Function (Fct.)
Input Range
Description
2.1.1.5 SENSOR INFO
2.1.1.5.1 Sensor upper limit
= Probe length
Read-only Menu. Upper sensor limit
2.1.1.5.2 Sensor lower limit
= 0
Read-only Menu. Lower sensor limit
2.1.1.5.3 Sensor min. span
= 1 mm (3.3 ft)
Read-only Menu. Sensor minimum span.
2.1.2.0 DISPLAY
2.1.2.1 LENGTH
2.1.2.1.1 LENGTH UNIT
Select: m, cm, mm, inch, Ft, optional units
Length unit of displayed value
(level / distance).
The optional unit allows the user to define a new unit (name and factor)
see menu 1.2.1.3.
mm
2.1.2.1.2 DISPLAY FORMAT
0, 1, 2, 3, 4, 5, exponential format, auto
Number of decimal places.
Defines the displayed length values format (option of the HART
®
communicator H275).
2
2.1.2.1.3.0 DEFINE NEW UNIT
2.1.2.1.3.1 UNIT NAME
4 ASCII characters
Optional unit name.
User has to enter the unit name before using it in the menu “LENGTH
UNIT”.
„UNIT”
2.1.2.1.3.2 UNIT FACTOR
Enter values between 0.0 to 100.000
Optional unit factor. User has to enter the Unit Factor before using it in the
menu “LENGTH UNIT”.
With a factor 1.0, the unit is equivalent to one millimetre.
With a factor 1000.0, the unit is equivalent to one meter.
1.0
2.1.2.2.0 TÉRFOGAT
2.1.2.2.1 VOLUME UNIT
Select: m
3
, l, US Gal, Ft
3
, bbl, M
3
/h,
Ft
3
/h, kg, Metric Tons, US Tons
Unit for conversion values ("volume table").
The selected unit is only used to display the conversion value from the
strapping table.
m³
2.1.2.2.2 DISPLAY FORMAT
0, 1, 2, 3, 4, 5, exponential format, auto
Number of decimal places.
Defines the displayed volume value format.
(Option of the HART
®
communicator H275).
→
2
2.1.3.0
ANALOG OUTPUT
2.1.3.1 FUNCTION
I
Select:
Level,
Distance, Volume, Ullage volume
Current output function (measured value to be displayed).
Volume functions will appear if a volume table exists in menu 2.1.7.0.
Level