Table C-4:  System and General Troubleshooting 

continued

 

Problem Possible 

Cause 

Remedy 

System temperature rise too 
high. 

System temperature rise ideally should not exceed 85°F. Check 
for clogged air filters. Check blower fan for excess dirt build-up 
or debris. Speed up blower fan if necessary. 

Poor “fan off” delay timing 
selection, (fan stops too soon). 

Check “fan off” delay timing setting. Use a duct thermometer in 
the supply air plenum take-off or first few inches of the supply 
air trunk duct. Ideally, the fan will shut off at a temperature of 
90° - 100°F. Manipulate the dip switch settings to come as close 
as possible to this “fan off” temperature. 

Fuel oil leak. 

Check fuel oil line for leaks. Repair or replace if necessary. 

Stack temperature too high. 

Check stack temperature. Stack temperatures will normally 
range from 350° to 450°F. Check draft regulator. Draft should 
be set to 0.02 in. w.c. 

Excessive fuel oil 
consumption. 

Thermostat improperly 
adjusted or in poor location. 

Check thermostat heat anticipator setting against measured 
amperage draw.  Increase heat anticipator setting if necessary. 
If the thermostat is being influenced by drafts, sunlight, duct 
work, etc., relocate to more suitable location. 

Insufficient combustion air 
adjustment at oil burner, or 
improper draft pressure. 

Adjust the oil burner combustion air band and draft regulator to 
gain the highest practical CO

2

 or lowest practical O

2

 content in 

the flue gases. See Burner Set Up. 

Too much smoke. 

Heat exchanger partially 
clogged. 

Check for soot build-up in heat exchanger flue passages, 
especially in the outer radiator. 

Poor alignment between oil 
burner blast tube and fire pot. 

Check alignment. Blast tube should be centered with fire pot 
burner opening. Oil burner head should be ¼ inch back from the 
inside surface of the fire pot. 

Flame impingement caused by 
Incorrect nozzle angle. 

Check nozzle size and angle. (See Appendix A). Check 
distance from head to inside surface of the fire pot. 

Soot building up on blast 
tube (end coning). 

Defective fire-pot 

Check fire-pot. Repair or replace. 

Airflow blocked or dirty air 
filter. 

Clean or replace air filter. 

Thermostat adjustments or 
location. 

Check thermostat heat anticipator setting against measured 
amperage draw.  Increase heat anticipator setting if necessary. 
If the thermostat is being influenced by drafts, sunlight, duct 
work, etc., relocate to more suitable location. 

Insufficient airflow. 

Check all dampers. Open closed dampers including registers in 
unused rooms. Check system temperature rise. If temperature 
rise is too high, speed up blower fan. 

Defective high limit control. 

Test high limit function of all limit switches. Use a duct 
thermometer to assess accuracy of limit control. Check for 
obstructions to airflow around limit switch bi-metal elements. 
Replace control if necessary. 

Under-sized nozzle. 

Check nozzle. If problem is not caused by air flow problems, 
use larger nozzle, if permitted by rating plate. 

Blower fan motor stopping 
intermittently on overload. 

Check blower fan motor amperage draw. Check motor 
ventilation ports, clean if necessary. Replace motor if 
necessary. 

Furnace will not warm 
home to desired 
temperature. 

Burner motor stopping 
intermittently on overload. 

Check burner motor. Replace if necessary. 

Home does not heat 
evenly 

Improper distribution of heat. 

This is not likely to be a furnace problem. Balance duct system. 

Continues on next page

 

Содержание O4HD-091A-12-FA

Страница 1: ...WER ECM 8 FURNACE CONTROLS 9 OIL BURNER 9 FURNACE INSTALLATION SET UP 11 MAINTENANCE AND SERVICE 12 OPERATING INSTRUCTIONS 12 TABLE A 1 BECKETT OIL BURNER SET UP 13 TABLE A 2 DIRECT DRIVE BLOWER SET U...

Страница 2: ...f Oil Burning Equipment as well as in accordance with local codes In Canada the installation of the furnace and related equipment shall be installed in accordance with the regulations of CAN CSA B139...

Страница 3: ...able 1 Installation on a combustible floor requires a clearance of 1 inch Using a noncombustible material such as one inch thick channel iron or similar material can do this The furnace must be suppor...

Страница 4: ...VRV INCLUDED IN THIS KIT MUST BE USED IN CONJUNCTION WITH THE FURNACE BOOT CHIMNEY VENTING The chimney must be sized correctly and be in good repair If the chimney is oversized there is a high risk o...

Страница 5: ...on extension cord Change to straight or to long offset I Two or more openings to the same chimney Found by inspection from basement The least important opening must be closed using some other chimney...

Страница 6: ...urnace may be installed with a one pipe system with gravity feed or lift The maximum allowable lift on a single line system is 8 feet Lift should be measured from the bottom outlet of the tank to the...

Страница 7: ...tory is fed into pre programmed algorithms in the microprocessor to determine the correct motor output required to maintain constant airflow regardless of external static pressure The microprocessor a...

Страница 8: ...ng the dipswitch combination displayed in Table 5 This fan on delay can be set at 30 60 90 or 120 seconds This provides a delay between the burner ignition and blower start up to eliminate excessive f...

Страница 9: ...efficiency PREPARATIONS Drill a test port in the venting ideally at least 2 flue pipe diameters away from the furnace breeching if venting horizontally from the furnace or from the flue pipe elbow if...

Страница 10: ...s ducts the inside radius of elbows etc The supply air temperature should be measured at a point where the thermometer will be well within the air stream near the furnace supply air outlet Usually the...

Страница 11: ...tele spout oiler This oiler has a long flexible plastic spout DO NOT OVER LUBRICATE Excess oil may result in premature electric motor failure Inspect the blower fan Clean it if necessary Oil Burner Ma...

Страница 12: ...f air passing through the oil burner combustion chamber breeching etc up the chimney between burner cycles NOTE THE USE OF THIS CONTROL CAN OCCASIONALLY CAUSE POST COMBUSTION NOZZLE DRIP TABLE A 2 DIR...

Страница 13: ...w 1622 1602 1541 1499 1433 0 1 1 1215 1214 1214 1207 1204 1 0 0 1128 1108 1101 1095 1089 1 0 1 988 987 981 978 938 O4HD 091A V F 11 10 DD 9 6 50 80 F 0 0 0 788 787 781 777 756 1 1 0 1800 1800 1800 180...

Страница 14: ...ir Width A Depth B Height C D x E Side F x G Bottom Dia Height H Filter Perm Ship Weight lb O4HD 091A 22 31 50 1 2 20 1 2 x 20 14 x 22 14 x 22 5 42 16 x 25 x 1 190 O4HD 140A 22 31 58 1 8 20 1 2 x 20 1...

Страница 15: ...151B0801 R5 3 28 2006 15 APPENDIX A WIRING DIAGRAM O4HD 091A 12 FA and O4HD 140A 16 FA...

Страница 16: ...151B0801 R5 3 28 2006 16 APPENDIX B WIRING DIAGRAM O4HD 091A V F and O4HD 140A V F...

Страница 17: ...JURY PROPERTY DAMAGE OR DEATH ACCESSORIES The EFTB has provisions for supplying 115 volt power to an electronic air cleaner EAC as well as 115 volts to a line voltage humidifier or humidifier step dow...

Страница 18: ...park for 10 sec a Provides continuous spark after flame is sensed to assure that burner remains lit b Turns on LED diagnostic light c Starts carryover timer i Flame and call for heat are monitored If...

Страница 19: ...noid Valve LED Diagnostic Light RETURNS TO IDLE STATE FLAME FLAME FLAME FLAME NO FLAME NO FLAME FLAME LOST FLAME LOST REMAINS IN IDLE STATE R7184 SEQUENCE OF OPERATION LOCKOUT STATE R7184 Shuts off bu...

Страница 20: ...0 seconds b Burner motor is de energized Even though thermostat is still calling for heat c If circulator fan has started it continues through the selected heat fan off delay period Established flame...

Страница 21: ...t existing call for heat a Circulator fan turns off when heat fan off delay time is complete b Normal operation resumes electronic fan timer control is in standby mode awaiting next thermostat command...

Страница 22: ...shooting IMPORTANT Due to the potential hazard of line voltage only a trained experienced service technician should perform the troubleshooting procedure PRELIMINARY STEPS Check the diagnostic light f...

Страница 23: ...ce the R7184 control If the indicator light turns off replace cad cell bracket assembly Burner starts Trouble is in thermostat circuit Check thermostat wiring connections If connections are clean and...

Страница 24: ...Step 7 6 Reset oil primary control by pushing in and releasing red reset button Indicator light continues to flash at 1 Hz rate Verify that the control is not in restricted mode See notes at end of th...

Страница 25: ...each time a call for heat is successfully completed To reset from RESTRICTED MODE press and hold the reset button for 30 seconds When the LED flashes twice the device has reset NOTE Disable function P...

Страница 26: ...ht a maximum of 1500 in the presence of light Ensure that room light is not leaking into the cad cell compartment See diagnostic light section No fuel oil Check fuel oil supply Check that all hand ope...

Страница 27: ...r radiator Poor alignment between oil burner blast tube and fire pot Check alignment Blast tube should be centered with fire pot burner opening Oil burner head should be inch back from the inside surf...

Страница 28: ...re rise Slow down blower fan if necessary Supply air temperature too cool Excessive duct losses Check supply air ductwork Seal leaky joints and seams Insulate ductwork if necessary Fan control fan on...

Страница 29: ...151B0801 R5 3 28 2006 29 PARTS...

Страница 30: ...Filter 16 x 25 x 1 Permanent 2180023 23 Filter Frame End Support 5592B2 24 Junction Box 28723 25 Junction Box Cover 28722 26 Blower Assembly Complete Direct Drive 3 4 hp ECM O4HD 091A V F 30381 26a Bl...

Страница 31: ...unit 29161 20 Clean out Cover 2 per unit 29162 21 Filter Frame 16 x 25 x 1 18020 22 Filter Frame End Support 5592B2 23 Air Filter 16 x 25 x 1 Permanent 2180023 24 Junction Box 28723 25 Junction Box Co...

Страница 32: ...e Installed Contractor Contact Address Postal Code Telephone No After Hours No Service Contractor if different from Installation Contractor Service Tech Telephone No After Hours No Fuel Supplier Oil S...

Отзывы: