Nidec D2-018 Скачать руководство пользователя страница 16

 

 

 

Diagnostics 

6.1  LEDs 

08554.

B

 

LED Status 

Ready 

Run 

Off 

No control power 

Motor not running 

On 

Ready 

Motor running at full speed 

Flash 

Starter tripped 

Motor starting or stopping 

 

 

 

 

6.2  Trip Codes 

The Ready LED will flash a different number of times to indicate the cause of the trip. 

Ready LED 

Description 

  x 1 

Power Circuit: Check mains supply (L1, L2, L3), motor circuit (T1, T2, T3), soft starter 

SCRs and bypass relays. 

  x 2 

Excess Start Time: Check load, increase Current Limit or adjust Excess Start Time 

setting. 

  x 3 

Motor Overload: Allow motor to cool, reset soft starter and restart.   

The soft starter cannot be reset until the motor has cooled. 

  x 4 

Motor Thermistor: Check motor ventilation and thermistor connection TH1, TH2. Allow 

motor to cool. 

  x 5 

Current imbalance: Check for mains supply or line current imbalance (L1, L2, L3). 

  x 6 

Supply Frequency: Check mains voltage is available and supply frequency is in range. 

  x 7 

Phase sequence: Check for correct phase sequence. 

  x 8 

Network Communication Failure (between module and network): Check network 

connections, settings and configuration. 

  x 9 

Starter Communication Failure (between starter and module): Remove and refit accessory 

module. 

  x 10 

Bypass Overload: Starter rating may be too low for the application. 

 

6.3  Reset 

Trips can be cleared by pressing the Reset button on the soft starter, sending a Reset command from the 

serial communications network, or by switching the control inputs. 
To clear a trip via the control inputs, the soft starter requires a closed to open transition on the stop input (DI2). 

  In three-wire control, use the external stop button to momentarily open the stop input (open 

CSL-DI2). 

  In two-wire control, if the soft starter tripped with a start signal present, remove the start signal 

(open CSL to DI1, DI2). 

 

  In two wire control, if the Digistart D2 tripped with no start signal present (eg Digistart D2 motor 

thermistor trip), apply then remove the start signal (close then reopen CSL to DI1, DI2). 

 

The Reset button is located on the front of the unit, above the adjustment switches. 

 

The soft starter will trip again immediately if the cause of the trip still exists. 

 

16 

 

Digistart D2: User Guide 

 

 

Issue: F 

 

Содержание D2-018

Страница 1: ......

Страница 2: ...impacts of its manufacturing operations To this end we operate an Environmental Management System EMS which is certified to the International Standard ISO 14001 When the products eventually reach the...

Страница 3: ...al Installation 5 2 Rating Data 6 2 1 Model Code 6 2 2 Current Ratings 6 3 Mechanical Installation 7 3 1 Dimensions and Weights 7 3 2 Physical Installation 8 4 Electrical Installation 9 4 1 Terminal l...

Страница 4: ...ed behaviour or through incorrect operation due to a fault In any application where a malfunction of the starter or its control system could lead to or allow damage loss or injury a risk analysis must...

Страница 5: ...starting immediately on first commissioning or operation after transportation always ensure that the control supply is applied before the power so that the contactor state is initialised 1 7 3 STOP f...

Страница 6: ...these ratings charts AC53b 4 6 354 1000 metres AC53b 4 20 340 1000 metres 40 C 50 C 40 C 50 C D2 018 18 A 17 A 17 A 15 A D2 034 34 A 32 A 30 A 28 A D2 042 42 A 40 A 36 A 33 A D2 048 48 A 44 A 40 A 36...

Страница 7: ...to models D2 140 to D2 200 while the product is energized provides protection against contact and ingress requirements of IP20 Models D2 140 to D2 200 can be installed with optional finger guards in...

Страница 8: ...h between the soft starter and solid surfaces D2 140 D2 200 Allow 200 mm 7 9 inch between the soft starter and solid surfaces Soft starters may be mounted side by side with no clearance that is if mou...

Страница 9: ...ee Technical Data on page 18 1 L1 3 L2 5 L3 2 T1 4 T2 6 T3 mm2 AWG CSL CSR CSH DI1 DI2 TH1 TH2 COM2 RLO2 COM1 RLO1 mm2 AWG 018 060 075 100 140 200 018 200 10427 A 10 35 8 2 10428 A 14 mm 0 55 inch 25...

Страница 10: ...VAC Start Stop To reset a trip open then close DI2 Stop To reset a trip open then close DI2 Start Fuse optional For sizing of the control fuse see Technical Data on page 18 The maximum cable run is d...

Страница 11: ...tomation system 4 1 5 Semiconductor Fuses Semiconductor fuses can be used with Digistart D2 soft starters to reduce the potential for damage to SCRs from transient overload currents and for Type 2 coo...

Страница 12: ...shunt trip device Soft starter installed with a system protection circuit breaker and main contactor 6 T3 4 T2 2 T1 5 L3 3 L2 1 L1 COM2 RLO2 M K1 K1 08332 B M Motor three phase K1 Main contactor COM2...

Страница 13: ...rent A and ramp time B Current ramp starting extends the time soft starter takes to reach the current limit and is suitable for generator set supplies loads requiring an extended start time or applica...

Страница 14: ...unction Select the function of the soft starter s programmable output terminals COM1 RLO1 When set to Run the relay will operate when the soft start is complete When set to Trip the relay will operate...

Страница 15: ...FWD FWD Phase sequence 08860 A Relay action The relay will close when a trip occurs Reset the trip and resume operation Phase sequence protection The soft starter will allow any phase sequence Digista...

Страница 16: ...munication Failure between module and network Check network connections settings and configuration x 9 Starter Communication Failure between starter and module Remove and refit accessory module x 10 B...

Страница 17: ...rotection is not adjustable and is only active when the average motor current is 50 or more of the programmed motor FLC If the soft starter frequently trips on current imbalance check that there is no...

Страница 18: ...ature 10 C to 60 C Storage temperature 25 C 60 C to 70 C for less than 24 hours Humidity 5 95 Relative Humidity Pollution degree Pollution Degree 3 Vibration IEC 60068 Test Fc Sinusoidal 4 Hz to 13 2...

Страница 19: ...Heat Dissipation During Start 3 watts ampere During Run 10 watts typical Approvals UL C UL UL 508 CE EN 60947 4 2 RoHS Compliant with EU Directive 2011 65 EU Digistart D2 User Guide 19 Issue F...

Страница 20: ...monitoring motor current motor temperature To use Digistart Soft with the Digistart D2 the soft starter must be fitted with a USB Module Modbus Module or a Remote Operator Digistart D2 Remote Keypad...

Страница 21: ...Digistart D2 User Guide 21 Issue F...

Страница 22: ......

Отзывы: