6.4  Protections 

The Digistart D2 includes the following types of protection for the motor and starter: 

6.4.1  Excess Start Time Protection 

The Digistart D2 will trip on excess start time if the motor does not successfully start within the time 

selected in the Excess Start Time setting. This may indicate that the load has stalled.   
If the soft starter frequently trips on excess start time: 

  check that the Current Limit setting is high enough for the application 

  check that the Excess Start Time setting is long enough for the application 

  check that the load has not stalled or increased since the soft starter was installed 

 

6.4.2  Motor Overload Protection 

The Digistart D2 will trip on motor overload if it calculates that the motor has been running above its 

operating range for longer than the time selected in the Motor Trip Class setting. Motor Trip Class should 

be set to match the motor's locked rotor time. If this information is not available from the motor datasheet, 

use the default setting (Motor Trip Class = 10). Using a higher setting can damage the motor. 

 

NOTE

 

Motor overload protection does not protect the soft starter, and does not protect the motor from 

short circuit.     

 

 

6.4.3  Current Imbalance Protection 

The Digistart D2 will trip on current imbalance if the highest and lowest currents on the three phases vary 

by an average of 30% for more than 3 seconds. Current imbalance protection is not adjustable, and is 

only active when the average motor current is 50% or more of the programmed motor FLC.   
If the soft starter frequently trips on current imbalance: 

  check that there is no imbalance on the mains voltage (on the input side of the soft starter) 

  insulation test the motor 

  move all input cables over one position (move L1 cable to L2, move L2 cable to L3, move L3 

cable to L1) to rule out a cabling fault 

 

6.4.4  Supply Frequency Protection 

The soft starter will trip on supply frequency if the frequency rises above 72 Hz or falls below 40 Hz for 

more than five seconds while the soft starter is running. These trip points are not adjustable.   
In pre-start, starting and stopping modes the high and low frequency limits both apply with no time delay. 
A supply frequency trip will also occur if: 

  all three input phases are lost while the soft starter is running 

  all three input phases fall below 120 VAC at start or while the soft starter is running 

  the line contactor opens while running 

 

6.4.5  Bypass Overload Protection 

Bypass overload protection protects the soft starter from severe operating overloads while running. The 

protection is not adjustable and has two components: 

  The soft starter will trip if it detects overcurrent at 600% of the programmed motor full load 

current. 

  The soft starter models the temperature of the internal bypass relays and will trip if the 

temperature exceeds the safe operating level. 

If the trip occurs frequently, this indicates that the soft starter has not been selected correctly for the 

application. 

 

Digistart D2: User Guide 

 

17 

Issue: F 

 

Содержание D2-018

Страница 1: ......

Страница 2: ...impacts of its manufacturing operations To this end we operate an Environmental Management System EMS which is certified to the International Standard ISO 14001 When the products eventually reach the...

Страница 3: ...al Installation 5 2 Rating Data 6 2 1 Model Code 6 2 2 Current Ratings 6 3 Mechanical Installation 7 3 1 Dimensions and Weights 7 3 2 Physical Installation 8 4 Electrical Installation 9 4 1 Terminal l...

Страница 4: ...ed behaviour or through incorrect operation due to a fault In any application where a malfunction of the starter or its control system could lead to or allow damage loss or injury a risk analysis must...

Страница 5: ...starting immediately on first commissioning or operation after transportation always ensure that the control supply is applied before the power so that the contactor state is initialised 1 7 3 STOP f...

Страница 6: ...these ratings charts AC53b 4 6 354 1000 metres AC53b 4 20 340 1000 metres 40 C 50 C 40 C 50 C D2 018 18 A 17 A 17 A 15 A D2 034 34 A 32 A 30 A 28 A D2 042 42 A 40 A 36 A 33 A D2 048 48 A 44 A 40 A 36...

Страница 7: ...to models D2 140 to D2 200 while the product is energized provides protection against contact and ingress requirements of IP20 Models D2 140 to D2 200 can be installed with optional finger guards in...

Страница 8: ...h between the soft starter and solid surfaces D2 140 D2 200 Allow 200 mm 7 9 inch between the soft starter and solid surfaces Soft starters may be mounted side by side with no clearance that is if mou...

Страница 9: ...ee Technical Data on page 18 1 L1 3 L2 5 L3 2 T1 4 T2 6 T3 mm2 AWG CSL CSR CSH DI1 DI2 TH1 TH2 COM2 RLO2 COM1 RLO1 mm2 AWG 018 060 075 100 140 200 018 200 10427 A 10 35 8 2 10428 A 14 mm 0 55 inch 25...

Страница 10: ...VAC Start Stop To reset a trip open then close DI2 Stop To reset a trip open then close DI2 Start Fuse optional For sizing of the control fuse see Technical Data on page 18 The maximum cable run is d...

Страница 11: ...tomation system 4 1 5 Semiconductor Fuses Semiconductor fuses can be used with Digistart D2 soft starters to reduce the potential for damage to SCRs from transient overload currents and for Type 2 coo...

Страница 12: ...shunt trip device Soft starter installed with a system protection circuit breaker and main contactor 6 T3 4 T2 2 T1 5 L3 3 L2 1 L1 COM2 RLO2 M K1 K1 08332 B M Motor three phase K1 Main contactor COM2...

Страница 13: ...rent A and ramp time B Current ramp starting extends the time soft starter takes to reach the current limit and is suitable for generator set supplies loads requiring an extended start time or applica...

Страница 14: ...unction Select the function of the soft starter s programmable output terminals COM1 RLO1 When set to Run the relay will operate when the soft start is complete When set to Trip the relay will operate...

Страница 15: ...FWD FWD Phase sequence 08860 A Relay action The relay will close when a trip occurs Reset the trip and resume operation Phase sequence protection The soft starter will allow any phase sequence Digista...

Страница 16: ...munication Failure between module and network Check network connections settings and configuration x 9 Starter Communication Failure between starter and module Remove and refit accessory module x 10 B...

Страница 17: ...rotection is not adjustable and is only active when the average motor current is 50 or more of the programmed motor FLC If the soft starter frequently trips on current imbalance check that there is no...

Страница 18: ...ature 10 C to 60 C Storage temperature 25 C 60 C to 70 C for less than 24 hours Humidity 5 95 Relative Humidity Pollution degree Pollution Degree 3 Vibration IEC 60068 Test Fc Sinusoidal 4 Hz to 13 2...

Страница 19: ...Heat Dissipation During Start 3 watts ampere During Run 10 watts typical Approvals UL C UL UL 508 CE EN 60947 4 2 RoHS Compliant with EU Directive 2011 65 EU Digistart D2 User Guide 19 Issue F...

Страница 20: ...monitoring motor current motor temperature To use Digistart Soft with the Digistart D2 the soft starter must be fitted with a USB Module Modbus Module or a Remote Operator Digistart D2 Remote Keypad...

Страница 21: ...Digistart D2 User Guide 21 Issue F...

Страница 22: ......

Отзывы: