12 / 44
♦
spa580en22p06
4.1
A
VAILABLE USER INTERFACES
The transmitter can be set up (programmed) using the following devices:
MultiCONT
Multichannel Process Controller
Ordered separately. Functions as a display as well.
HART
®
USB modem
UNICOMM SAT–504–0, –1, –2
Ordered separately. See chapter “5.3.1 Programming with the EView2 software.”
HART
®
USB modem
UNICOMM SAT–504–3
Ordered separately. See chapter “5.3.1 Programming with the EView2 software.”
The NiFlash software can also be used to update the device's firmware. See chapter
“6.1 Firmware
upgrade.”
5.
COMMISSIONING, SETTING UP
5.1
U
SAGE
If the device is connected correctly, it will click audibly for a short time after the power supply has been switched on. After 10…20 s, the ECHO LED will light up,
and the current output will display 4…20 mA. From the moment of switching on until the start of the current transmission proportional to the measured value, during
the initialization time, the value of the transmitted current will be as set in parameter
P12b "Current generator operating mode."
In this case, the device measures with the factory default settings. The factory settings can also be used for checking the functionality and solving the simplest
measurement tasks, but the possibilities of the device can only be utilized with the correct programming that fits the measured process. Therefore, to thoroughly
understand the operating characteristics and acquire the operational knowledge required to solve complex measurement tasks, it is also necessary to study the
programming chapters.
Single-LED status indications:
•
ECHO
-LED
–
ON if the
device is receiving a proper echo.
–
Blinking, if the device is searching for an echo.
–
Blinking rapidly, when the device is in level simulation mode.
•
COM
-LED
–
Blinking on HART communication
–
ON, when remote programming is in progress
–
Blinking for 4 seconds after the device is switched on: During this time,
a service communication link can be established. If it keeps blinking, it
indicates a firmware error.
•
RELAY
LED (optional)
–
Lights up, if CC-
C2 is ON
.
–
Does not light up, if CC-
C1 is ON
.