Steam-distribution pipe fitted on suction side:
Because of the under-pressure in the appliance or the duct
part, condensate may be kept back in the steam-distribution
pipe. If there is an outlet in the empty part of the humidifier,
the condensate can be bled off in the immediate vicinity.
An alternative method of bleeding off the condensate can be
seen in the diagram.
3.5 Fitting the blowers
For the humidifier to work best, correct steam distribution is essential. For this reason, the minimum distances must
be observed when installing the equipment.
Please note that only wall installation is possible with the econoVap.
Minimum distances for steam blowers 4-23 kg/h
Minimum distances for steam blowers 32-65 kg/h
8
Pressure-
compensation
hose
Stench trap
Type: Sperrfix 3
Tight-fitting
rubber bung
A
B
Fig. 3.21
Fig. 3.22
450 mm
min.
15 m
Typ 32: min. 1500 mm
Typ 45: min. 2000 mm
450 mm
Fig. 3.22
Fig. 3.22
Type A
B
min.
min.
4 kg
600 mm
3 m
8 kg
900 mm
5 m
15 kg
1000 mm
7 m
23 kg
1000 mm
10 m