16 / 44
♦
spa580en22p06
A:
Shortest measurable distance
H:
Maximum measurable distance, also the
distance to zero level
B:
Volume associated with the highest
measurable level
C:
Total volume of the tank
Transmitted value
VOL
f
P40…P45
(H-DIST)
Parameters to set
P00
P01a
= 3
P02b
P04
= H
P05
≥
X
m
P40…P45
P02: - c b a Calculation units
FACTORY DEFAULT: 000
a
Temperature
The unit of temperature can be selected at this point.
EView2 setting:
“Device Settings”
→
“Measurement configuration”
→
“Temperature.”
0
°C
1
°F
b
Volume
*
Weight
(set also P32)
Volume flow
Metric
US
Metric
US
Metric
US
0
m
3
ft
3
tons
lb (pound)
m
3
/time
ft
3
/time
1
liter
gallon (BR)
tons
tons (BR)
liter/time
gallon/time
2
liter
gallon (US)
tons
tons (US)
liter/time
gallon/time
The unit of measure of the transmitted quantity for an instrument set to measure volume, mass or flow. The contents of the table is interpreted
in accordance with
P00c
,
P01a
and
P02c
. The instrument converts the measured level into volume, weight, or flow by calculating using a level-
dependent (non-linear) function or output correction table (OCT) according to
P40
. This parameter also gives the unit of measure of the “Output”
column of the OCT table.
EView2 setting:
“Device Settings”
→
“Measurement configuration”
→
“Engineering units.”