4
Electrical Installation
WARNING
Always apply control voltage before (or with) mains voltage.
CAUTION
Always follow the specified tightening torque for all power and ground terminal connections.
All Digistart D2 starters include an internal bypass relay that bypasses the soft starter SCRs during run.
This allows the Digistart D2 to be installed in a non-ventilated enclosure without an external bypass
contactor.
4.1 Terminal layout
For specifications and detailed technical data, see
Technical Data
on page 18.
1/L1, 3/L2, 5/L3, 2/T1, 4/T2, 6/T3
mm
2
(AWG)
CSL, CSR, CSH, DI1,
DI2, TH1, TH2, COM2,
RLO2, COM1, RLO1
mm
2
(AWG)
018 - 060
075 - 100
140 - 200
018 - 200
10
42
7.
A
10 - 35
(8 - 2)
10
42
8.
A
14 mm
(0.55 inch)
25 - 50
(4 - 1/10)
10
42
8.
A
14 mm
(0.55 inch)
n/a
26
(1.02)
11
(0.43)
Ø 8.5
(0.33)
10
42
9.
A
mm (inch)
0.14 - 1.5
(26 - 16)
10
42
8.
A
6 mm
(0.24 inch)
Torx (T20)
3 Nm
2.2 ft-lb
Torx (T20)
4 Nm
2.9 ft-lb
n/a
n/a
7 mm
3 Nm
2.2 ft-lb
7 mm
4 Nm
2.9 ft-lb
n/a
3.5 mm
0.5 Nm max
4.4 in-lb max
4.1.1 Ground terminal
All Digistart D2 soft starters have one ground terminal at the bottom of the starter.
Model
Terminal size
Maximum Torque
D2-018 to D2-060
4 mm
2 Nm
D2-075 to D2-200
6 mm
3 Nm
Digistart D2: User Guide
9
Issue: F