background image

151B0801 R5 3/28/2006

 

6

not interfere with the combustion air 
supplied to the burner. The control 
should be located a minimum of 3 flue 
pipe diameters from the furnace 
breeching and installed in accordance to 
the instructions supplied with the 
regulator. 

Table 3: Minimum Chimney Base 

Temperatures (°F) 

Chimney Height (ft.) 

Nozzle 

11 20 28 36 

Chimney Thermal Resistance < R6 

0.50 300 

400 

535 

725 

0.65 275 

340 

430 

535 

0.70 270 

330 

405 

505 

0.75 260 

320 

380 

475 

0.85 250 

300 

355 

430 

1.00 255 

300 

365 

430 

Chimney Height (ft.) 

Nozzle 

11 20 28 36 

Chimney Thermal Resistance > R6 

0.50 185 

200 

220 

250 

0.65 175 

185 

205 

220 

0.70 175 

185 

195 

215 

0.75 175 

185 

195 

210 

0.85 165 

185 

195 

205 

1.00 165 

185 

195 

205 

< - 

Less than

,   > - 

greater than

 

OIL TANK 

Oil storage tanks must be selected and 
installed in compliance with applicable 
codes; in the United States, 

NFPA 31, 

Standard for the Installation of Oil 
Burning Equipment

, Chapter 2 and in 

Canada, 

CAN/CSA-B139, 

Installation 

Code for Oil Burning Equipment

Section 6

. Observe all local codes and 

by-laws. 

In general, the oil tank must be properly 
supported and remain stable in both 
empty and full condition. The oil tank 
must be fitted with vent and supply pipes 
to the outdoors. Refer to the above-
mentioned codes for sizing. The vent 
pipe must be no less than 1¼ inches 
I.P.S., and terminate with an appropriate 
vent cap in a location where it will not be 
blocked. The fill pipe must be no less 
than 2 inches I.P.S., and terminate with 
an appropriate cap in a location where 
debris will not enter the fill pipe during oil 
delivery. 

If located indoors, the tank should 
normally be in the lowest level, (cellar, 

basement, etc.). It must be equipped 
with a shut-off valve at the tank outlet 
used for the oil supply. The oil tank must 
be located as to not block the furnace / 
room exit pathway. Observe all 
clearances specified in the above-
mentioned codes. 

PIPING INSTALLATION 

In the United States, 

NFPA 31, 

Standard for the Installation of Oil 
Burning Equipment

, Chapter 2. 

In Canada, the entire fuel system should 
be installed in accordance with the 
requirements of 

CAN/CSA B139

, and 

local regulations. Use only approved fuel 
oil tanks piping, fittings and oil filters. 

Ensure that all fittings used in a copper 
oil line system are high quality flare 
fittings. Do not use compression fittings. 

Do not use Teflon tape on any fittings. 

Pressurized or gravity feed installations 
must not exceed 3 PSIG. Pressures 
greater than 10 PSIG may cause 
damage to the shaft seal. If the height of 
the oil stored in a tank above the oil 
burner exceeds 11½ feet, it may be 
necessary to use a pressure-regulating 
device approved for this purpose. 

The furnace may be installed with a one-
pipe system with gravity feed or lift. The 
maximum allowable lift on a single line 
system is 8 feet. Lift should be measured 
from the bottom (outlet) of the tank, to 
the inlet of the burner. Sizing a single 
line system is complex because of the 
difficulty estimating the pressure drop 
through each fitting, bend and 
component in the line. In general, keep 
single line systems short as possible. 2-
stage oil pumps are not available for the 
O4HD furnaces. The following chart 
shows the allowable line lengths 
(hori vertical) for single and two-
line oil piping systems. All distances are 
in feet. 

In retrofit applications, where an existing 
oil line system is in place, a vacuum 
check will help determine the efficacy of 
the existing oil line system The vacuum 
in a system should not exceed 6” Hg. for 
a single pipe system, nor 12” Hg. for a 
two-pipe system. 

NOTE

: The oil burner requires the use of 

a bypass plug when converting from 
single-pipe to two-pipe oil piping 
systems. See burner manufacturer’s 
instructions. 

 

Table 4: Oil Lines 

Copper Tubing Oil Line Length (Feet) 

Single-Pipe Two-Pipe 

Lift 

(Feet) 

” 

OD

 ½” 

OD

 

” 

OD

 ½” 

OD

 

0 53 100 68 100 
1 49 100 65 100 
2 45 100 63 100 
3 41 100 60 100 
4 37 100 58 100 
5 33 100 55 100 
6 29 100 53 100 
7 25 99 50 100 
8 21 83 48 100 
9 17 68 45 100 

10 13  52  42 100 
12 

- - - 

- - - 

37 

100 

14 

- - - 

- - - 

32 

100 

16 

- - - 

- - - 

27 

100 

18 

- - - 

- - - 

22 

88 

All fuel systems should include an oil 
filter between the fuel oil storage tank 
and the oil burner. For best results, 
install the oil filter as close to the burner 
as possible. When using an indoor oil 
tank, the oil filter may be installed at the 
tank downstream from the shut-off valve. 
If firing the furnace under the 0.65 gph 
rate, a 7 to 10 micron line filter should be 
installed as close to the oil burner as 
possible. 

ELECTRICAL CONNECTIONS 

The furnace is listed by the 

Canadian 

Standards Association (CSA)

. It is 

factory wired and requires minimal field 
wiring. In the United States, the wiring 
must be in accordance with the 

National 

Fire Protection Association

 

NFPA-70

National Electrical Code

, and with local 

codes and regulations. In Canada, all 
field wiring should conform to 

CAN/CSA 

C22.1 Canadian Electrical Code, Part 
1

, and by local codes, where they 

prevail.  

The furnace should be wired to a 
separate and dedicated circuit in the 
main electrical panel; however, 
accessory equipment such as electronic 
air cleaners and humidifiers may be 
included on the furnace circuit. Although 
a suitably located circuit breaker can be 
used as a service switch, a separate 
service switch is advisable. The service 
switch is necessary if reaching the circuit 
breaker involves becoming close to the 
furnace, or if the furnace is located 
between the circuit breaker and the 
means of entry to the furnace room. The 
furnace switch (service switch) should be 
clearly marked, installed in an easily 

Содержание O4HD-091A-12-FA

Страница 1: ...WER ECM 8 FURNACE CONTROLS 9 OIL BURNER 9 FURNACE INSTALLATION SET UP 11 MAINTENANCE AND SERVICE 12 OPERATING INSTRUCTIONS 12 TABLE A 1 BECKETT OIL BURNER SET UP 13 TABLE A 2 DIRECT DRIVE BLOWER SET U...

Страница 2: ...f Oil Burning Equipment as well as in accordance with local codes In Canada the installation of the furnace and related equipment shall be installed in accordance with the regulations of CAN CSA B139...

Страница 3: ...able 1 Installation on a combustible floor requires a clearance of 1 inch Using a noncombustible material such as one inch thick channel iron or similar material can do this The furnace must be suppor...

Страница 4: ...VRV INCLUDED IN THIS KIT MUST BE USED IN CONJUNCTION WITH THE FURNACE BOOT CHIMNEY VENTING The chimney must be sized correctly and be in good repair If the chimney is oversized there is a high risk o...

Страница 5: ...on extension cord Change to straight or to long offset I Two or more openings to the same chimney Found by inspection from basement The least important opening must be closed using some other chimney...

Страница 6: ...urnace may be installed with a one pipe system with gravity feed or lift The maximum allowable lift on a single line system is 8 feet Lift should be measured from the bottom outlet of the tank to the...

Страница 7: ...tory is fed into pre programmed algorithms in the microprocessor to determine the correct motor output required to maintain constant airflow regardless of external static pressure The microprocessor a...

Страница 8: ...ng the dipswitch combination displayed in Table 5 This fan on delay can be set at 30 60 90 or 120 seconds This provides a delay between the burner ignition and blower start up to eliminate excessive f...

Страница 9: ...efficiency PREPARATIONS Drill a test port in the venting ideally at least 2 flue pipe diameters away from the furnace breeching if venting horizontally from the furnace or from the flue pipe elbow if...

Страница 10: ...s ducts the inside radius of elbows etc The supply air temperature should be measured at a point where the thermometer will be well within the air stream near the furnace supply air outlet Usually the...

Страница 11: ...tele spout oiler This oiler has a long flexible plastic spout DO NOT OVER LUBRICATE Excess oil may result in premature electric motor failure Inspect the blower fan Clean it if necessary Oil Burner Ma...

Страница 12: ...f air passing through the oil burner combustion chamber breeching etc up the chimney between burner cycles NOTE THE USE OF THIS CONTROL CAN OCCASIONALLY CAUSE POST COMBUSTION NOZZLE DRIP TABLE A 2 DIR...

Страница 13: ...w 1622 1602 1541 1499 1433 0 1 1 1215 1214 1214 1207 1204 1 0 0 1128 1108 1101 1095 1089 1 0 1 988 987 981 978 938 O4HD 091A V F 11 10 DD 9 6 50 80 F 0 0 0 788 787 781 777 756 1 1 0 1800 1800 1800 180...

Страница 14: ...ir Width A Depth B Height C D x E Side F x G Bottom Dia Height H Filter Perm Ship Weight lb O4HD 091A 22 31 50 1 2 20 1 2 x 20 14 x 22 14 x 22 5 42 16 x 25 x 1 190 O4HD 140A 22 31 58 1 8 20 1 2 x 20 1...

Страница 15: ...151B0801 R5 3 28 2006 15 APPENDIX A WIRING DIAGRAM O4HD 091A 12 FA and O4HD 140A 16 FA...

Страница 16: ...151B0801 R5 3 28 2006 16 APPENDIX B WIRING DIAGRAM O4HD 091A V F and O4HD 140A V F...

Страница 17: ...JURY PROPERTY DAMAGE OR DEATH ACCESSORIES The EFTB has provisions for supplying 115 volt power to an electronic air cleaner EAC as well as 115 volts to a line voltage humidifier or humidifier step dow...

Страница 18: ...park for 10 sec a Provides continuous spark after flame is sensed to assure that burner remains lit b Turns on LED diagnostic light c Starts carryover timer i Flame and call for heat are monitored If...

Страница 19: ...noid Valve LED Diagnostic Light RETURNS TO IDLE STATE FLAME FLAME FLAME FLAME NO FLAME NO FLAME FLAME LOST FLAME LOST REMAINS IN IDLE STATE R7184 SEQUENCE OF OPERATION LOCKOUT STATE R7184 Shuts off bu...

Страница 20: ...0 seconds b Burner motor is de energized Even though thermostat is still calling for heat c If circulator fan has started it continues through the selected heat fan off delay period Established flame...

Страница 21: ...t existing call for heat a Circulator fan turns off when heat fan off delay time is complete b Normal operation resumes electronic fan timer control is in standby mode awaiting next thermostat command...

Страница 22: ...shooting IMPORTANT Due to the potential hazard of line voltage only a trained experienced service technician should perform the troubleshooting procedure PRELIMINARY STEPS Check the diagnostic light f...

Страница 23: ...ce the R7184 control If the indicator light turns off replace cad cell bracket assembly Burner starts Trouble is in thermostat circuit Check thermostat wiring connections If connections are clean and...

Страница 24: ...Step 7 6 Reset oil primary control by pushing in and releasing red reset button Indicator light continues to flash at 1 Hz rate Verify that the control is not in restricted mode See notes at end of th...

Страница 25: ...each time a call for heat is successfully completed To reset from RESTRICTED MODE press and hold the reset button for 30 seconds When the LED flashes twice the device has reset NOTE Disable function P...

Страница 26: ...ht a maximum of 1500 in the presence of light Ensure that room light is not leaking into the cad cell compartment See diagnostic light section No fuel oil Check fuel oil supply Check that all hand ope...

Страница 27: ...r radiator Poor alignment between oil burner blast tube and fire pot Check alignment Blast tube should be centered with fire pot burner opening Oil burner head should be inch back from the inside surf...

Страница 28: ...re rise Slow down blower fan if necessary Supply air temperature too cool Excessive duct losses Check supply air ductwork Seal leaky joints and seams Insulate ductwork if necessary Fan control fan on...

Страница 29: ...151B0801 R5 3 28 2006 29 PARTS...

Страница 30: ...Filter 16 x 25 x 1 Permanent 2180023 23 Filter Frame End Support 5592B2 24 Junction Box 28723 25 Junction Box Cover 28722 26 Blower Assembly Complete Direct Drive 3 4 hp ECM O4HD 091A V F 30381 26a Bl...

Страница 31: ...unit 29161 20 Clean out Cover 2 per unit 29162 21 Filter Frame 16 x 25 x 1 18020 22 Filter Frame End Support 5592B2 23 Air Filter 16 x 25 x 1 Permanent 2180023 24 Junction Box 28723 25 Junction Box Co...

Страница 32: ...e Installed Contractor Contact Address Postal Code Telephone No After Hours No Service Contractor if different from Installation Contractor Service Tech Telephone No After Hours No Fuel Supplier Oil S...

Отзывы: