Diagnostics
6.1 LEDs
08554.
B
LED Status
Ready
Run
Off
No control power
Motor not running
On
Ready
Motor running at full speed
Flash
Starter tripped
Motor starting or stopping
6.2 Trip Codes
The Ready LED will flash a different number of times to indicate the cause of the trip.
Ready LED
Description
x 1
Power Circuit: Check mains supply (L1, L2, L3), motor circuit (T1, T2, T3), soft starter
SCRs and bypass relays.
x 2
Excess Start Time: Check load, increase Current Limit or adjust Excess Start Time
setting.
x 3
Motor Overload: Allow motor to cool, reset soft starter and restart.
The soft starter cannot be reset until the motor has cooled.
x 4
Motor Thermistor: Check motor ventilation and thermistor connection TH1, TH2. Allow
motor to cool.
x 5
Current imbalance: Check for mains supply or line current imbalance (L1, L2, L3).
x 6
Supply Frequency: Check mains voltage is available and supply frequency is in range.
x 7
Phase sequence: Check for correct phase sequence.
x 8
Network Communication Failure (between module and network): Check network
connections, settings and configuration.
x 9
Starter Communication Failure (between starter and module): Remove and refit accessory
module.
x 10
Bypass Overload: Starter rating may be too low for the application.
6.3 Reset
Trips can be cleared by pressing the Reset button on the soft starter, sending a Reset command from the
serial communications network, or by switching the control inputs.
To clear a trip via the control inputs, the soft starter requires a closed to open transition on the stop input (DI2).
•
In three-wire control, use the external stop button to momentarily open the stop input (open
CSL-DI2).
•
In two-wire control, if the soft starter tripped with a start signal present, remove the start signal
(open CSL to DI1, DI2).
•
In two wire control, if the Digistart D2 tripped with no start signal present (eg Digistart D2 motor
thermistor trip), apply then remove the start signal (close then reopen CSL to DI1, DI2).
The Reset button is located on the front of the unit, above the adjustment switches.
The soft starter will trip again immediately if the cause of the trip still exists.