manualshive.com logo in svg
background image

31-5000737   Rev. 0   11-22   GEA

NF80LS

80% Upflow/Horizontal Single 

Stage Constant Torque Low NOx 

(<40 Ng/J) Gas Furnace

Service 

Manual

READ  CAREFULLY.   

KEEP THESE INSTRUCTIONS

.

Содержание GE NF80LS

Страница 1: ...31 5000737 Rev 0 11 22 GEA NF80LS 80 Upflow Horizontal Single Stage Constant Torque Low NOx 40 Ng J Gas Furnace Service Manual READ CAREFULLY KEEP THESE INSTRUCTIONS ...

Страница 2: ... see this symbol on labels or in manuals be alert to the potential for personal injury or death Electric shock hazard Can cause injury or death Before attempting to perform any service or maintenance turn the electrical power to unit OFF at disconnect switch es Unit may have multiple power supplies WARNING As with any mechanical equipment contact with sharp sheet metal edges can result in personal...

Страница 3: ...60 1 15 6 8 40 111 NF80L070S3B 66 000 53 000 80 00 1 1 2 3 1 2 120 60 1 15 6 8 40 127 NF80L090S4B 88 000 72 000 80 00 2 1 2 4 1 2 120 60 1 15 8 4 40 142 NF80L110S5C 110 000 90 000 80 00 4 5 1 2 120 60 1 15 10 9 40 160 Note For vent sizing and clearances to combustibles please reference installation instructions MAJOR MINOR REVISION CABINET WIDTH A 14 5 B 17 5 C 21 NOMINAL CFM 3 1200 CFM 4 1600 CFM...

Страница 4: ...d Low 1050 1025 985 945 905 870 830 Low 880 845 795 760 705 665 625 NF80L070S3B 1 2 10 x 10 40 70 High 1355 1330 1290 1245 1225 1190 1160 Med High 1225 1190 1155 1115 1045 1000 925 Med 1110 1060 1015 980 920 855 790 Med Low 1080 1035 970 930 865 790 735 Low 885 825 770 695 625 540 445 NF80L090S4B 3 4 10 x 10 35 65 High 1730 1690 1645 1615 1590 1545 N A Med High 1505 1460 1435 1395 1350 1300 1270 M...

Страница 5: ...ural to LP Kit 11K50 1 Stage 11K45 High Altitude 7500 Return Air Base 68W61 14 5 A Width 68W62 17 5 B Width 68W63 21 0 C Width Twinning Kit 16W72 Constant Torque Gas Furnace Twinning Kit Note For vent length and clearances to combustibles please reference installation instructions ...

Страница 6: ...switch and transformer Gas Valve Burner Box includes sensor ignitor and rollout switches Combustion Air Inducer Combustion Air Inducer Pressure Switch Heat Exchanger Primary Limit under combustion air inducer Make Up Box Blower Assembly Power Choke not on all models Parts Arrangement ...

Страница 7: ...s overcurrent protection to the transformer T1 The breaker is rated at 3A at 32V If the current exceeds this limit the breaker will trip and all unit operation will shutdown The breaker can be manually reset by pressing the button on the face Integrated Ignition Control Shock hazard Disconnect power before servicing Control is not field repairable If control is inoperable simply replace entire con...

Страница 8: ...emand 4 Low Flame Signal check flame sensor 5 Soft lockout burner failed to light exceeded maximum number of retries or recycles 6 Not Used 7 Primary or Secondary Limit Open or Soft Lockout Mode Limit Switch Open longer than 3 minutes 8 Rollout Switch Open 9 Pressure Switch failed to close or opened during heat demand 10 Soft lockout Pressure Switch opened 5 times during one heat demand 11 Pressur...

Страница 9: ...p time between trials of 35 seconds After a total of five trials for ignition including the initial trial the integrated control goes into Soft Lockout Flame Failure mode After a 60 minute reset period the integrated control will begin the ignition sequence again Fan Time Control Heating Fan On Time The fan on time of 30 seconds is not adjustable Heating Fan Off Time Fan off time time that the blo...

Страница 10: ... a high temperature limit Each furnace is equipped with two identical switches The limit is a N C SPST manual reset limit connected in series with the integrated control A92 When S47 senses rollout the integrated control immediately stops ignition and closes the gas valve If unit is running and flame rollout is detected the gas valve will close and integrated control will be disabled Rollout can b...

Страница 11: ...bustion Air Inducer Primary Limit Gas Valve Figure 6 The NF80LS uses an internally redundant valve to assure safety shut off If the gas valve must be replaced the same type valve must be used 24VAC terminals and valve switch are located on the valve All terminals on the gas valve are connected to wires from the integrated control 24V applied to the terminals energizes the valve Inlet and outlet pr...

Страница 12: ...or Wire from Integrated Control and Connect Alligator Clip to Flame Sensor Lead Flame Sensor Terminal Remove Sensor Wire from Integrated Control and Connect Alligator Clip to Terminal on Control DIGITAL METER To Control Sensor Terminal To flame sensor Set dial to measure dc microamps Red Collar Indicates Positive Lead ...

Страница 13: ... into terminals 2 and 4 use small diameter probes in order not to damage plug Check voltage during 20 second ignitor warm up period Voltage should read 120 volts 10 If voltage reads below these values check for correct supply voltage to furnace Meter set to ohms Meter set to ohms Integrated Control Board Detail Meter set to ohms Test 1 Check ignitor circuit for correct resistance Remove 4 pin plug...

Страница 14: ...he switch is a single pole single throw proving switch electrically connected to the furnace control The purpose of the switch is to prevent burner operation if the combustion air inducer is not operating or if the flue becomes obstructed On start up the switch senses that the combustion air inducer is operating It closes a circuit to the integrated control when pressure inside the combustion air ...

Страница 15: ...inducer then reinstall the mounting screws See unit Installation Instructions for more detail The combustion air pressure switch must be moved for horizontal discharge air left position IMPORTANT Figure 11 vent pipe vent pipe flue transition vent pipe FLOW AIR flue transition vent pipe pressure switch vent pipe In all positions route the wires away from moving parts and the heat of the inducer mot...

Страница 16: ...0mA Troubleshooting the Motor Troubleshooting the motor is an easy process Follow steps below 1 Shut off power to unit 2 Remove input plugs P48 and P49 from motor See Figure 14 for troubleshooting procedure If correct voltage is present in tests 1 and 2 and motor is not operating properly replace motor The motor is not field repairable If replacing the indoor blower motor or blower wheel is necess...

Страница 17: ... If 24 volts is not present problem may be up stream of plug P49 Proceed to test 4 Multi Meter set to VAC 12 0 12 0 24 Multi Meter set to VAC problem is with the harness If voltage is not present problem may be may be with the integrated control Check for 120 volts across terminals CIRC and Neutrals on the integrated control If voltage is present problem is with the harness If voltage is not prese...

Страница 18: ...may need to be repeated to purge air from gas line 12 If the appliance will not operate follow the instructions Turning Off Gas to Unit and call your service technician or gas supplier Turning Off Gas to Unit 1 Set the thermostat to the lowest setting 2 Turn off all electrical power to the unit if service is to be performed 3 Remove the upper access panel 4 Move gas valve switch to OFF position Do...

Страница 19: ...e to time in Table 8 If manifold pressure matches Table 10 and rate is incorrect check gas orifices for proper size and restriction Remove temporary gas meter if installed NOTE To obtain accurate reading shut off all other gas appliances connected to meter Capacity Seconds for One Revolution Natural LP 1 cu ft Dial 2 cu ft Dial 1 cu ft Dial 2 cu ft Dial 45 80 160 200 400 70 55 110 136 272 90 41 82...

Страница 20: ... 0 10 0 11 0 070 Natural 3 5 3 2 2 8 3 5 4 5 LP Propane 10 0 10 0 10 0 10 0 11 0 090 Natural 3 5 3 2 2 7 3 5 4 5 LP Propane 10 0 10 0 9 6 10 0 11 0 110 Natural 3 5 3 5 3 0 3 5 4 5 LP Propane 10 0 10 0 9 6 10 0 11 0 NOTE A natural to LP propane gas changeover kit is necessary to convert this unit Refer to the changeover kit installation instruction for the conversion procedure Table 10 Manifold and...

Страница 21: ...cates a poor or partial ground Compare the readings to Table 12 If the readings exceed the maximum shown in Table 12 make repairs before operating the furnace 2 In addition measure the AC voltage from Line Hot to Line Neutral spade terminals on the integrated control See Figure 17 This voltage should be in the range of 97 to 132 VAC Furnace Status Measurement VAC Expected Maximum Power On Furnace ...

Страница 22: ...turn air plenums Insert manometer hose flush with inside edge of hole or insulation Seal around the hose with permagum Connect the zero end of the manometer to the discharge supply side of the system On ducted systems connect the other end of manometer to the return duct as above 3 With only the blower motor running and the evaporator coil dry observe the manometer reading Adjust blower motor spee...

Страница 23: ...iness of burners and heat exchanger and clean if necessary 6 Check the cleanliness of blower assembly and clean the housing blower wheel and blower motor if necessary The blower motors are prelubricated for extended bearing life No further lubrication is needed 7 Inspect the combustion air inducer and clean if necessary 8 Evaluate the heat exchanger integrity by inspecting the heat exchanger per t...

Страница 24: ...t exchanger It may be necessary to spread cabinet side to allow more room If so remove five screws from the left side or right side of cabinet See Figure 21 10 Backwash using steam Begin from the burner opening on each clam Steam must not exceed 275 F 11 To clean burners run a vacuum cleaner with a soft brush attachment over the face of burners Visually inspect inside the burners and crossovers fo...

Страница 25: ...abinet 1 2 3 4 5 Heat Exchanger Gasket Collector Box Orifice Plate Flue Transition Pressure Switch Combustion Air Inducer Manifold And Gas Valve Retention Rings Cross Over Ignitor Flame Sensor Rollout Switches Figure 22 Burner Combustion Air Inducer Assembly Heat Exchanger Removal ...

Страница 26: ...Page 26 31 5000737 Rev 0 Wiring Diagram 045 3A 070 3A 090 4B 090 5C 110 5C 135 5D Figure 23 Wiring Diagram ...

Страница 27: ...GAS VALVE OFF COMBUSTION AIR INDUCER ON INDOOR BLOWER ON HEATING SPEED LED FLASHES CODE 11 PRESSURE SWITCH CLOSED GAS VALVE OFF COMBUSTION AIR INDUCER OFF INDOOR BLOWER OFF WITH DELAY Sequence holds until pressure switch opens or thermostat resets control NO NO YES YES IS VOLTAGE ABOVE 70 VOLTS LED FLASHES CODE 13 LOW LINE VOLTAGE CONTROL WILL NOT RESPOND TO A CALL FOR HEATING UNTIL VOLTAGE RISES ...

Страница 28: ... IS 60 MINUTE RESET PERIOD COMPLETE YES 4 SECONDS YES HAS CONTROL RESET IGNITION SEQUENCE FOUR TIMES FLAME SIGNAL 1 5 MICROAMPS OR GREATER YES YES YES ROLLOUT SWITCH CLOSED LED FLASHES CODE 8 ROLLOUT SWITCH OPEN GAS VALVE POWER OFF COMBUSTION AIR INDUCER POWER ON INDOOR BLOWER ON SEQUENCE HOLDS UNTIL ROLLOUT SWITCH IS RESET AND MAIN POWER IS INTERRUPTED OR THERMOSTAT IS CYCLED OFF ON FOR 1 SEC MIN...

Страница 29: ...RED CONTINUOUSLY IS ROLLOUT SWITCH CLOSED LED SLOW FLASH RATE REMAINS UNCHANGED THROUGHOUT COOLING CYCLE THERMOSTAT CALLS FOR COOLING COMPRESSOR CONTACTOR AND SYSTEM FAN ENERGIZED WITH 2 SECOND DELAY COOLING SPEED COMPRESSOR OFF THERMOSTAT OPENS SYSTEM FAN AND EAC TERM OFF WITH 45 SECOND DELAY NO NO LED FLASHES CODE 8 ROLLOUT SWITCH OPEN GAS VALVE OFF COMBUSTION AIR INDUCER ON INDOOR BLOWER ON SEQ...

Страница 30: ...RMOSTAT OPENS SYSTEM FAN SWITCHED TO COOL SPEED EAC TERM REMAINS ON THERMOSTAT OPENS MANUAL FAN SELECTION MADE AT THERMOSTAT CONTROL G ENERGIZES SYSTEM FAN AT FAN SPEED EAC TERM ENERGIZED NO YES YES NO SYSTEM FAN SWITCHES TO HEAT SPEAD AFTER 30 SECOND DELAY EAC AND HUM TERMINALS REMAIN ON SYSTEM FAN CONTINUES FAN SPEED WITHOUT INTERRUPTION EAC TERMINAL REMAIN ON HUM TERMINALS ARE ENERGIZED WITH CO...

Страница 31: ...Page 31 31 5000737 Rev 0 Notes ...

Страница 32: ...Printed in the U S A All specifications and illustrations subject to change without notice and without incurring obligations ...

Отзывы: