CHARGER / DISCAHRGER UL10
OPERATION MAUNAL
36
©
NorTec Electronics 2014
6.9.6 Program 420 stage 6
1
2
3
4
P420:S6:TOPPING CHARGE 2 00:36:38
29.60V 0.40A 4.019AH +060MIN --.-°C
5
6
7
8
9
1
Program number
operation type
4 = maintenance
battery type
20 = enclosed aircraft nickel-cadmium battery.
2
stage number
= Stage 6
3
stage name
= topping charge 2
4
00:36:38
= current time
5
29.6 V
= current battery voltage
6
0.40
А
= current charging current
The charging voltage grows and can exceed 31 V. Because of
this all the batteries reach the final charging voltage. The
capacities of the cells equalize. Extra charging 2 with the
current 0.4
А
(1/10 of the nominal capacity) is supplied into the
cells for 90 minutes.
7
4.019
А
h
The capacity counting continues. The main charging plus extra
charging. The total is 4
А
h + 2 minutes of 0.4
А
= 0.019
А
h; the
total is 4.019
А
h.
8
0060 MIN
Indication of the charging time.
After 75 min a beep sounds.
а
) the voltage of the cells should measured with the measuring
cable.
b) distilled water should be added into the batteries.
Содержание UL10
Страница 2: ...CHARGER DISCAHRGER UL10 OPERATION MAUNAL NorTec Electronics 2014 1 ...
Страница 3: ...CHARGER DISCAHRGER UL10 OPERATION MAUNAL 2 NorTec Electronics 2014 CHARGER DISCHARGER UL10 ...
Страница 73: ...CHARGER DISCAHRGER UL10 OPERATION MAUNAL 72 NorTec Electronics 2014 switch off the device ...
Страница 74: ...CHARGER DISCAHRGER UL10 OPERATION MAUNAL NorTec Electronics 2014 73 Protection according to DIN 34 ...