mia505en2102p
12 / 16
3.3.
A
CCESSORIES
User’s and programming manual
Warranty Card
EU declaration of conformity
1 x gasket (klingerit oilit) for BSP threads only
4.
INTEGRATION INTO THE TECHNOLOGICAL PROCESS (INSTALLATION, WIRING)
When choosing the installation place please ensure proper space for later calibrations, verification or maintenance service.
Waving, vortex or vibration effects have negative influence on the measurement accuracy. To avoid these effects, the mounting placement should be
as far as possible from the sources of these disturbing effects for instance from openings of filling or emptying. These effects can be attenuated in
applications with rigid tube probes by the use of stilling pipe along the whole probe. Please consult with a NIVELCO distributor!
To ensure consistent and durable operation the measurement medium should be free of suspended solid materials, which could stick between the
float and the probe.
The unit should be protected against direct heat radiation.
Prior to the installation the mounting dimensions of the unit and the tank as well as the calculations should be checked carefully.
Prior to the installation a preliminary operation check is suggested.
If necessary to change the default factory settings the programming should be performed in accordance to the description in the 5
th
chapter.
The units are offering a wide variety of process connections according to the available order codes. The tank opening should be fit for the selected
level transmitter by means of the insertion hole is bigger than the float diameter. If this is not possible the float has to be removed from the probe and
when the unit is mounted into the tank the float can be mounted from inside of the vessel. The “UP” marking on the float ensures that the float is
mounted back in the correct position. See the drawing! Prior to finishing the mounting the spacer needed to assemble back between the float and the
counterweight.
ATTENTION!
In order to avoid damaging the probe, do not put it to torsion when installing or removing the unit. Therefore, special care has to be
taken when the process connection is being screwed into or out of the flange. The best is to hold the rigid part of the probe with a
suitable tool as long as the process connection is tightened to its place. Sliding sleeve must not be loosened during operation.