Function (Fct.)
Input Range
Description
2.1.3.2
RANGE I
Select a 4 – 20 mA
or 4 – 20 mA + 22 mA if error
Current output range 4
ؘ
– 20 mA (1st choice).
When the MicroTREK 2-wire is in error mode, the current output is frozen
except if the second choice is selected and then the current output is fixed
at 22 mA.
4 – 20 mA
2.1.3.3
ERROR DELAY
Select: No delay,
10 s, 20 s, 30 s, 1 min, 2 min, 5 min, 15 min
This menu is available in case if the range I menu is set to 4 – 20 mA with
error 22 mA.
This parameter sets the delay before the current output goes to 22 mA after
the error mode occurred.
No delay
2.1.3.4 SCALE
I
min. 4 mA
Enter value between 0 to Scale I max
Input the lower range value (corresponding to 4 mA) depending of the
parameter 2.1.3.1 chosen.
As per order
2.1.3.5 SCALE
I
max. 20 mA
Enter value between Scale I min
to tank height
Input the upper range value (corresponding to 20 mA) depending of the
parameter 2.1.3.1 chosen.
As per order
2.1.4.0 USER
DATA
2.1.4.1 TAG
00000 01
Tag number of devices.
2.1.4.2 SERIAL
NUMBER
Read-only menu. Each device has its own serial number
2.1.4.3 FRENCH
COMMISSION
NUMBER
Read-only
menu.
This number is factory preset.
Refer to this number in case of warranty or service claims.
2.1.4.4 GERMAN
COMMISSION
NUMBER
Read-only
menu.
This number is factory preset.
Refer to this number in case of warranty or service claims.
2.1.4.5
RELEASE NUMBER
Read-only menu.
Release number of the device (Software and Hardware version).