TABLE A-1: BECKETT OIL BURNER SET-UP 

BECKETT AFG SERIES OIL BURNERS 

FURNACE 

MODEL

 

OUTPUT 

BTU/Hr.

 

BURNER 

MODEL

 

NOZZLE 

(Delavan)

 

PUMP 

PRESSURE

 

FLOW 

RATE

 

HEAD 

STATIC 

PLATE

 

58,100 

1, 2

 

AF76BO 

0.50 / 70° W 

100 PSIG 

0.50 GPH 

F0 

3-3/8 in. 

73,700 

2

 

AF76BN 

0.65 / 70° W 

100 PSIG 

0.65 GPH 

F3 

3-3/8 in. 

O4HD-091A 

78,900 

2

 

AF76BN 

0.70 / 70° W 

100 PSIG 

0.70 GPH 

F3 

3-3/8 in. 

87,700 

2

 

AF76BZHS 

0.75 / 70° W 

100 PSIG 

0.75 GPH 

F4 

3-3/8 in. 

98,800 

AF76BZHS 

0.85 / 70° W 

100 PSIG 

0.85 GPH 

F4 

3-3/8 in. 

O4HD-140A 

113,400 

AF76BZHS 

1.00 / 70° W 

100 PSIG 

1.00 GPH 

F4 

3-3/8 in. 

1

 F0 Head required for proper combustion.   

2

 Low Firing Rate Baffle required, Beckett Part No. 3708 

In the United States, the R. W. Beckett “AFG” Burner may be equipped with Beckett’s “Inlet Air Shut-Off”, Beckett Part No. AF/A 5861, to increase efficiency. It reduces the 
amount of air passing through the oil burner, combustion chamber, breeching, etc. up the chimney between burner cycles. 

NOTE: THE USE OF THIS CONTROL CAN OCCASIONALLY CAUSE POST COMBUSTION NOZZLE DRIP. 

 

TABLE A-2: DIRECT DRIVE BLOWER SET-UP 

BLOWER SET-UP 

COOLING CAPACITY 

0.20 in. w.c. 

0.50 in. w.c. 

FURNACE 

OUTPUT 

BTU/Hr. 

BLOWER 

MOTOR 

HP

 

Dip 

Switch/Speed 

Setting 

Dip 

Switch/Speed 

Setting 

Htg. CFM 

Range 

1

 

Tons 

2

 

MOTOR 

HP

 

Clg. CFM 

Range

 

58,100 Low 

Low 

668-1069 

73,700 Medium-Low 

Medium-Low 

841-1346 

O4HD-091A-12-

FA 

78,900 

10-10DD ½ 

Medium-High Medium-High  910-1456 

3 ½ 

1047-1267 

87,700 Low 

Low 

943-1458 

98,800 Low 

Medium-Low 

1084-1676 

O4HD-140A-16-

FA 

113,400 

11-10DD ¾ 

Low Medium-Low 

1279-1977 

5 ¾ 

1499-1879 

58,100 0-0-0 

0-0-0 

900 

73,700 1-0-1 

1-0-1 

1050 

O4HD-091A-V-F 

78,900 

11 10DD 

¾ 

1-0-0 1-0-0  1200 

3 ¾ 

312-1531 

87,700 1-0-0 

1-0-0 

1200 

98,800 0-1-1 

0-1-1 

1350 

O4HD-140A-V-F 

113,400 

11 10DD 

¾ 

0-1-0 0-1-0  1500 

5 ¾ 

312-1844 

(1)

 Heating Range values based on temperature rise. Upper values may exceed measured airflow values in Table A-3.      

(2)

 Nominal values only.

 

 

Содержание O4HD-091A-12-FA

Страница 1: ...WER ECM 8 FURNACE CONTROLS 9 OIL BURNER 9 FURNACE INSTALLATION SET UP 11 MAINTENANCE AND SERVICE 12 OPERATING INSTRUCTIONS 12 TABLE A 1 BECKETT OIL BURNER SET UP 13 TABLE A 2 DIRECT DRIVE BLOWER SET U...

Страница 2: ...f Oil Burning Equipment as well as in accordance with local codes In Canada the installation of the furnace and related equipment shall be installed in accordance with the regulations of CAN CSA B139...

Страница 3: ...able 1 Installation on a combustible floor requires a clearance of 1 inch Using a noncombustible material such as one inch thick channel iron or similar material can do this The furnace must be suppor...

Страница 4: ...VRV INCLUDED IN THIS KIT MUST BE USED IN CONJUNCTION WITH THE FURNACE BOOT CHIMNEY VENTING The chimney must be sized correctly and be in good repair If the chimney is oversized there is a high risk o...

Страница 5: ...on extension cord Change to straight or to long offset I Two or more openings to the same chimney Found by inspection from basement The least important opening must be closed using some other chimney...

Страница 6: ...urnace may be installed with a one pipe system with gravity feed or lift The maximum allowable lift on a single line system is 8 feet Lift should be measured from the bottom outlet of the tank to the...

Страница 7: ...tory is fed into pre programmed algorithms in the microprocessor to determine the correct motor output required to maintain constant airflow regardless of external static pressure The microprocessor a...

Страница 8: ...ng the dipswitch combination displayed in Table 5 This fan on delay can be set at 30 60 90 or 120 seconds This provides a delay between the burner ignition and blower start up to eliminate excessive f...

Страница 9: ...efficiency PREPARATIONS Drill a test port in the venting ideally at least 2 flue pipe diameters away from the furnace breeching if venting horizontally from the furnace or from the flue pipe elbow if...

Страница 10: ...s ducts the inside radius of elbows etc The supply air temperature should be measured at a point where the thermometer will be well within the air stream near the furnace supply air outlet Usually the...

Страница 11: ...tele spout oiler This oiler has a long flexible plastic spout DO NOT OVER LUBRICATE Excess oil may result in premature electric motor failure Inspect the blower fan Clean it if necessary Oil Burner Ma...

Страница 12: ...f air passing through the oil burner combustion chamber breeching etc up the chimney between burner cycles NOTE THE USE OF THIS CONTROL CAN OCCASIONALLY CAUSE POST COMBUSTION NOZZLE DRIP TABLE A 2 DIR...

Страница 13: ...w 1622 1602 1541 1499 1433 0 1 1 1215 1214 1214 1207 1204 1 0 0 1128 1108 1101 1095 1089 1 0 1 988 987 981 978 938 O4HD 091A V F 11 10 DD 9 6 50 80 F 0 0 0 788 787 781 777 756 1 1 0 1800 1800 1800 180...

Страница 14: ...ir Width A Depth B Height C D x E Side F x G Bottom Dia Height H Filter Perm Ship Weight lb O4HD 091A 22 31 50 1 2 20 1 2 x 20 14 x 22 14 x 22 5 42 16 x 25 x 1 190 O4HD 140A 22 31 58 1 8 20 1 2 x 20 1...

Страница 15: ...151B0801 R5 3 28 2006 15 APPENDIX A WIRING DIAGRAM O4HD 091A 12 FA and O4HD 140A 16 FA...

Страница 16: ...151B0801 R5 3 28 2006 16 APPENDIX B WIRING DIAGRAM O4HD 091A V F and O4HD 140A V F...

Страница 17: ...JURY PROPERTY DAMAGE OR DEATH ACCESSORIES The EFTB has provisions for supplying 115 volt power to an electronic air cleaner EAC as well as 115 volts to a line voltage humidifier or humidifier step dow...

Страница 18: ...park for 10 sec a Provides continuous spark after flame is sensed to assure that burner remains lit b Turns on LED diagnostic light c Starts carryover timer i Flame and call for heat are monitored If...

Страница 19: ...noid Valve LED Diagnostic Light RETURNS TO IDLE STATE FLAME FLAME FLAME FLAME NO FLAME NO FLAME FLAME LOST FLAME LOST REMAINS IN IDLE STATE R7184 SEQUENCE OF OPERATION LOCKOUT STATE R7184 Shuts off bu...

Страница 20: ...0 seconds b Burner motor is de energized Even though thermostat is still calling for heat c If circulator fan has started it continues through the selected heat fan off delay period Established flame...

Страница 21: ...t existing call for heat a Circulator fan turns off when heat fan off delay time is complete b Normal operation resumes electronic fan timer control is in standby mode awaiting next thermostat command...

Страница 22: ...shooting IMPORTANT Due to the potential hazard of line voltage only a trained experienced service technician should perform the troubleshooting procedure PRELIMINARY STEPS Check the diagnostic light f...

Страница 23: ...ce the R7184 control If the indicator light turns off replace cad cell bracket assembly Burner starts Trouble is in thermostat circuit Check thermostat wiring connections If connections are clean and...

Страница 24: ...Step 7 6 Reset oil primary control by pushing in and releasing red reset button Indicator light continues to flash at 1 Hz rate Verify that the control is not in restricted mode See notes at end of th...

Страница 25: ...each time a call for heat is successfully completed To reset from RESTRICTED MODE press and hold the reset button for 30 seconds When the LED flashes twice the device has reset NOTE Disable function P...

Страница 26: ...ht a maximum of 1500 in the presence of light Ensure that room light is not leaking into the cad cell compartment See diagnostic light section No fuel oil Check fuel oil supply Check that all hand ope...

Страница 27: ...r radiator Poor alignment between oil burner blast tube and fire pot Check alignment Blast tube should be centered with fire pot burner opening Oil burner head should be inch back from the inside surf...

Страница 28: ...re rise Slow down blower fan if necessary Supply air temperature too cool Excessive duct losses Check supply air ductwork Seal leaky joints and seams Insulate ductwork if necessary Fan control fan on...

Страница 29: ...151B0801 R5 3 28 2006 29 PARTS...

Страница 30: ...Filter 16 x 25 x 1 Permanent 2180023 23 Filter Frame End Support 5592B2 24 Junction Box 28723 25 Junction Box Cover 28722 26 Blower Assembly Complete Direct Drive 3 4 hp ECM O4HD 091A V F 30381 26a Bl...

Страница 31: ...unit 29161 20 Clean out Cover 2 per unit 29162 21 Filter Frame 16 x 25 x 1 18020 22 Filter Frame End Support 5592B2 23 Air Filter 16 x 25 x 1 Permanent 2180023 24 Junction Box 28723 25 Junction Box Co...

Страница 32: ...e Installed Contractor Contact Address Postal Code Telephone No After Hours No Service Contractor if different from Installation Contractor Service Tech Telephone No After Hours No Fuel Supplier Oil S...

Отзывы: