Nilan reserves the right to alter these instructions without prior notice
Page 4 af 15
Power supply
Power supply including safety switch must be installed by an authorized electrician.
The Comfort-unit must be connected according to the attached electrical chart.
The unit is delivered with 3 m test cable for the CTS 700 panel. The panel should be connected to
the CTS 700 control in the unit with cable type cat 5e twisted in pairs. (Maximum length 20m).
The CTS 700 panel must be placed dry and frost-
proof. The panels’ integrated feeler prevents fur-
ther cooling of the building if the primary heat-supply stops by stopping the ventilation if the panel
feeler gets below a specific value. (Factory setting is 10°C; the value can be set from 1-20°C.)
Figure 1: CTS 700 control
If a water heating element is installed in the system, the regulation vent must be connected electri-
cally as described in the enclosed wiring diagrams.