Figure 5. C8BA Coil Dimensions
2 1/2”
W
19 1/2”
1 3/8”
1”
12 1/8”
14 1/2”
H
Table 1. Coil Specifications
C8BA-
01830
036
042
Nominal Capacity (BTUH)
18,000 - 30,000
36,000
42,000
Nominal Airflow (CFM)
600 - 1,000
1,200
1,400
W - Width (in.)
18 1/8
18 1/8
18 1/8
H - Height (in.)
18
18
24 3/4
Connection - Liquid Line (in.)
3/8
3/8
3/8
Connection - Suction Line (in.)
3/4
3/4
7/8
Installed Orifice Size (in.)
.061
.067
.071
NOTES:
1. Individual restrictors are available by part number - PN664*** (where *** represents the size).
Example: 664103 is a restrictor 0.103 in diameter.
2.
Refer to sales specification sheets for Listed/Certified combinations of equipment and required accessories.
3.
Refer to the current AHRI directory for certified ratings of split systems.
4.
Based on a nominal 0.3” W.C. pressure drop across the coil.
5. TXV valve may be required to achieve AHRI rating