background image

3

It is the sole responsibility of the homeowner to 
make certain that heat pump has been correctly 
set up and adjusted to operate properly. 

The Manufacturer warrants the heat pump to be 
free from defects in material or workmanship for a 
period of one year. We will not be responsible for 
any costs found necessary to correct problems 
due to improper setup, improper installation, 
adjustments, improper operating procedure on 
the part of the user, etc. 

Some specifi c examples of service calls which 
are not included in the limited warranty are:

1.  Correcting wiring problems in the electrical 

circuit supplying the heat pump. 

SECTION 1. OWNER INFORMATION

WINTER HEATING

1.  Outdoor air enters the heat pump.
2.  The cold, heat-transfer section (outdoor coil) 

extracts the heat from the air as the refrigerant 
evaporates from a liquid to a cold gas.

3.  The refrigerant, compressed to a hot gas by 

the heat pump, carries the heat to the heat-
transfer section (indoor coil).

4. The hot, heat-transfer section (indoor 

coil) releases the heat as the refrigerant 
condenses   from a gas to a liquid.

5.  The blower circulates the heat throughout 

the home via the supply duct.

6.  The refrigerant returns to the outdoor coil 

and evaporates once again to absorb more 
heat.

SUMMER COOLING

1.  Indoor air enters the return air duct.
2.  The cold, heat-transfer section (indoor coil) 

extracts the heat from the air as the refrigerant 
evaporates from a liquid to a cold gas. 

3.  The refrigerant, drawn to the heat pump and 

compressed to a hot gas, carries the heat 
outdoors. 

4.  The hot, heat-transfer section (outdoor coil) 

releases the heat as the refrigerant condenses 
from a gas to a liquid.

5.  The heat pump (outdoor fan) discharges the 

heat to the outside air. 

6. The refrigerant returns to the indoor coil 

and evaporates once again to absorb more 
heat. 

5

4

1

2

3

6

2

1

5

3

6

4

2.  Resetting circuit breakers or other switches. 

3.  Adjusting or calibrating of thermostat. 

To avoid misunderstandings at a later date, 
carefully review these responsibilities with your 
dealer or service company.

The heat pump system will heat and cool your 
home and save your energy dollars.

During the summer, a heat pump cools a house 
by absorbing heat from within the house and 
exhausting it outdoors. During the winter, a heat 
pump heats a house by absorbing heat outdoors 
and exhausting it indoors. This is an effi cient 
heating means because you pay for “moving” 
heat from outdoors to indoors, but do not pay 
to generate the heat. 

Содержание Q4RD 060

Страница 1: ...g appliances Some local codes require licensed installation service personnel for this type equipment All installations must be in accordance with these instructions and with all applicable national a...

Страница 2: ...2...

Страница 3: ...a the supply duct 6 The refrigerant returns to the outdoor coil and evaporates once again to absorb more heat SUMMER COOLING 1 Indoor air enters the return air duct 2 The cold heat transfer section in...

Страница 4: ...oned the outdoor unit fan and the compressor may not start immediately A protectivetimercircuitholdsthecompressorand the outdoor fan off for approximately six minutes following a previous operation or...

Страница 5: ...ecautionsintheliterature on tags and on labels provided with the unit and or approved field installed kits The type of hazard and severity are described on each label or tag Pressures Within The Syste...

Страница 6: ...URN DUCT OPENING 23 5 1 25 Power Entry 1 75 Power Entry Capped 0 88 Control Wiring Entry 23 6 27 2 30 1 8 4 00 13 5 16 0 14 7 13 5 16 0 13 45 11 75 22 75 55 8 C SUPPLY RETURN 4 0 CONDENSING COIL 5 0 8...

Страница 7: ...hat drains well See Figure 6 AIR DUCTS This unit is designed only for use with a supply and return duct Air ducts should be installed in accordance with the standards of the National Fire Protection A...

Страница 8: ...ion SMACNA application standard for duct liners Duct lining must be UL classified batts or blankets with a fire hazard classification of FHC 25 50 or less Fiber duct work may be used in place of inter...

Страница 9: ...achieve maximum performance Locating and Installing the Supply Damper s When locating the supply damper s carefully check floor joists and frame members that could interfere with the installation of...

Страница 10: ...tionandplasticsleeve should be pulled over the connection and clamped f For homes with multiple supply ducts or for special applications a Y fitting is available to divide the supply air so it can be...

Страница 11: ...stalled circuit breaker kits are used inside the control compartment Use only copper wire for the line voltagepowersupplytothisunit Usepropercode agency listed conduit and a conduit connector for conn...

Страница 12: ...0 minutes 60 minutes and 90 minutes Time setting selection is dependent on the climate where the unit is being installed Example 1 Dry climate of Southern Arizona A 90 minute setting is recommended Ex...

Страница 13: ...essor and fan energize and that the temperature of the discharge air is cooler than the room temperature This is available only for the single phase models System Cooling 1 Set the thermostat system s...

Страница 14: ...out the availability of maintenance contracts At a minimum routine maintenance should include the following 1 Inspect and clean or replace air filters at the beginning of each heating and cooling seas...

Страница 15: ...1 Stage Cool 1 Stage Electric Heat Typical Wiring Field Supplied for 2 Stage Cool 2 Stage Electric Heat with an Optional Outdoor Thermostat Figure 12 Typical Heat Pump Thermostat Connections E O G R...

Страница 16: ...173 253 174 270 175 81 222 175 238 177 255 178 272 179 289 180 83 226 179 242 181 258 182 274 183 291 184 85 245 185 261 186 278 187 293 188 87 265 190 281 192 297 193 89 284 196 301 197 91 304 202 93...

Страница 17: ...SETS THE INTERVAL TO 0 1 2 3 4 C R S C H F E DFTR W2 0 Y C T2 T1 DF2 DF1 C Y 0 W2 R E PRESSURE SWITCH IF EQUIPPED TO 208 230 VAC POWER SUPPLY BLOWER MOTOR T1 T3 T4 T2 G N L C 2 3 4 5 6 7 8 9 1 2 3 4 5...

Страница 18: ...RESETS THE INTERVAL TO 0 1 2 3 4 C R S C H F E DFTR W2 0 Y C T2 T1 DF2 DF1 C Y 0 W2 R E PRESSURE SWITCH IF EQUIPPED TO 208 230 VAC POWER SUPPLY BLOWER MOTOR T1 T3 T4 T2 G N L C 2 3 4 5 6 7 8 9 1 2 3...

Страница 19: ...19...

Страница 20: ...5460 Specifications and illustrations subject to change without notice and without incurring obligations Printed in U S A 05 06 708546 INSTALLER PLEASE LEAVE THESE INSTALLATION INSTRUCTIONS WITH THE H...

Отзывы: