EasyGrid User Guide
6
4
First Steps
4.1
Introducing the Nortech EasyGrid
Nortech EasyGrid fiber optic temperature measurement system is designed for real-time monitoring of
transformer hotspots.
It can be configured to have 4 to 18 channels. Modules can be daisy chained to a maximum of 32, which
gives the possibility to have up to 576 channels in a single system. Each unit has multiple serial
interfaces: USB and RS485/RS422. Supported communication protocols are Nortech and MODBUS (RTU
and ASCII). Optional modules are available for IEC 61850, IEC 60870-5-104 and DNP 3.0.
EASYGRID
Data Logging
Life of the Transformer
Relays
0, 8 or 16 form C with user-configurable set points
5A 250VAC; 5A 30VDC
Relay System
1 form C for fail-safe system fault
3A 250VAC; 3A 30VDC
Power requirement
24VDC ±10%, 40W
Number of Channels
4 to 18
Sensing range
-40°C to 225°C
Resolution
0.1°C
Accuracy
±1°C
Sampling Rate
1 Hz
Display
7” TFT
Serial port
USB and RS-485/422
Standard Communication
Protocol
MODBUS (ASCII, RTU)
Nortech Proprietary Protocol
Optional Communication
Protocol
IEC 61850
IEC 61870-5-104
DNP 3.0
Analog output
4-20 mA (or optional 0-1 mA)
Light source
Life of the transformer
Weight
2.9 Kg
Dimension (HxWxD)
300 mm x 235 mm x 98 mm
Relative humidity
95% RH non-condensing
(Tested at 25°C and 55°C)
Warranty
4 years
Note
: All specifications are given at room temperature, except where noted. All technical specifications
are subject to change without notice.
Содержание EasyGrid V1
Страница 1: ...EasyGrid User Guide i Nortech EasyGrid User Guide MAN 00084 R 10 0 ...
Страница 24: ...EasyGrid User Guide 19 6 Hardware Configuration 6 1 Dimensions ...
Страница 97: ...EasyGrid User Guide 92 11 3 Assembly Diagram ...
Страница 99: ...EasyGrid User Guide 94 11 4 1 2 Pre Drilling 11 4 1 3 Using the Knockout Punch ...
Страница 100: ...EasyGrid User Guide 95 11 4 1 4 Cutting the Cable Slot 11 4 1 5 Inserting the Easy Disk ...