4.1.

 

WIRING 

This transmitter is designed to operate on 12.5…36 V DC power only.  

The measured voltage on the terminals of the unit should be at least 12.5 V. Using transmitter with HART

®

 a terminal resistance 

with a minimum value of 250 

 should be applied. 

CAUTION

! the enclosure of the transmitter should be grounded. Grounding resistance should be R 

 1 

. Shielding of the 

interconnecting cable should be grounded at the control room side. To avoid disturbing noises the interconnecting cable must not 
be led near to high voltage cables. Especially critical are inductive couplings of AC harmonics against which the protection of 
shielding is not effective. 

 

 

5.

 

PROGRAMMING 

LED display: 

 

continuously lit: normal operation 

 

off, 1 brief flash: no echo 

 

off, 2 short flashes: excitation signal generation error 

 

off, 3 short flashes: current generator fault, current output does not match device set program 

 

lit, 1 short-term non-lighting: saturation 

Parameters can set using a HART

®

 modem, EView2, or PACTware™ program or MultiCONT process controller. 

Parameters are entered as 4 place value decimal numbers for the parameters where it's indicated. Indication of each place value 

’ d c b a ’

, unused place 

values in the description: (-). The instrument ignores unused place values. 

P0: - c b -: Measuring unit, Dimension of the measuring unit 

Parameter: 

P0:c

, Measuring unit 

Description: This should be configured as the first step of the programming. Here you can choose the default unit system: 

 

c = 0: EU – European unit system 

 

c = 1: US – Anglo-Saxon unit system 

Default measuring unit system: c = 0: EU 

Parameter: 

P0: b

, Dimension of the measuring unit 

Description: The dimension of the unit can be specified in this menu: 

 

EU European unit system: b = 0: m; b = 1: cm; b = 2: mm 

 

US Anglo-Saxon unit system: b = 0: ft; b = 1: inch 

Default measuring unit: b = 2: mm 

ATTENTION! If the unit system or measuring unit is changed, after a warning message the device resets all the parameters. 

 

Содержание Nivotrack MI-5 Series

Страница 1: ...mia505en2102p 1 16...

Страница 2: ...mia505en2102p 2 16...

Страница 3: ...mia505en2102p 3 16...

Страница 4: ...mia505en2102p 4 16...

Страница 5: ...RDERED 8 2 2 FLOAT SELECTION 8 3 TECHNICAL DATA 9 3 1 MEASUREMENT DATA MSZ EN 60770 1 2011 MSZ EN 61298 1 2009 MSZ EN 61298 3 2009 10 3 2 DIMENSIONS 11 3 3 ACCESSORIES 12 4 INTEGRATION INTO THE TECHNO...

Страница 6: ...uracy measurement of clean fluids Operating principle The magnetostrictive transmitter is using the special feature of the magnetostrictive wire spanned in the rigid probe A magnetic field excited in...

Страница 7: ...Y 1 BSP lower connection B 1 1 3 3 0 1 0 33 1 Transmitter with plastic coating X 2 BSP C 2 2 6 6 0 2 0 66 2 2 BSP lower connection F 3 3 10 0 3 1 3 1 NPT D 0 4 1 33 4 1 NPT lower connection E 0 5 1 6...

Страница 8: ...dium density Specific gravity 0 45 kg dm3 0 55 kg dm3 0 8 kg dm3 0 55 kg dm3 0 4 kg dm3 0 4 kg dm3 0 7 kg dm3 0 4 kg dm3 0 8 kg dm3 Material Titanium 1 4404 316L 1 4435 316L Titanium 1 4401 316 PVDF P...

Страница 9: ...cm 95 mm 3 74 float min 0 55 g cm 124 mm 4 88 float min 0 4 g cm PVDF float min 0 7 g cm3 Material of wetted parts Stainless steel 1 4571 316Ti floats see Float Selection PFA PVDF PP Ambient temperatu...

Страница 10: ...ce conditions Hysteresis under reference conditions 0 25 mm 0 01 Zero span in LEVEL measurement mode Anywhere within the active range Measurement range reducing Minimal range 32 mm 1 26 Maximum range...

Страница 11: ...mia505en2102p 11 16 3 2 DIMENSIONS STANDARD VERSION MI 5 M MINI VERSION MY 5 M MIF MIH MIU MYB MXU...

Страница 12: ...l as the calculations should be checked carefully Prior to the installation a preliminary operation check is suggested If necessary to change the default factory settings the programming should be per...

Страница 13: ...rrent output does not match device set program lit 1 short term non lighting saturation Parameters can set using a HART modem EView2 or PACTware program or MultiCONT process controller Parameters are...

Страница 14: ...rement range needs to be decreased virtually The absolute value of this number shall be less than the active measurement range Wrong configuration of the zero point offset can result negative level di...

Страница 15: ...ndication by the current output a 0 HOLD Error indication has no effect on the output current In this case it holds the last valid measurement result at the output a 1 3 8 mA Error indication the outp...

Страница 16: ...andling Form must be enclosed Download it from our website www nivelco com The device must be sent with a declaration of decontamination Please provide a statement in the declaration that the decontam...

Отзывы: