EasyGrid User Guide
101
The temperature value is replaced by an Error Code when there is something wrong with the channel.
The error appears on a temperature channel in the different measurement pages.
EasyGrid
Displays
Error
Description
Possible Cause
Possible Solution
Error -
Signal Too Low
(out of range)
Measured temperature is
lower than the minimum
permitted temperature.
Make sure minimum sensor
temperature is greater than -40 °C.
Check the offset value.
Error +
Signal Too High
(out of range)
Measured temperature is
greater than the maximum
permitted temperature.
Make sure maximum sensor
temperature is less than 225 °C.
Check the offset value.
Error 3
Excessive
Back Reflection
Excessive back reflection.
The ratio of reference
signal to reflected signal is
too high.
Clean connectors, check connectors
for scratches.
Error 4
Unknown signal
Incorrect reference.
Make sure sensor is operating
within temperature specifications.
Error 5
Initialization
System is starting up
Wait a few seconds.
Error 6
Signal Shape
Not enough light, due to
bad connections, dirty
connections, weak sensor,
weak light source.
Make sure that all connections are
clean. Make sure sensor is properly
connected.
Error 7
No Signal
Bad connection or broken
cable.
Check all connections and cables
Error 8
No Calibration
Missing calibration or
calibration is unusable.
Return unit to factory for
calibration.
12.2
Resetting to Factory Defaults
For any problem that occurs with your EasyGrid unit, please consult the
Troubleshooting
section of this
manual. If your problem is not listed, then you can perform a reset to factory defaults.
Important
If you press the RESET to factory settings button, you will lose all configuration you have made to the
instrument.
Содержание EasyGrid V1
Страница 1: ...EasyGrid User Guide i Nortech EasyGrid User Guide MAN 00084 R 10 0 ...
Страница 24: ...EasyGrid User Guide 19 6 Hardware Configuration 6 1 Dimensions ...
Страница 97: ...EasyGrid User Guide 92 11 3 Assembly Diagram ...
Страница 99: ...EasyGrid User Guide 94 11 4 1 2 Pre Drilling 11 4 1 3 Using the Knockout Punch ...
Страница 100: ...EasyGrid User Guide 95 11 4 1 4 Cutting the Cable Slot 11 4 1 5 Inserting the Easy Disk ...