A SAFE PLACE FOR FUTURE REFERENCE.

NOTE: Model H9HK035Q-21 shown.

H9HK SERIES HEATER KITS FOR INSTALLATION IN 208/240V AND 480V 

LIGHT COMMERCIAL PACKAGED AIR CONDITIONERS

Revision:  CP-H9HK (05-20) 1012566-B

Supersedes:  CP-H9HK (08-19) PN1012566R1

Содержание 1011669

Страница 1: ...with these instructions and with all applicable national and local codes and standards Please read all instructions carefully before starting the installation Return these instructions to the customer...

Страница 2: ...ons are primarily intended to assist qualified individuals experienced in the properinstallationofthesecomponents Somelocalcodes may require licensed installation service personnel for this type of eq...

Страница 3: ...and DO NOT serve as a unit disconnect The circuit breakers DO NOT provide over current protection of the supply wiring Whether or not circuit breakers are used in the units protection and disconnect...

Страница 4: ...supply grille 1 Remove Compressor Access panel See Figure 2 foam wire guards for later use See 4 Install the DIN rail mounting bracket inside of the unit and tightly secure it with two screws See NOT...

Страница 5: ...m flange of the element mounting plate to the bottom pan and then one in the rear of the element assembly support bracket as shown in and 11 Route all wiring out the two wire passage holes and foam wi...

Страница 6: ...0Q 21 1011675 2 Figure 18 210 F 35 H9HK035Q 21 1011678 2 Figure 18 210 F 6 7 5 10 and 12 5 ton 460V 3PH P7TQ 072 090 120 150 D 9 H9HK009S 01 1011670 NONE Figure 15 155 F 18 H9HK018S 01 1011673 NONE Fi...

Страница 7: ...49 4 58 5 30 35 50 60 UNIT EQUIPPED WITH 3 HP 2 SPEED MOTOR HEATER KIT 3 HP 2 SPEED MOTOR HEATER KIT POWER EXHAUST COOLING TONNAGE UNIT VOLTAGE MCA MOP MCA MOP 9 KW 18 KW 30 KW 35 KW 9 KW 18 KW 30 KW...

Страница 8: ...7 40 31 7 40 31 7 40 31 7 40 14 9 15 27 1 30 43 3 45 52 3 60 HIGH STATIC DRIVE OPTIONAL 3 HP ECM MOTOR 6 208 240 33 7 50 33 7 50 33 7 50 33 7 50 23 5 27 1 30 30 45 4 52 3 50 60 75 0 86 6 80 90 90 7 1...

Страница 9: ...POWER SUPPLY L1 L2 L3 To Cooling Circuit Power Supply Disconnect Main Control Panel 3 Pole Terminal Block To Cooling Components and Control L1 L2 L3 L1 L2 L3 Electric Heat 3 Pole Terminal Block Elect...

Страница 10: ...BE REPLACED WITH WIRING MATERIAL OF THE 1 IF ANY OF THE ORIGINAL WIRE AS SUPPLIED WITH THE UNIT MUST BE NOTES 2 USE COOPER CONDUCTORS WITH A MINIMUM TEMPERATURE RATING OF 60 C FOR SUPPLY CONNECTIONS 1...

Страница 11: ...T BE REPLACED WITH WIRING MATERIAL OF THE 1 IF ANY OF THE ORIGINAL WIRE AS SUPPLIED WITH THE UNIT MUST BE NOTES 2 USE COOPER CONDUCTORS WITH A MINIMUM TEMPERATURE RATING OF 60 C FOR SUPPLY CONNECTIONS...

Страница 12: ...OF THE ORIGINAL WIRE AS SUPPLIED WITH THE UNIT MUST BE NOTES 2 USE COOPER CONDUCTORS WITH A MINIMUM TEMPERATURE RATING OF 60 C FOR SUPPLY CONNECTIONS 1012105A Replaces 10121050 05 17 18 kW 1 Stage 20...

Страница 13: ...RING MATERIAL OF THE 1 IF ANY OF THE ORIGINAL WIRE AS SUPPLIED WITH THE UNIT MUST BE NOTES 2 USE COOPER CONDUCTORS WITH A MINIMUM TEMPERATURE RATING OF 60 C FOR SUPPLY CONNECTIONS 1012106A Replaces 10...

Страница 14: ...HE ORIGINAL WIRE AS SUPPLIED WITH THE UNIT MUST BE NOTES 2 USE COOPER CONDUCTORS WITH A MINIMUM TEMPERATURE RATING OF 60 C FOR SUPPLY CONNECTIONS 1012108A Replaces 10121080 05 17 30 35 kW 1 Stage 208...

Страница 15: ...THE ORIGINAL WIRE AS SUPPLIED WITH THE UNIT MUST BE NOTES 2 USE COOPER CONDUCTORS WITH A MINIMUM TEMPERATURE RATING OF 60 C FOR SUPPLY CONNECTIONS 1012109A Replaces 10121090 05 17 30 35 kW 1 Stage 48...

Страница 16: ...HESE INSTALLATION INSTRUCTIONS WITH THE HOMEOWNER Specifications and illustrations subject to change without notice or incurring obligations 2020 Nortek Global HVAC LLC O Fallon MO All rights reserved...