background image

13

•    Verify that the low voltage wires are securely 

connected to the correct leads on the low 
voltage terminal strip.

• 

Verify that all exterior panels are replaced 
and securely fastened.

• 

Verify that the outdoor fan turns freely.

• 

Verify that the power supply branch circuit 
overcurrent protection is sized properly.

• 

Verify that the thermostat is wired correctly. 
The thermostat function switch should be 
set to “Off’ and the thermostat fan switch 
should be set to “Auto.”

Start-Up Procedure

Close all electrical disconnects to energize the 
system.

 WARNING:

If the unit is equipped with a crankcase 
heater, allow 24 hours prior to 
continuing the start up procedures 
to allow for heating of the refrigerant 
compressor crankcase. Failure to 
comply may result in damage and 
could cause premature failure of 
the system. This warning should be 
followed at initial start up and any 
time the power has been removed for 
12 hours or longer.

Air Circulation — 

Leave the thermostat system 

switch set to “Off” and set the thermostat fan 
switch to “On.” The blower motor should run 
continuously. Check for air delivery at the 
register(s). Ensure that there are no obstructions 
at the registers or in the duct work. Set thermostat 
fan switch to “Auto.”

Short Cycle Protection —

 With the system 

operating in cooling mode, note the temperature 
setting of the thermostat and gradually raise the 
set-point temperature until the unit de-energizes. 
Immediately lower the set point temperature of 
the thermostat to its original setting and verify 
that the indoor blower is energized. Verify that 
after approximately 5 minutes the compressor 
and fan energize and that the temperature 

of the discharge air is cooler than the room 
temperature. This is available only for the single 
phase models.

System Cooling

1.  Set the thermostat system switch to “Cool” 

and the thermostat fan switch to “Auto”. 
Gradually lower the thermostat temperature 
switch below room temperature and 
observe that the blower, compressor, and 
fan energize. Check that air cooler than 
room temperature is being discharged 
at the register. Listen for any unusual 
noises.

2.  After allowing the unit to run for several 

minutes, set the temperature selector 
above room temperature.

-  The fan and compressor cycles off with 

the thermostat.

-  The blower should also stop unless fan 

switch is set to “ON” position.

System Heating — 

If the unit has been equipped 

with optional electric heater kits, set the system 
thermostat switch to HEAT and set the thermostat 
fan switch to AUTO. Verify that the compressor 
and outdoor fan are not energized but that the 
blower and heaters are. Check for warm air at 
the supply registers.

UNIT MAINTENANCE

 WARNING:

To avoid risk of electrical shock, 
personal injury, or death, disconnect 
all electrical power to the unit before 
performing any maintenance or 
service. The unit may have more than 
one electrical supply.

Refrigerant Charging — 

Packaged heat 

pumps are fully charged at the factory . The 
system refrigerant charge can be checked and 
adjusted through the service ports provided 
in the front panel. Use only gauge lines which 
have a “Schrader” depression device present 
to actuate the valve. Draw a vacuum on gauge 
lines to remove air before attaching them to the 
service ports on the unit. Refrigerant charging 
must be done by qualifi ed personnel familiar with 
safe and environmentally responsible refrigerant 
handling procedures.

Содержание Q4RD 060

Страница 1: ...g appliances Some local codes require licensed installation service personnel for this type equipment All installations must be in accordance with these instructions and with all applicable national a...

Страница 2: ...2...

Страница 3: ...a the supply duct 6 The refrigerant returns to the outdoor coil and evaporates once again to absorb more heat SUMMER COOLING 1 Indoor air enters the return air duct 2 The cold heat transfer section in...

Страница 4: ...oned the outdoor unit fan and the compressor may not start immediately A protectivetimercircuitholdsthecompressorand the outdoor fan off for approximately six minutes following a previous operation or...

Страница 5: ...ecautionsintheliterature on tags and on labels provided with the unit and or approved field installed kits The type of hazard and severity are described on each label or tag Pressures Within The Syste...

Страница 6: ...URN DUCT OPENING 23 5 1 25 Power Entry 1 75 Power Entry Capped 0 88 Control Wiring Entry 23 6 27 2 30 1 8 4 00 13 5 16 0 14 7 13 5 16 0 13 45 11 75 22 75 55 8 C SUPPLY RETURN 4 0 CONDENSING COIL 5 0 8...

Страница 7: ...hat drains well See Figure 6 AIR DUCTS This unit is designed only for use with a supply and return duct Air ducts should be installed in accordance with the standards of the National Fire Protection A...

Страница 8: ...ion SMACNA application standard for duct liners Duct lining must be UL classified batts or blankets with a fire hazard classification of FHC 25 50 or less Fiber duct work may be used in place of inter...

Страница 9: ...achieve maximum performance Locating and Installing the Supply Damper s When locating the supply damper s carefully check floor joists and frame members that could interfere with the installation of...

Страница 10: ...tionandplasticsleeve should be pulled over the connection and clamped f For homes with multiple supply ducts or for special applications a Y fitting is available to divide the supply air so it can be...

Страница 11: ...stalled circuit breaker kits are used inside the control compartment Use only copper wire for the line voltagepowersupplytothisunit Usepropercode agency listed conduit and a conduit connector for conn...

Страница 12: ...0 minutes 60 minutes and 90 minutes Time setting selection is dependent on the climate where the unit is being installed Example 1 Dry climate of Southern Arizona A 90 minute setting is recommended Ex...

Страница 13: ...essor and fan energize and that the temperature of the discharge air is cooler than the room temperature This is available only for the single phase models System Cooling 1 Set the thermostat system s...

Страница 14: ...out the availability of maintenance contracts At a minimum routine maintenance should include the following 1 Inspect and clean or replace air filters at the beginning of each heating and cooling seas...

Страница 15: ...1 Stage Cool 1 Stage Electric Heat Typical Wiring Field Supplied for 2 Stage Cool 2 Stage Electric Heat with an Optional Outdoor Thermostat Figure 12 Typical Heat Pump Thermostat Connections E O G R...

Страница 16: ...173 253 174 270 175 81 222 175 238 177 255 178 272 179 289 180 83 226 179 242 181 258 182 274 183 291 184 85 245 185 261 186 278 187 293 188 87 265 190 281 192 297 193 89 284 196 301 197 91 304 202 93...

Страница 17: ...SETS THE INTERVAL TO 0 1 2 3 4 C R S C H F E DFTR W2 0 Y C T2 T1 DF2 DF1 C Y 0 W2 R E PRESSURE SWITCH IF EQUIPPED TO 208 230 VAC POWER SUPPLY BLOWER MOTOR T1 T3 T4 T2 G N L C 2 3 4 5 6 7 8 9 1 2 3 4 5...

Страница 18: ...RESETS THE INTERVAL TO 0 1 2 3 4 C R S C H F E DFTR W2 0 Y C T2 T1 DF2 DF1 C Y 0 W2 R E PRESSURE SWITCH IF EQUIPPED TO 208 230 VAC POWER SUPPLY BLOWER MOTOR T1 T3 T4 T2 G N L C 2 3 4 5 6 7 8 9 1 2 3...

Страница 19: ...19...

Страница 20: ...5460 Specifications and illustrations subject to change without notice and without incurring obligations Printed in U S A 05 06 708546 INSTALLER PLEASE LEAVE THESE INSTALLATION INSTRUCTIONS WITH THE H...

Отзывы: