P01: - - - a Measurement Mode
FACTORY DEFAULT: 11
Parameter value “a” determines the basic measurement value transmitted. Subsequently, values for the relays are also relating to these quantities.
Setting the physical quantity associated with the
transmitted measurement unit. The instrument
measures distance. The other quantities are
calculated based on the specified container
parameters and material properties.
EView2
settings:
“Device Settings”
→
“Measurement configuration”
→
“Measurement
mode.”
a
Measurement mode
Transmitted value
0
Distance
Distance
1
Level
Level
2
Volume
Volume
3*
Mass
Mass
4
Flow
Volumetric flow
* See:
P32
A:
Shortest measurable distance
H:
Maximum measurable distance, also the
distance to the zero level
Transmitted value
DIST
LEV
=H-DIST
Parameters to set
P00
P01a = 0
P05
≥ X
m
P00
P01a = 1
P04
= H
P05
≥
X
m