16
5
OUTDOOR TEMPERATURE (°F)
TON
70
75
80
85
90
95
100
105
Suct.
Press.
Dis.
Press.
Dis.
Temp.
Dis.
Press.
Dis.
Temp.
Dis.
Press.
Dis.
Temp.
Dis.
Press.
Dis.
Temp.
Dis.
Press.
Dis.
Temp.
Dis.
Press.
Dis.
Temp.
Dis.
Press.
Dis.
Temp.
Dis.
Press.
Dis.
Temp.
67
154
140
69
156
146
173
146
71
158
151
176
152
193
152
73
160
158
178
157
195
157
212
158
75
163
160
180
162
197
162
214
163
231
164
77
183
165
199
167
216
168
233
168
251
170
79
203
170
219
172
235
173
253
174
270
175
81
222
175
238
177
255
178
272
179
289
180
83
226
179
242
181
258
182
274
183
291
184
85
245
185
261
186
278
187
293
188
87
265
190
281
192
297
193
89
284
196
301
197
91
304
202
93
Table 2. 13 SEER Cooling Charging Charts
Cooling Charging Chart
* Note: All pressures are listed in psig. and all temperatures in deg. F.
— Shaded Boxes indicate fl ooded conditions
— Rated Design Values. Suction Pressure will be lower than design
value if indoor airfl ow, entering dry bulb, or entering wet bulb tem-
peratures are lower than design.
— Discharge temperatures greater than charted values indicates a
refrigerant undercharge.