Connecting Refrigerant Tubing Between 
the Indoor & Outdoor Unit

 CAUTION:

When servicing, cover or seal openings to 

minimize the exposure of the refrigerant system 

to air to prevent accumulation of moisture and 

other contaminants.

After outdoor and indoor unit placement has been 

determined, route refrigerant tubing between the 

equipment in accordance with sound installation practices.

•  When  connecting  refrigerant  linesets  together,  it  is 

recommended that dry nitrogen be flowing through the 

joints during brazing. This will prevent internal oxidation 

and scaling from occurring.

•  Refrigerant tubing should be routed in a manner that 

minimizes the length of tubing and the number of bends 

in the tubing.

•  Refrigerant tubing should be supported in a manner 

that the tubing will not vibrate or abrade during system 

operation.

•  Tubing should be kept clean of foreign debris during 

installation.

•  Every effort should be made by the installer to ensure 

that the field installed refrigerant containing components 

of the system have been installed in accordance with 

these instructions and sound installation practices to 

insure reliable system operation and longevity.

•  The  maximum  recommended  interconnecting 

refrigerant line length is 75 feet, and the vertical elevation 

difference between the indoor and outdoor sections 

should not exceed 20 feet.

•  If  precise  forming  of  refrigerant  lines  is  required,  a 

copper tubing bender is recommended. Avoid sharp 

bends and contact of the refrigerant lines with metal 

surfaces.

•  A  filter  dryer  is  provided  with  the  unit  and  must  be 

installed in the liquid line of the system. If the installation 

replaces a system with a filter dryer already present 

in the liquid line, the filter dryer must be replaced with 

the one supplied with the unit. The filter dryer must be 

installed in strict accordance with the manufacturer’s 

installation instructions.

•  Optional equipment such as liquid line solenoid valves, 

low ambient, etc., should be installed in strict accordance 

with the manufacturer’s installation instructions.

Outdoor Orifice Removal & Installation

The orifice installed in the outdoor unit has been sized 

for use with the most popularly matched indoor units.  

Depending on the indoor coil that the unit is being matched 

with, the outdoor restrictor may need to be changed.  Please 

refer to the Quick Reference Data sheet that is supplied 

with the outdoor unit for more information.

If the outdoor unit has the liquid valve shown in 

Figure 

2

, then the restrictor is located inside the swivel nut 

connection of the liquid valve and not inside the outdoor 

unit’s distributor. Perform steps 1 - 5 if the outdoor restrictor 

needs to be changed.

 CAUTION:

When servicing, cover or seal openings to 

minimize the exposure of the refrigerant system 

to air to prevent accumulation of moisture and 

other contaminants.

 CAUTION:

To prevent damage to the unit or internal 

components, it is recommended that two 

wrenches be used when loosening or tightening 

nuts. Do not over tighten!

1. Using two wrenches loosen the nut and liquid valve.  

Turn the assembly nut counter-clockwise until the orifice 

body halves are separated.

Liquid

Valve

Restrictor

Swivel Nut

Figure 2. 

Liquid Valve, Restrictor, &

 

Swivel Nut Adapter

Figure 3. Removal of Orifice

Содержание T4BE-018 Series

Страница 1: ...s 13 Figure 12 Charging Chart for 5 Ton Models 13 Refrigerant Charging Tables Cooling Mode Only 14 Table 5 Charging Table for 1 5 Ton Models 14 Table 6 Charging Table for 2 Ton Models 14 Table 7 Charg...

Страница 2: ...er hazardous conditions which may result in personal injury or property damage Installation of equipment may require brazing operations Installer must comply with safety codes andwearappropriatesafety...

Страница 3: ...ed immediately with the carrier Pleaseconsultyourdealerformaintenanceinformation and availability of maintenance contracts Please read all instructions before installing the unit Locating the Heat Pum...

Страница 4: ...dryer is provided with the unit and must be installedintheliquidlineofthesystem Iftheinstallation replaces a system with a filter dryer already present in the liquid line the filter dryer must be rep...

Страница 5: ...therestrictororificewhilebeingcarefulnottoscratch either part Carefully remove the restrictor orifice from the valve body See Figure 3 page 4 3 Check the actual size of the new orifice NOTE The size i...

Страница 6: ...be properly connected to the units low voltage terminal block Recommended wire gauge and wire lengths for typical thermostat connections are listed in Table 2 The thermostat should be mounted about 5...

Страница 7: ...terminal strip Verify that the power supply branch circuit overcurrent protection is sized properly Verify that the thermostat is wired correctly Start Up Procedures WARNING This unit is equipped wit...

Страница 8: ...tween the test pins for more than 1 second will force the unit into a defrost cycle As soon as the jumper is removed the defrost cycle will end as determined by the typical criteria Verify the Status...

Страница 9: ...ve Acommonsuctionportforheatingmodecharging is included and located on the compressor access panel above the outdoor unit service valves Heat Mode Verification Tables are provided for quick reference...

Страница 10: ...e ideal system sub cooling can vary over the range of operation Reference the charts to determine the ideal amount of sub cooling for a given liquid pressure Units charged to other values will not per...

Страница 11: ...Liquid Pressure psig Remove refrigerant when above the curve Add refrigerant when below the curve 200 220 240 260 280 300 320 340 360 380 400 420 440 460 480 500 520 540 560 580 600 75 80 85 90 95 10...

Страница 12: ...he curve Add refrigerant when below the curve Figure 9 Charging Chart for 3 Ton Models TXV Matches 200 220 240 260 280 300 320 340 360 380 400 420 440 460 480 500 520 540 560 580 600 75 80 85 90 95 10...

Страница 13: ...the curve Add refrigerant when below the curve Figure 11 Charging Chart for 4 Ton Models TXV Matches 200 220 240 260 280 300 320 340 360 380 400 420 440 460 480 500 520 540 560 580 600 75 80 85 90 95...

Страница 14: ...4 135 236 115 255 120 137 238 115 257 120 276 125 139 240 116 259 121 278 126 297 131 141 242 116 261 121 280 126 299 131 318 136 143 263 122 282 127 301 132 320 137 339 142 145 285 128 304 132 323 13...

Страница 15: ...S DIS TEMP 135 242 131 137 243 132 265 135 139 244 132 266 135 287 138 141 245 132 266 135 288 138 310 141 143 246 132 267 135 289 138 310 141 332 144 145 268 135 290 138 311 141 333 144 354 148 147 2...

Страница 16: ...ESS DIS TEMP 132 248 128 134 248 128 269 133 136 248 128 269 133 290 137 138 248 128 269 133 290 137 310 141 140 249 129 269 133 290 137 311 141 331 146 142 270 133 290 137 311 141 332 146 352 150 144...

Страница 17: ...172 408 178 141 365 166 387 172 409 178 143 388 172 410 178 145 411 178 147 Table 11 Charging Table for 5 Ton Models Restrictor Matches Shaded boxes indicate flooded conditions Rated design values The...

Страница 18: ...arts Switch the unit into cooling mode and allow it to operate and stabilize for a few minutes then inspect the unit operation with the cooling mode charts and procedures Before changing the unit char...

Страница 19: ...266 267 114 52 277 278 119 68 287 288 125 83 298 299 131 99 334 335 134 117 373 374 137 135 412 414 139 Table 14 Verification Table for 2 5 Ton Models OUTDOOR TEMPERATURE DEG F 0 10 20 30 40 50 60 SUC...

Страница 20: ...81 292 139 104 307 318 150 120 332 343 161 30 221 232 105 45 239 250 112 60 257 268 120 75 275 286 127 90 288 299 136 105 314 325 146 121 339 350 155 31 228 239 103 46 245 256 110 61 261 272 118 76 27...

Страница 21: ...y 3 Not suitable on systems that exceed 150 volts to ground 4 For replacement wires use conductors suitable for 105 C 5 For ampacities and overcurrent protection see unit rating plate 6 Connect to 24...

Страница 22: ...ed 150 volts to ground 4 For replacement wires use conductors suitable for 105 C 5 For ampacities and overcurrent protection see unit rating plate 6 Connect to 24 vac 40va class 2 circuit See furnace...

Страница 23: ...0 volts to ground 4 For replacement wires use conductors suitable for 105 C 5 For ampacities and overcurrent protection see unit rating plate 6 Connect to 24 vac 40va class 2 circuit See furnace air h...

Страница 24: ...me Delay Relays Pressure Switches Transformers Relays MOTORS Blower Motor Fan Motor COMPONENTS Blower Assembly Fan Grille Cabinet Panels Filter Driers Expansion Valves REFRIGERATION SYSTEM Was unit gi...

Отзывы: