![Nortec UL10 Скачать руководство пользователя страница 45](http://html1.mh-extra.com/html/nortec/ul10/ul10_operation-manual_1705753045.webp)
CHARGER / DISCAHRGER UL10
OPERATION MAUNAL
44
©
NorTec Electronics 2014
7.8 Program 111. Commissioning – Pb battery sealed commercial
Stage
name
Maximum
duration
Program
number
111
Operation
number
1
Operation
type
Commissioning
Battery
type
Lead
acid
Manufacturing
process
Gel
/
absorbed
electrolyte
Access
to
valves
unavailable
Battery
type
11
Minimum
battery
capacity
2 Ah
Maximum
battery
capacity
200 Ah
Minimum
battery
voltage
2 V
Maximum
battery
voltage
30 V
Maximum number of batteries
15
Stage 1 (
S1
)
Discharge
Discharge current = x
С
(A)
x= 0.2
Stage 1 (
S1
)
Discharge
Discharge depth V/battery
1.5
Discharge voltage
<1,5 V
Error
message.
Use program
410!
Stage 2 (
S2
)
I-Charge Current
=
x
С
(A)
x= 0,36
8h
Stage 2 (
S2
)
I-Charge Umax
=
V/battery
2.4
8h
Stage 3 (
S3
)
U-Charge
Umax
=
V/battery
2.4
8h
Stage 3 (
S3
)
U-Charge
Ia
=
x
С
(A)
x=
0.04
8h
Note: when the maximum output current of the device is exceeded the maximum time para-
meters change accordingly.
Содержание UL10
Страница 2: ...CHARGER DISCAHRGER UL10 OPERATION MAUNAL NorTec Electronics 2014 1 ...
Страница 3: ...CHARGER DISCAHRGER UL10 OPERATION MAUNAL 2 NorTec Electronics 2014 CHARGER DISCHARGER UL10 ...
Страница 73: ...CHARGER DISCAHRGER UL10 OPERATION MAUNAL 72 NorTec Electronics 2014 switch off the device ...
Страница 74: ...CHARGER DISCAHRGER UL10 OPERATION MAUNAL NorTec Electronics 2014 73 Protection according to DIN 34 ...