CHARGER / DISCAHRGER UL10
OPERATION MAUNAL
40
©
NorTec Electronics 2014
7.4 Program 16. Discharge – Pb battery vented commercial
Stage
name
Maximum
duration
Program
number
16
Operation
number
0
Operation
type
Discharge
Battery
type
Lead
acid
Manufacturing
process
Liquid
electrolyte
Access
to
valves
Open
Battery
type
16
Minimum
battery
capacity
10
Maximum
battery
capacity
400
А
h
Minimum
battery
voltage
2
Maximum
battery
voltage
30
Maximum number of batteries in a battery
15
Stage 1 (
S1
)
Discharge
Current
=
x
С
(A)
x=0.1
max 10 h
Stage 1 (
S1
)
Discharge
Discharge depth V/battery
1.5
Stage 1 (
S1
)
Discharge
Time
t=1min – 999min