P11:  Output current value 20 mA 

Description: Measured value assigned to 20 mA. The transmitted value is in accordance to the primary value (PV) (P01:a). 
Assignment can be done that the change in measured value and the change in the output value are the same (normal), or opposite directional (inverse 
operation). For example: 1 m level is 4 mA, 10 m level is 20 mA, or 1 m level is 20 mA and 10 m level is 4 mA.  
Default value: Maximum measurement range accordance to the nominal length of the device (mm). 
 

P12: - - b a: Output current mode, Error mode 

Parameter: P12: b, Output current mode 

Description: Current transmitter mode [AUTO, MANUAL] 

 

b = 0: AUTO, output current value is calculated from the measured value. 

 

b = 1: MANUAL, The Output current is the fixed current set-in parameter P8. In this case, the output current error setting is not valid either! 

Default value: AUTO 

Parameter: P12: a, Error mode 

Description: “Error indication” by the current output 

 

a = 0: HOLD, Error indication has no effect on the output current. In this case, it holds the last valid measurement result at the output. 

 

a = 1: 3.8 mA, Error indication: the output current gets 3.8 mA. 

 

a = 2: 22 mA, Error indication: the output current gets 22 mA. 

Attention!

 This error indication is active unless the failure is fixed, or until the failure terminates. 

Default value: HOLD 

P19:  HART polling address 

Description: HART polling address of the device (0…15).  
The polling address can be set between 0 and 15. For a single instrument the polling address is 0 and the output is 4…20 mA (analogue output).  
If multiple units are used in HART Multidrop mode (max. 15 pcs.) the polling addresses should differ from 0 (1…15), in this case the output current will be 
fixed at 4 mA. 
Default value: 0

 

P20: Damping time 

Description: Damping time is used to damp the unwanted fluctuations of the output and display. If the measured value changes rapidly the new value will 
settle with 1% accuracy after this set time. (damping according to an exponential function). 
Adjustable values: 0…99 sec. 
Default value: 0 sec 
 

Содержание Nivotrack MI-5 Series

Страница 1: ...mia505en2102p 1 16...

Страница 2: ...mia505en2102p 2 16...

Страница 3: ...mia505en2102p 3 16...

Страница 4: ...mia505en2102p 4 16...

Страница 5: ...RDERED 8 2 2 FLOAT SELECTION 8 3 TECHNICAL DATA 9 3 1 MEASUREMENT DATA MSZ EN 60770 1 2011 MSZ EN 61298 1 2009 MSZ EN 61298 3 2009 10 3 2 DIMENSIONS 11 3 3 ACCESSORIES 12 4 INTEGRATION INTO THE TECHNO...

Страница 6: ...uracy measurement of clean fluids Operating principle The magnetostrictive transmitter is using the special feature of the magnetostrictive wire spanned in the rigid probe A magnetic field excited in...

Страница 7: ...Y 1 BSP lower connection B 1 1 3 3 0 1 0 33 1 Transmitter with plastic coating X 2 BSP C 2 2 6 6 0 2 0 66 2 2 BSP lower connection F 3 3 10 0 3 1 3 1 NPT D 0 4 1 33 4 1 NPT lower connection E 0 5 1 6...

Страница 8: ...dium density Specific gravity 0 45 kg dm3 0 55 kg dm3 0 8 kg dm3 0 55 kg dm3 0 4 kg dm3 0 4 kg dm3 0 7 kg dm3 0 4 kg dm3 0 8 kg dm3 Material Titanium 1 4404 316L 1 4435 316L Titanium 1 4401 316 PVDF P...

Страница 9: ...cm 95 mm 3 74 float min 0 55 g cm 124 mm 4 88 float min 0 4 g cm PVDF float min 0 7 g cm3 Material of wetted parts Stainless steel 1 4571 316Ti floats see Float Selection PFA PVDF PP Ambient temperatu...

Страница 10: ...ce conditions Hysteresis under reference conditions 0 25 mm 0 01 Zero span in LEVEL measurement mode Anywhere within the active range Measurement range reducing Minimal range 32 mm 1 26 Maximum range...

Страница 11: ...mia505en2102p 11 16 3 2 DIMENSIONS STANDARD VERSION MI 5 M MINI VERSION MY 5 M MIF MIH MIU MYB MXU...

Страница 12: ...l as the calculations should be checked carefully Prior to the installation a preliminary operation check is suggested If necessary to change the default factory settings the programming should be per...

Страница 13: ...rrent output does not match device set program lit 1 short term non lighting saturation Parameters can set using a HART modem EView2 or PACTware program or MultiCONT process controller Parameters are...

Страница 14: ...rement range needs to be decreased virtually The absolute value of this number shall be less than the active measurement range Wrong configuration of the zero point offset can result negative level di...

Страница 15: ...ndication by the current output a 0 HOLD Error indication has no effect on the output current In this case it holds the last valid measurement result at the output a 1 3 8 mA Error indication the outp...

Страница 16: ...andling Form must be enclosed Download it from our website www nivelco com The device must be sent with a declaration of decontamination Please provide a statement in the declaration that the decontam...

Отзывы: