background image

9

if a minimum two inch clearance is available. If 
desired, the return opening can be located inside 
a closet with louvered doors that have an open 
area equal to or greater than the return grille.  
The return air grille can be placed in the wall 
of a closet and the air ducted into the fi lter box 
through a boxed-in area at the closet fl oor level.  
Make sure the fi lter is readily accessible.

After determining the location of the return air 
opening, start the installation from under the home 
by cutting a small hole in the fi ber underboard to 
determine how the fl oor joist location will affect 
cutting the opening needed for the box.  Floor 
joists generally are located on 16” centers, leav-
ing 14-3/8” between joists.  After measuring the 
return air box, cut the hole through the fl oor so 
that the box will fi t between the fl oor joists. Care 
should be taken when cutting through carpeting 
to avoid snags.  In most installations it will be 
necessary to cut a similar hole in the fi berboard 
directly under the hole in the fl oor.  However, if 
the fl oor is more than ten inches deep, it will only 
be necessary to cut a hole for the collar on the 
return air box or for the insulated duct. 

Set the box into the opening and fasten with 
screws or nails.  Put the fi lter and return air 
grille in place.

Note: For highly resistive duct systems it may be 
necessary to add an additional return air duct to 
achieve maximum performance.

Locating and Installing the Supply 

Damper(s)

When locating the supply damper(s), carefully 

check fl oor joists and frame members that could 
interfere with the installation of the damper or 
fl exible duct. Ideally, the damper should be 
located in the bottom of the main duct, forward 
of center of the home, at least three feet from 
the nearest register.  The round supply opening 
in the slanted side of the damper should face 
the side of the home where the heat pump is 
located.  To locate the center of the heat duct, 
fi rst cut a small hole in the fi berboard below the 
duct at the desired location.  After locating the 
duct center, cut a hole approximately 3/4” larger 
than the damper opening in the fi berboard.  Cut 
a 9-1/8” x 13-1/8” hole in the duct and bend over 
all tabs fl at on the inside of the heat duct.  After 
inserting the damper into the duct, bend over 
all tabs fl at on the inside of the heat duct. Seal 
the opening between the fi berboard and damper 
or fl exible duct. 

DUCTING SYSTEM

Duct Requirements

 

 

The supply duct system, including the number 

and type of registers, will have much more ef-
fect on the performance the system than any 
other factor.  The duct must be suffi ciently large 
to conduct an adequate amount of air to each 
register.

THE HEAT PUMP SYSTEM WILL NOT COOL 
OR HEAT THE HOME IF THE AIR IS LOST 
TO THE  OUTSIDE THROUGH  LEAKS  IN THE 
DUCT SYSTEM.  ALSO, DUCTS WHICH ARE 
COLLAPSED OR RESTRICTED BY FOREIGN 
OBJECTS WILL PREVENT ADEQUATE AIR 
FLOW.

Figure  9.  Supply Damper

AUTOMATIC DAMPER IS CLOSED

WHEN HEAT PUMP IS OFF

Figure  8.  Return Air Box

Содержание Q4RD 060

Страница 1: ...g appliances Some local codes require licensed installation service personnel for this type equipment All installations must be in accordance with these instructions and with all applicable national a...

Страница 2: ...2...

Страница 3: ...a the supply duct 6 The refrigerant returns to the outdoor coil and evaporates once again to absorb more heat SUMMER COOLING 1 Indoor air enters the return air duct 2 The cold heat transfer section in...

Страница 4: ...oned the outdoor unit fan and the compressor may not start immediately A protectivetimercircuitholdsthecompressorand the outdoor fan off for approximately six minutes following a previous operation or...

Страница 5: ...ecautionsintheliterature on tags and on labels provided with the unit and or approved field installed kits The type of hazard and severity are described on each label or tag Pressures Within The Syste...

Страница 6: ...URN DUCT OPENING 23 5 1 25 Power Entry 1 75 Power Entry Capped 0 88 Control Wiring Entry 23 6 27 2 30 1 8 4 00 13 5 16 0 14 7 13 5 16 0 13 45 11 75 22 75 55 8 C SUPPLY RETURN 4 0 CONDENSING COIL 5 0 8...

Страница 7: ...hat drains well See Figure 6 AIR DUCTS This unit is designed only for use with a supply and return duct Air ducts should be installed in accordance with the standards of the National Fire Protection A...

Страница 8: ...ion SMACNA application standard for duct liners Duct lining must be UL classified batts or blankets with a fire hazard classification of FHC 25 50 or less Fiber duct work may be used in place of inter...

Страница 9: ...achieve maximum performance Locating and Installing the Supply Damper s When locating the supply damper s carefully check floor joists and frame members that could interfere with the installation of...

Страница 10: ...tionandplasticsleeve should be pulled over the connection and clamped f For homes with multiple supply ducts or for special applications a Y fitting is available to divide the supply air so it can be...

Страница 11: ...stalled circuit breaker kits are used inside the control compartment Use only copper wire for the line voltagepowersupplytothisunit Usepropercode agency listed conduit and a conduit connector for conn...

Страница 12: ...0 minutes 60 minutes and 90 minutes Time setting selection is dependent on the climate where the unit is being installed Example 1 Dry climate of Southern Arizona A 90 minute setting is recommended Ex...

Страница 13: ...essor and fan energize and that the temperature of the discharge air is cooler than the room temperature This is available only for the single phase models System Cooling 1 Set the thermostat system s...

Страница 14: ...out the availability of maintenance contracts At a minimum routine maintenance should include the following 1 Inspect and clean or replace air filters at the beginning of each heating and cooling seas...

Страница 15: ...1 Stage Cool 1 Stage Electric Heat Typical Wiring Field Supplied for 2 Stage Cool 2 Stage Electric Heat with an Optional Outdoor Thermostat Figure 12 Typical Heat Pump Thermostat Connections E O G R...

Страница 16: ...173 253 174 270 175 81 222 175 238 177 255 178 272 179 289 180 83 226 179 242 181 258 182 274 183 291 184 85 245 185 261 186 278 187 293 188 87 265 190 281 192 297 193 89 284 196 301 197 91 304 202 93...

Страница 17: ...SETS THE INTERVAL TO 0 1 2 3 4 C R S C H F E DFTR W2 0 Y C T2 T1 DF2 DF1 C Y 0 W2 R E PRESSURE SWITCH IF EQUIPPED TO 208 230 VAC POWER SUPPLY BLOWER MOTOR T1 T3 T4 T2 G N L C 2 3 4 5 6 7 8 9 1 2 3 4 5...

Страница 18: ...RESETS THE INTERVAL TO 0 1 2 3 4 C R S C H F E DFTR W2 0 Y C T2 T1 DF2 DF1 C Y 0 W2 R E PRESSURE SWITCH IF EQUIPPED TO 208 230 VAC POWER SUPPLY BLOWER MOTOR T1 T3 T4 T2 G N L C 2 3 4 5 6 7 8 9 1 2 3...

Страница 19: ...19...

Страница 20: ...5460 Specifications and illustrations subject to change without notice and without incurring obligations Printed in U S A 05 06 708546 INSTALLER PLEASE LEAVE THESE INSTALLATION INSTRUCTIONS WITH THE H...

Отзывы: