background image

12

the accessories installed with the unit. Select a 
thermostat which operates in conjunction with 
the installed accessories. The thermostat should 
be mounted about fi ve feet above the ground on 
an inside wall. The thermostat should be kept 
away from drafts, slamming doors, lamps, direct 
sunlight, or in line with the supply air fl ow. 

To install the thermostat:

1.  Position the sub base on an inside wall and 

mark the mounting holes and thermostat 
cable openings. 

2.  Cut out the cable opening and route the 

thermostat cable from the unit’s low voltage 
compartment to the thermostat location. 
The thermostat cable is supplied by the 
installer.

3.  Connect the cable leads to the sub base 

or thermostat terminals and to the unit’s 
low voltage pigtails as shown in 

Figure 10

.  

A system wiring diagram is also provided 
on the inside of the control panel cover.

4.  Secure sub base or thermostat to the 

wall using screws provided with the 
thermostat.

5.  If sub base is used, install the correct 

thermostat housing to sub base.

6.  Refer to thermostat instruction sheet for 

complete detailed mounting information.

Defrost Cycle Timer — 

The defrost cycle timer 

controls the time interval of the hot gas defrost 
after the defrost sensor closes. It is located in 
the lower left corner of the defrost control board 
on the low voltage side of the control box. Three 
interval settings are available: 30 minutes, 60 
minutes, and 90 minutes. Time setting selection 
is dependent on the climate where the unit is 
being installed. 

Example 1. Dry climate of Southern Arizona. 
A 90 minute setting is recommended.

Example 2. Moist climate of Seattle, 
Washington. A 30 minute setting is 
recommended.

To set the cycle timer, place the timing pin on 
the defrost control board to the desired time 
interval post. 
 

Note:

 All units are shipped from the factory with 

the default time setting of 30 minutes.

Field Installed Electric Heat — 

These Single 

Package Heat Pumps are designed to allow 
optional electric heat to be fi eld installed as 
required by the building’s particular heating load. 
The options available for each unit are shown in 
the heater kit installation instructions. As noted 
in the instructions, a fi eld installed circuit breaker 
kit is available as a means of electrical discon-
nect for the unit. 

Install the heater kits as directed by the installation 
instructions that come as part of the heater kit. 
Follow all cautions and warnings as directed.

START UP AND SYSTEM CHECK

Pre-Start Check List

• 

Verify that the unit is level to allow proper 
condensate drainage.

• 

Verify that there is free airfl ow to and from 
the outdoor coil and that all clearance 
requirements are met.

• 

Verify that the duct work is sealed to prevent 
air leakage. 

• 

Verify that the line voltage power leads are 
securely connected and the unit is properly 
grounded.

Figure 11. Motor Lead Connector

PIN NUMBER

MOTOR SPEED

WIRE COLOR

1

LOW

  RED

2

4

HIGH

BLACK

3

MEDIUM

BLUE

5

N/A

N/A

6

COMMON

WHITE

1

2

4

3

5

6

RED

BLACK

BLUE

WHITE

Содержание Q4RD 060

Страница 1: ...g appliances Some local codes require licensed installation service personnel for this type equipment All installations must be in accordance with these instructions and with all applicable national a...

Страница 2: ...2...

Страница 3: ...a the supply duct 6 The refrigerant returns to the outdoor coil and evaporates once again to absorb more heat SUMMER COOLING 1 Indoor air enters the return air duct 2 The cold heat transfer section in...

Страница 4: ...oned the outdoor unit fan and the compressor may not start immediately A protectivetimercircuitholdsthecompressorand the outdoor fan off for approximately six minutes following a previous operation or...

Страница 5: ...ecautionsintheliterature on tags and on labels provided with the unit and or approved field installed kits The type of hazard and severity are described on each label or tag Pressures Within The Syste...

Страница 6: ...URN DUCT OPENING 23 5 1 25 Power Entry 1 75 Power Entry Capped 0 88 Control Wiring Entry 23 6 27 2 30 1 8 4 00 13 5 16 0 14 7 13 5 16 0 13 45 11 75 22 75 55 8 C SUPPLY RETURN 4 0 CONDENSING COIL 5 0 8...

Страница 7: ...hat drains well See Figure 6 AIR DUCTS This unit is designed only for use with a supply and return duct Air ducts should be installed in accordance with the standards of the National Fire Protection A...

Страница 8: ...ion SMACNA application standard for duct liners Duct lining must be UL classified batts or blankets with a fire hazard classification of FHC 25 50 or less Fiber duct work may be used in place of inter...

Страница 9: ...achieve maximum performance Locating and Installing the Supply Damper s When locating the supply damper s carefully check floor joists and frame members that could interfere with the installation of...

Страница 10: ...tionandplasticsleeve should be pulled over the connection and clamped f For homes with multiple supply ducts or for special applications a Y fitting is available to divide the supply air so it can be...

Страница 11: ...stalled circuit breaker kits are used inside the control compartment Use only copper wire for the line voltagepowersupplytothisunit Usepropercode agency listed conduit and a conduit connector for conn...

Страница 12: ...0 minutes 60 minutes and 90 minutes Time setting selection is dependent on the climate where the unit is being installed Example 1 Dry climate of Southern Arizona A 90 minute setting is recommended Ex...

Страница 13: ...essor and fan energize and that the temperature of the discharge air is cooler than the room temperature This is available only for the single phase models System Cooling 1 Set the thermostat system s...

Страница 14: ...out the availability of maintenance contracts At a minimum routine maintenance should include the following 1 Inspect and clean or replace air filters at the beginning of each heating and cooling seas...

Страница 15: ...1 Stage Cool 1 Stage Electric Heat Typical Wiring Field Supplied for 2 Stage Cool 2 Stage Electric Heat with an Optional Outdoor Thermostat Figure 12 Typical Heat Pump Thermostat Connections E O G R...

Страница 16: ...173 253 174 270 175 81 222 175 238 177 255 178 272 179 289 180 83 226 179 242 181 258 182 274 183 291 184 85 245 185 261 186 278 187 293 188 87 265 190 281 192 297 193 89 284 196 301 197 91 304 202 93...

Страница 17: ...SETS THE INTERVAL TO 0 1 2 3 4 C R S C H F E DFTR W2 0 Y C T2 T1 DF2 DF1 C Y 0 W2 R E PRESSURE SWITCH IF EQUIPPED TO 208 230 VAC POWER SUPPLY BLOWER MOTOR T1 T3 T4 T2 G N L C 2 3 4 5 6 7 8 9 1 2 3 4 5...

Страница 18: ...RESETS THE INTERVAL TO 0 1 2 3 4 C R S C H F E DFTR W2 0 Y C T2 T1 DF2 DF1 C Y 0 W2 R E PRESSURE SWITCH IF EQUIPPED TO 208 230 VAC POWER SUPPLY BLOWER MOTOR T1 T3 T4 T2 G N L C 2 3 4 5 6 7 8 9 1 2 3...

Страница 19: ...19...

Страница 20: ...5460 Specifications and illustrations subject to change without notice and without incurring obligations Printed in U S A 05 06 708546 INSTALLER PLEASE LEAVE THESE INSTALLATION INSTRUCTIONS WITH THE H...

Отзывы: