Condensation drain / water seal
The Comfort unit is delivered with a 20mm condensation drain. (PVC, GF-fittings). The drain is
placed under the discharge.
The condensation drain should be carried with an even inclination of at least 1cm per
metre, frost-proof to the nearest outlet. The overflow from the safety valve should also be
carried to the nearest outlet.
To avoid frost problems it can be necessary to supply the condensation drain with a
heat
ing cable. It is the plumbers’ responsibility to secure the drain. (See Accessories)
When the system is running, there can be a vacuum of up to 500Pa (corresponding to 50mm water
column) in the outlet. For this reason, the difference in height in the water seal must be minimum
50mm. This means that the first bend of the water seal must be at least twice as long in order for
the system to be able to dispose of the condense water (see figure 3).
The condensation drain must be airproof from the unit to the water seal in order for the condensa-
tion water to be let away from the unit. If the condensation drain is not airproof false air will be
sucked in to the unit and the water will stay inside the unit.
The water seal can dry out and avoid the water from running out of the unit. Therefore the water
seal should be tested regularly and refilled with water if necessary. An elevated height of the water
seal will reduce the need for refilling with water.
Ø 20 mm drain
Unit
5 cm
5 cm
11,5 cm