background image

7

Compressor Protection

The CoreSense

TM

 Diagnostics module utilizes proprietary 

algorithms to protect the compressor and system from 

repeated trips of system pressure controls and the 

compressor internal overload. The protection terminal 

of the module should be wired in series with the system 

low pressure and high pressure cutouts, as well as the 

compressor contactor. When the module detects a series 

of trips as described below, it will activate a lockout feature 

that opens the normally closed protection contacts in 

the module, thereby cutting power to the contactor and 

shutting off the compressor.

Resetting Alert Codes

When the CoreSense

TM

 Diagnostics module has detected a 

series of adverse conditions that have caused it to lockout 

the compressor, and after the issue has been resolved, 

it is necessary to manually reset the module in order to 

clear the present alert code.

The primary way of clearing the code and resetting the 

alert is to press the reset button located on the module. 

NOTE:

 Pressing the reset will require a pin or a mini 

electronics screwdriver. This button must be pressed and 

held for a minimum of one second for the module to be 

reset. Pressing the reset button clears the immediate lock 

code and the seven day operating history. It will not clear 

the permanent module history. In the case of the three-

wire module, the codes can be reset or cleared by cycling 

power to the module. This can be done by disengaging 

the Common (

C

) terminal. This will not clear the seven 

day operating history.

START UP & ADJUSTMENTS

Pre-Start Check List

  Verify the unit is level and has sufficient clearances for 

unobstructed airflow.

  Verify the outdoor coil and top of the unit are free from 

obstructions and debris, and all equipment access/

control panels are in place.

  Verify that the line voltage power leads are securely 

connected and the unit is properly grounded.

    Verify that the low voltage wires are securely connected 

to the correct leads on the low voltage terminal strip.

  Verify that the power supply branch circuit overcurrent 

protection is sized properly.

  Verify that the thermostat is wired correctly.

Start-Up Procedures

 WARNING:

This unit is equipped with a crankcase heater. 

Allow 24 hours prior to continuing the start up 

procedures to allow for heating of the refrigerant 

compressor crankcase. Failure to comply may 

result in damage and could cause premature 

failure of the system. This warning should be 

followed at initial start up and any time the power 

has been removed for 12 hours or longer.

Air Circulation - Indoor Blower

1. Set the thermostat system mode on OFF and the fan 

mode to ON.

2. Verify the blower runs continuously. Check the air delivery 

at the supply registers and adjust register openings for 

balanced air distribution. If insufficient air is detected, 

examine ductwork for leaks or obstructions.

3. Set the thermostat fan mode to AUTO and verify the 

blower stops running.

Table 3. LED Diagnostics for CoreSense

TM

 Diagnostics Module

ALERT CODE

ALERT CONDITION

LOCK LEVEL

LOCK INDICATION

Normal Run

Solid Yellow

Normal operation, no trip

N/A

N/A

Code1

Yellow Flash 1

Long run time. Compressor is on running for more than 18 hours.

(Code1 is disabled in Heat Pump Mode)

N/A

N/A

Code2

Yellow Flash 2

Compressor (pressure) trip. Compressor runs for 12 sec to 15 min followed 

by a compressor trip condition lasting for more than 7 min.

4x consecutive

Red: Flash2

Yellow: Off

Code3

Yellow Flash 3

Pressure switch cycling. Compressor runs for 12 sec to 15 min followed 

by a compressor trip lasting between 35 sec to 7 min.

4x consecutive

or 10x total

Red: Flash3

Yellow: Off

Code4

Yellow Flash 4

Locked rotor. Compressor trips within a compressor run time of 12 sec 

and does not start within 35 sec.

10x consecutive

Red: Flash4

Yellow: Off

Code5

Yellow Flash 5

Compressor (moderate run) trip. Compressor runs for 15 min to 18 hrs 

followed by a compressor trip lasting longer than 7 min.

4x consecutive

or 10x total

Red: Flash5

Yellow: Off

Code9

Red Flash 9

The current to the PROT terminal is greater than 2A.

Current >2A

for 40ms

Red: Flash9

Yellow: Off

Trip

Solid Red

Demand is present, but compressor is not running.

N/A

N/A

Содержание T4BE-018 Series

Страница 1: ...s 13 Figure 12 Charging Chart for 5 Ton Models 13 Refrigerant Charging Tables Cooling Mode Only 14 Table 5 Charging Table for 1 5 Ton Models 14 Table 6 Charging Table for 2 Ton Models 14 Table 7 Charg...

Страница 2: ...er hazardous conditions which may result in personal injury or property damage Installation of equipment may require brazing operations Installer must comply with safety codes andwearappropriatesafety...

Страница 3: ...ed immediately with the carrier Pleaseconsultyourdealerformaintenanceinformation and availability of maintenance contracts Please read all instructions before installing the unit Locating the Heat Pum...

Страница 4: ...dryer is provided with the unit and must be installedintheliquidlineofthesystem Iftheinstallation replaces a system with a filter dryer already present in the liquid line the filter dryer must be rep...

Страница 5: ...therestrictororificewhilebeingcarefulnottoscratch either part Carefully remove the restrictor orifice from the valve body See Figure 3 page 4 3 Check the actual size of the new orifice NOTE The size i...

Страница 6: ...be properly connected to the units low voltage terminal block Recommended wire gauge and wire lengths for typical thermostat connections are listed in Table 2 The thermostat should be mounted about 5...

Страница 7: ...terminal strip Verify that the power supply branch circuit overcurrent protection is sized properly Verify that the thermostat is wired correctly Start Up Procedures WARNING This unit is equipped wit...

Страница 8: ...tween the test pins for more than 1 second will force the unit into a defrost cycle As soon as the jumper is removed the defrost cycle will end as determined by the typical criteria Verify the Status...

Страница 9: ...ve Acommonsuctionportforheatingmodecharging is included and located on the compressor access panel above the outdoor unit service valves Heat Mode Verification Tables are provided for quick reference...

Страница 10: ...e ideal system sub cooling can vary over the range of operation Reference the charts to determine the ideal amount of sub cooling for a given liquid pressure Units charged to other values will not per...

Страница 11: ...Liquid Pressure psig Remove refrigerant when above the curve Add refrigerant when below the curve 200 220 240 260 280 300 320 340 360 380 400 420 440 460 480 500 520 540 560 580 600 75 80 85 90 95 10...

Страница 12: ...he curve Add refrigerant when below the curve Figure 9 Charging Chart for 3 Ton Models TXV Matches 200 220 240 260 280 300 320 340 360 380 400 420 440 460 480 500 520 540 560 580 600 75 80 85 90 95 10...

Страница 13: ...the curve Add refrigerant when below the curve Figure 11 Charging Chart for 4 Ton Models TXV Matches 200 220 240 260 280 300 320 340 360 380 400 420 440 460 480 500 520 540 560 580 600 75 80 85 90 95...

Страница 14: ...4 135 236 115 255 120 137 238 115 257 120 276 125 139 240 116 259 121 278 126 297 131 141 242 116 261 121 280 126 299 131 318 136 143 263 122 282 127 301 132 320 137 339 142 145 285 128 304 132 323 13...

Страница 15: ...S DIS TEMP 135 242 131 137 243 132 265 135 139 244 132 266 135 287 138 141 245 132 266 135 288 138 310 141 143 246 132 267 135 289 138 310 141 332 144 145 268 135 290 138 311 141 333 144 354 148 147 2...

Страница 16: ...ESS DIS TEMP 132 248 128 134 248 128 269 133 136 248 128 269 133 290 137 138 248 128 269 133 290 137 310 141 140 249 129 269 133 290 137 311 141 331 146 142 270 133 290 137 311 141 332 146 352 150 144...

Страница 17: ...172 408 178 141 365 166 387 172 409 178 143 388 172 410 178 145 411 178 147 Table 11 Charging Table for 5 Ton Models Restrictor Matches Shaded boxes indicate flooded conditions Rated design values The...

Страница 18: ...arts Switch the unit into cooling mode and allow it to operate and stabilize for a few minutes then inspect the unit operation with the cooling mode charts and procedures Before changing the unit char...

Страница 19: ...266 267 114 52 277 278 119 68 287 288 125 83 298 299 131 99 334 335 134 117 373 374 137 135 412 414 139 Table 14 Verification Table for 2 5 Ton Models OUTDOOR TEMPERATURE DEG F 0 10 20 30 40 50 60 SUC...

Страница 20: ...81 292 139 104 307 318 150 120 332 343 161 30 221 232 105 45 239 250 112 60 257 268 120 75 275 286 127 90 288 299 136 105 314 325 146 121 339 350 155 31 228 239 103 46 245 256 110 61 261 272 118 76 27...

Страница 21: ...y 3 Not suitable on systems that exceed 150 volts to ground 4 For replacement wires use conductors suitable for 105 C 5 For ampacities and overcurrent protection see unit rating plate 6 Connect to 24...

Страница 22: ...ed 150 volts to ground 4 For replacement wires use conductors suitable for 105 C 5 For ampacities and overcurrent protection see unit rating plate 6 Connect to 24 vac 40va class 2 circuit See furnace...

Страница 23: ...0 volts to ground 4 For replacement wires use conductors suitable for 105 C 5 For ampacities and overcurrent protection see unit rating plate 6 Connect to 24 vac 40va class 2 circuit See furnace air h...

Страница 24: ...me Delay Relays Pressure Switches Transformers Relays MOTORS Blower Motor Fan Motor COMPONENTS Blower Assembly Fan Grille Cabinet Panels Filter Driers Expansion Valves REFRIGERATION SYSTEM Was unit gi...

Отзывы: