EasyGrid User Guide
46
Hysteresis
Description
Sets the hysteresis values to exit the condition met
status.
Range
-40°C to 225°C
Logic
Description
Selects the logic used to control the relay.
Range
OR
: Condition is met when ANY of the selected
channels are ABOVE the Setpoint.
AND
: Condition is met when ALL of the selected
channels are ABOVE the Setpoint.
AVERAGE
: Condition is met when the AVERAGE
temperature of the selected channels is ABOVE
the setpoint.
HEATER CONTROL
: Condition is met when the
EasyGrid Internal temperature is BELOW the
Setpoint.
COOLER CONTROL
: Condition is met when the
EasyGrid Internal temperature is ABOVE the
Setpoint.