5
The following switches are located inside of the operating board front cover.
(20) Reset switch ····················· When this switch (red) is pressed to reset side, fire indicator etc
(turning on of zone alarm indicator, alarm delay indicator,
sounding of panel alarm sounder and zone alarm bell) are reset.
These switches are bounce-back type so that when you release
the switches after operation, they return to their normal
positions.
Please note that CPU needs rise time of 2~3 seconds after
operation.
(21) Alarm transfer ···················· When this switch is pressed to stop side, fire signal transfer to
isolation switch · security company etc is shut-off. At this moment, switch
operation light (4) starts to flicker.
(22) General alarm switch ········ When this switch is pressed to sound side, all of zone alarm
bells can be sounded even not at fire. Also, this switch
supersedes all other silence switches. At this moment, switch
operation indicator (4) starts to flicker.
If emergency PA signal transfer circuit is available, signal
transfer is output to all areas by this switch operation.
Note: Depending upon a type of system, bells may not be
installed so that careful attention must be paid to its handling.
(23) Hydrant isolation switch---- Fire pump interlocking by operation of manual alarm station is
cancelled. At isolation time, switch operation light (4) starts to
flicker.
(24) Emergency PA ················· When this switch is pressed to silence side, signal transfer to
isolation switch emergency PA silences. At this moment, switch operation light
(4)starts to flicker.
(25) Fire test switch ················· This switch is used to measure alarm delay time at fire test.
When the switch is pressed to test side, switch operation light
(4) starts to flicker. Also, when switch is returned to normal
position after pressing to test side for 1~2 seconds, alarm delay
confirmation light turns on. For details, please refer to fire test
items. Do not conduct battery test at the same time with fire
test.
(26) Zone selection tens digit ····· After pressing fire test switch (25) to test side, configure
tens digit by this switch.
(27) Zone selection ones digit----Press fire test switch (25) to test side and first configure tens
digit by circuit selection switch (26), then ones digit by this
switch and carry out the test.
(28) Auto Reset switch ············· When operation test of detector and manual alarm station is
conducted, press this switch to reset side, then switch operation
light (4) starts to flicker and fire holding function and alarm
delay function are cancelled.
(The control panel can be automatically reset, either by detector
reset pulse which is output every few seconds or by manual reset
operation of manual alarm station.) From then onward, fire test
is conducted per every one zone operation.
(29) Battery test switch ············ This switch is used for standby battery test. When the switch
is pressed to test side for about 1 minute and if Circuit Voltage
indicator (3)turns off, it is necessary to inspect charge circuit
and standby battery. The switch is bounce-back type so that
when you release the switch, it returns to normal position.
2. Name and Function of Each Section