Nidec D2-018 Скачать руководство пользователя страница 20

 

 

 

Options 

Option name 

Function 

Digistart - DeviceNet 

Interface 

Fieldbus communications modules. 

 

 

NOTE

 

Ethernet communication modules are not suitable for use with 

Digistart D2 starters using 380/440 VAC control voltage. 

08

31

7.

B

 

Digistart - Ethernet IP 

Interface 
Digistart - Modbus 

Interface 
Digistart - Modbus TCP 

Interface 
Digistart - Profibus 

Interface 
Digistart - Profinet 

Interface 
Digistart - USB Interface 
Digistart-Soft 

The PC software is a fully functional program for controlling, monitoring and 

programming soft starters. It provides the following functionality: 
Operation of soft starter networks containing up to 254 individual soft starters   

  Operational control (Start, Stop, Reset, Quick Stop) 

  Starter status monitoring (Ready, Starting, Running, Stopping, 

Tripped) 

  Performance monitoring (motor current, motor temperature) 

To use Digistart-Soft with the Digistart D2, the soft starter must be fitted with a 

USB Module, Modbus Module or a Remote Operator.   

Digistart D2 - Remote 

Keypad 

The Remote Keypad and Interface Kit comprises a Remote Keypad Interface 

module and the Remote Keypad display and keypad. 

The Remote Keypad can control and monitor the soft starter's performance. 

Functionality includes: 

 

Operational control (Start, Stop, Reset, Quick Stop) 

 

Starter status monitoring (Ready, Starting, Running, Stopping, Tripped) 

 

Performance monitoring (motor current, motor temperature) 

 

Trip code display 

 

4-20 mA analog output (motor current) 

08

31

8.

A

 

Digistart D2 - Finger 

Guard Kit 

Finger guards may be specified for personnel safety. Finger guards fit over the 

soft starter terminals to prevent accidental contact with live terminals.  Finger 

guards provide IP20 protection when used with cable of diameter 22 mm or 

greater. 

08318.

A

 

 

 

20 

 

Digistart D2: User Guide 

 

 

Issue: F 

 

Содержание D2-018

Страница 1: ......

Страница 2: ...impacts of its manufacturing operations To this end we operate an Environmental Management System EMS which is certified to the International Standard ISO 14001 When the products eventually reach the...

Страница 3: ...al Installation 5 2 Rating Data 6 2 1 Model Code 6 2 2 Current Ratings 6 3 Mechanical Installation 7 3 1 Dimensions and Weights 7 3 2 Physical Installation 8 4 Electrical Installation 9 4 1 Terminal l...

Страница 4: ...ed behaviour or through incorrect operation due to a fault In any application where a malfunction of the starter or its control system could lead to or allow damage loss or injury a risk analysis must...

Страница 5: ...starting immediately on first commissioning or operation after transportation always ensure that the control supply is applied before the power so that the contactor state is initialised 1 7 3 STOP f...

Страница 6: ...these ratings charts AC53b 4 6 354 1000 metres AC53b 4 20 340 1000 metres 40 C 50 C 40 C 50 C D2 018 18 A 17 A 17 A 15 A D2 034 34 A 32 A 30 A 28 A D2 042 42 A 40 A 36 A 33 A D2 048 48 A 44 A 40 A 36...

Страница 7: ...to models D2 140 to D2 200 while the product is energized provides protection against contact and ingress requirements of IP20 Models D2 140 to D2 200 can be installed with optional finger guards in...

Страница 8: ...h between the soft starter and solid surfaces D2 140 D2 200 Allow 200 mm 7 9 inch between the soft starter and solid surfaces Soft starters may be mounted side by side with no clearance that is if mou...

Страница 9: ...ee Technical Data on page 18 1 L1 3 L2 5 L3 2 T1 4 T2 6 T3 mm2 AWG CSL CSR CSH DI1 DI2 TH1 TH2 COM2 RLO2 COM1 RLO1 mm2 AWG 018 060 075 100 140 200 018 200 10427 A 10 35 8 2 10428 A 14 mm 0 55 inch 25...

Страница 10: ...VAC Start Stop To reset a trip open then close DI2 Stop To reset a trip open then close DI2 Start Fuse optional For sizing of the control fuse see Technical Data on page 18 The maximum cable run is d...

Страница 11: ...tomation system 4 1 5 Semiconductor Fuses Semiconductor fuses can be used with Digistart D2 soft starters to reduce the potential for damage to SCRs from transient overload currents and for Type 2 coo...

Страница 12: ...shunt trip device Soft starter installed with a system protection circuit breaker and main contactor 6 T3 4 T2 2 T1 5 L3 3 L2 1 L1 COM2 RLO2 M K1 K1 08332 B M Motor three phase K1 Main contactor COM2...

Страница 13: ...rent A and ramp time B Current ramp starting extends the time soft starter takes to reach the current limit and is suitable for generator set supplies loads requiring an extended start time or applica...

Страница 14: ...unction Select the function of the soft starter s programmable output terminals COM1 RLO1 When set to Run the relay will operate when the soft start is complete When set to Trip the relay will operate...

Страница 15: ...FWD FWD Phase sequence 08860 A Relay action The relay will close when a trip occurs Reset the trip and resume operation Phase sequence protection The soft starter will allow any phase sequence Digista...

Страница 16: ...munication Failure between module and network Check network connections settings and configuration x 9 Starter Communication Failure between starter and module Remove and refit accessory module x 10 B...

Страница 17: ...rotection is not adjustable and is only active when the average motor current is 50 or more of the programmed motor FLC If the soft starter frequently trips on current imbalance check that there is no...

Страница 18: ...ature 10 C to 60 C Storage temperature 25 C 60 C to 70 C for less than 24 hours Humidity 5 95 Relative Humidity Pollution degree Pollution Degree 3 Vibration IEC 60068 Test Fc Sinusoidal 4 Hz to 13 2...

Страница 19: ...Heat Dissipation During Start 3 watts ampere During Run 10 watts typical Approvals UL C UL UL 508 CE EN 60947 4 2 RoHS Compliant with EU Directive 2011 65 EU Digistart D2 User Guide 19 Issue F...

Страница 20: ...monitoring motor current motor temperature To use Digistart Soft with the Digistart D2 the soft starter must be fitted with a USB Module Modbus Module or a Remote Operator Digistart D2 Remote Keypad...

Страница 21: ...Digistart D2 User Guide 21 Issue F...

Страница 22: ......

Отзывы: