The driver output can be configured as Alarm output by modifying the 

Holding Register 46

 to value 1. During the normal functioning, 

the value is 0V and, when an alarm occurs, the output value is 5V (or 10V depending on the fan model).

18.4  Digital Alarm Output 

The alarms are automatically reset following the action of the table below: 

18.5  Alarm Reset 

Operating Mode

Input Type

Action

Analog

1, 4, 7, 10

Signal set to 0V

Fixed

2, 6, 9, 12

Registers 21, 39, 30 and 50 set to 0

As conerns the Temporary Modbus mode, it is necessary to reset the fan by setting the 

Holding Register 0

 to value=1 instead of 

setting to 0 the 

Register 66

.

Temporary

0, 5, 8, 11 

Register 0 set to 1 

The Holding Register 0 is a general reset and works also in the Analog mode and Fixed mode. 

19.  AVAILABLE SOFTWARE 

A freeware software is available on 

Nicotra Gebhardt

 site (http://www.nicotra-gebhardt.com) for monitoring the fan. Please refer 

to the related manual for more details

The software can be used for configuring the fan and monitoring the performance. 

The performance is estimated through an algorithm and, therefore, subjected to variable tolerance depending on the working 

point, airflow stability and the constant algorithm resolution itself. 

WARNING

WARNING

Содержание DDMP 10/10

Страница 1: ...Rev 0 05 11 2020 EC FAN DDMP OPERATING MANUAL Regal Beloit Italy S p A Via Modena 18 24040 Ciserano BG ITALY Phone 39 035 873 111 Fax 39 035 884 319 www regalbeloit com...

Страница 2: ......

Страница 3: ...NICAL FEATURES 14 8 1 Dimensional drawings 14 8 2 LG and RD versions 24 9 INSTALLATION 25 9 1 Commisioning 25 9 2 Operation 25 9 3 Ambient operating condition 25 9 4 Fan installation 25 9 5 Accessory...

Страница 4: ...emulation 42 10 3 2 Modbus temporary asynchronous emulation 42 10 3 3 Modbus fixed asynchronous emulation 42 10 3 4 Asynchronous emulation curves examples 43 10 4 PID closed control loop 43 10 4 1 An...

Страница 5: ...lave 0 10V PWM out for other drivers 49 16 VARIABLE SWITCHING FREQUENCY for 3 phase 4 kW only 49 17 COMMUNICATION 49 17 1 Temporary holding register 50 17 2 Fixed holding register 50 17 3 Holding regi...

Страница 6: ...e user of the potential personal damage that may result from an incorrect use of the machine or from the non compliance with the use and maintenance instructions Failure to comply with these safety me...

Страница 7: ...e the DDMP fan is installed Before doing any maintenance make sure that the power supply and the batteries have been disconnected Install an all pole disconnecting device in the power supply system in...

Страница 8: ...nical Service has repaired it Theinstaller and themaintenance man must know the content of this manual Although themain features of theequipment described in this manual are not subject to change the...

Страница 9: ...h accompanies each product or ask your Nicotra Gebhardt sales representative for additional information 2 1 Mechanical and electrical safety Single phase drive systems DDMP 1 kW DDMP 2 kW The drivers...

Страница 10: ...APACITOR VALUE WHEN PRESENT 11 MAXIMUM CURRENT INPUT 12 MOTOR RATED POWER 13 RATED RPM To improve the Electromagnetic compatibility a ferrite should be put on the power supply cable close to the drive...

Страница 11: ...tion or since operating the fan for at least half an hour continuously The storage site shall have a temperature between 20 C and 70 C a Relative Humidity lower than 75 and not be subject to condensat...

Страница 12: ...he DDMP fan check to ensure that all of the items listed are present and that there are no visible signs of damage 1 Remove the fan from the box 2 Remove all the components from the packaging WARNING...

Страница 13: ...t motor with its electronic driver has a much higher energy efficiency in comparison with a drive system based on a conventional AC motor Energy saving system High efficiency EC motor Compact and stre...

Страница 14: ...20 C 40 C IP 55 9 7 1416A0 1431A5 1 Ph 4 51 1035 20 C 40 C IP 55 9 9 1416A1 1431A5 1 Ph 4 5 1040 20 C 40 C IP 55 9 9 1416A4 1431A8 1 Ph 9 42 2213 20 C 40 C IP 55 9 9 1416A4 1431G0 3 Ph 3 43 2140 20 C...

Страница 15: ...Rev 0 05 11 2020 OPERATING MANUAL OPERATING MANUAL EN EN 15 60 6M04A0 DDMP 7 7 1416A0 DRIVER 6M04E0 DDMP 7 7 1416A0 DRIVER FL 6M04X1 DDMP 7 7 TIG 1416A3 DRIVER FL...

Страница 16: ...Rev 0 05 11 2020 OPERATING MANUAL OPERATING MANUAL EN EN 16 60 6M04C7 DDMP 7 9 1416A1 DRIVER 6M04F7 DDMP 7 9 1416A1 DRIVER FL 6M04A5 DDMP 8 7 TIG 1416A0 DRIVER...

Страница 17: ...Rev 0 05 11 2020 OPERATING MANUAL OPERATING MANUAL EN EN 17 60 6M04A6 DDMP 8 9 TIG 1416A1 DRIVER 6M04E6 DDMP 8 9 TIG 1416A1 DRIVER FL 6M04E5 DDMP 8 7 TIG 1416A0 DRIVER FL...

Страница 18: ...Rev 0 05 11 2020 OPERATING MANUAL OPERATING MANUAL EN EN 18 60 6M04E9 DDMP 225 240 1416A1 DRIVER FL 6M04A1 DDMP 9 7 1416A0 DRIVER 6M04A9 DDMP 225 240 1416A1 DRIVER...

Страница 19: ...Rev 0 05 11 2020 OPERATING MANUAL OPERATING MANUAL EN EN 19 60 6M04A2 DDMP 9 9 1416A1 DRIVER 6M04E2 DDMP 10 8 1416A1 DRIVER FL 6M04E1 DDMP 9 7 1416A0 DRIVER FL...

Страница 20: ...Rev 0 05 11 2020 OPERATING MANUAL OPERATING MANUAL EN EN 20 60 6M04E3 DDMP 10 8 1416A2 DRIVER FL 6M04A4 DDMP 10 10 1416A2 DRIVER 6M04A3 DDMP 10 8 1416A2 DRIVER...

Страница 21: ...Rev 0 05 11 2020 OPERATING MANUAL OPERATING MANUAL EN EN 21 60 6M04H0 DDMP 9 9 1416A4 DRIVER 6M04K0 DDMP 9 9 1416A4 DRIVER FL 6M04E4 DDMP 10 10 1416A2 DRIVER FL...

Страница 22: ...Rev 0 05 11 2020 OPERATING MANUAL OPERATING MANUAL EN EN 22 60 6M04H1 DDMP 10 8 1416A4 DRIVER 6M04K1 DDMP 10 8 1416A4 DRIVER FL 6M04H2 DDMP 10 10 1416A4 DRIVER...

Страница 23: ...Rev 0 05 11 2020 OPERATING MANUAL OPERATING MANUAL EN EN 23 60 6M04H3 DDMP 12 9 1416A4 DRIVER 6M04K3 DDMP 12 9 1416A4 DRIVER FL 6M04K2 DDMP 10 10 1416A4 DRIVER FL...

Страница 24: ...on the fan is delivered in LG version counter clockwise rotation For accessibility needs the fan can be required in RD version clockwise rotation Each version is supplied with different motor connecti...

Страница 25: ...rding to any local legislation or codes WARNING WARNING The driver operates at high voltages Certain parameter settings may cause the driver to restart automatically after an input power failure CAUTI...

Страница 26: ...32 255 288 311 131 142 5 9 9 8 9 Tig RA60055ZZ0000000 298 255 354 311 164 142 5 10 8 RA60046ZZ0000000 265 284 321 340 147 5 157 10 10 RA60066ZZ0000000 331 284 387 340 180 5 157 12 9 RA60058ZZ0000000 3...

Страница 27: ...288 311 131 142 5 9 9 8 9 Tig R609A2 298 255 354 311 164 142 5 10 8 R609A3 265 284 321 340 147 5 157 10 10 R609A4 331 284 387 340 180 5 157 12 9 R609A5 309 334 365 390 169 5 182 12 12 R609A6 395 334 4...

Страница 28: ...153 161 153 12 12 RA80008ZZ0000000 491 521 395 295 230 38 408 445 421 332 266 232 224 161 153 161 153 15 11 RA8000BZZ0000000 569 609 373 343 264 38 495 423 399 380 309 272 258 197 211 201 200 15 15 RA...

Страница 29: ...d 18 18 the guard can be fixed to the back inserting a fifth M5 thread on a 6 hole on the back itself Size Code A B C D E F 7 7 R722N6 125 25 75 230 9 7 R722N7 150 25 100 230 9 9 R722N8 150 25 100 296...

Страница 30: ...terials 235 JR steel according to UNI EN 10025 Surface Fe Zn 8 according to UNI EN ISO 2081 Assembly Fix the protection guards using self threading screws 3 5 x 9 5 on the 3 2 5 holes 6 of the inlet c...

Страница 31: ...LED 5 Relay connection 2 1 3 4 DDMP 1 05kW 1 Phase 2 1 3 4 DDMP 2 1kW 1 Phase DDMP 2 65kW 3 Phase 1 2 3 4 5 OUT GND B A GND IN2 24V 10V IN0 IN1 PE T S R PE U V W NO C CN O ANALOG INPUT ENABLE 10V 24V...

Страница 32: ...e the motor connection is already done by Nicotra Gebhardt DDMP 1 05kW 1 Phase Single Phase 220 240V 10 50 60Hz The performance in the range 200V 264V 50Hz 60Hz is always the same due to the PFC modul...

Страница 33: ...4 GND 5 B 6 A 7 OUT TACHO OUT ANALOGUE SIGNAL IN MODBUS RS485 6 A 5 B 4 GND 3 10V 2 IN 1 GND TACHO OUT MODBUS RS485 ANALOGUE SIGNAL IN EXTERNAL FAN POWER SUPPLY 7 OUT 8 FAN 9 12V 7 ANALOG INPUT 8 ENA...

Страница 34: ...paragraphs 9 6 3 3 and 13 3 WARNING WARNING Do not use devices having the signal GND connected to the NEUTRAL cable of the power supply The driver may be damaged or not functioning properly The avail...

Страница 35: ...occurs when a fan is forced to run forward or backward rotation with a speed higher than 150 rpm If an ext 4 20mA device is used it is necessary to add 0 1 precision resistances between the ANALOG INP...

Страница 36: ...ion 2 With the driver powered off through an UART serial connection To connect OFFLINE the driver to a PC when the fan is powered off a USB to UART converter can be used K431A6 for 1 phase drivers and...

Страница 37: ...h only As an alternative to this operating mode it is possible to install the airflow measuring and adjusting system see picture aside which is composed of pressure tapping block W89041 connected to t...

Страница 38: ...1 Ph only The 12V power supply can be used to provide power to the pressure transducer K43198 where a 24V supply is not available An auxiliary power supply of 12V is available on the 2 1kW Single Phas...

Страница 39: ...fan is in the dragging phase 9 6 3 7 Relay for DDMP 2 65kW 3 Ph only A relay is available on the Three Phase drivers It is suitable for 250Vac 30Vdc 5A When the driver is powered off the relay is open...

Страница 40: ...analog signal can be read from the Input Register 14 For more details refer to the ANNEX Analog Signal Considerations The MAX and min speed default values are in function of the fan sizes 10 1 1 Analo...

Страница 41: ...limits are determined by the Safe Operating Area 10 2 1 Analog constant airflow INPUT TYPE 5 Through this setting the fan runs at the constant airflow defined by modifying the Holding Register 66 The...

Страница 42: ...rformance and vice versa INPUT TYPE 8 Through this setting the fan emulates an ACIM motor and the slip is defined by modifying the Holding Register 66 The setting is maintained meanwhile the fan is po...

Страница 43: ...KP Proportional Gain Holding Register 51 Kl Integral Gain Holding Register 52 KD Derivative Gain Holding Register 53 Time TPID Holding Register 54 The following equations represent the simplified PID...

Страница 44: ...alue stored the related register Fan is put in stop mode and after the data are saved the fan follows the target corresponding to the value stored into the related register Fixed Setting Temporary Set...

Страница 45: ...for 1 phase 1 05 kW only To activate this feature the Holding Register 46 must be set at value 3 and the low value of the Speed Threshold must be set into the Holding Register 16 While the high value...

Страница 46: ...size and the wheel inertia The acceleration and deceleration values are different and to avoid overvoltage alarm or loss of synchronism alarm the deceleration is always lower 11 6 Soft start During t...

Страница 47: ...must be multiplied by 3 2 The value can be monitored through the Input Register 13 13 3 Enable Function for 3 phase only A safety enable function is available and it is active for the Operating Modes...

Страница 48: ...uration must be set on the slave fan for a Master Slave connection It is possible to drive two fans in a master and slave configuration by setting the MASTER in any preferred mode and the SLAVE in Mas...

Страница 49: ...ault 1 Odd parity 1 Stop Bit 2 Even parity 1 Stop Bit Supported Function 03 Read Holding Registers 04 Read Input Registers 06 Write Single Holding Register Modbus Communication Timeout With this featu...

Страница 50: ...possible to read its value The setting remains active until the fan is powered on If the fan is powered off but there is a residual charge the microcontroller of the driver is still functioning Theref...

Страница 51: ...fan by writing the value 1 on it This register automatically retun to value 0 after being reset The driver will reset any error condition and it will try to restart Allowed values 0 and 1 Default valu...

Страница 52: ...d Low RPM This register can be used to set the speed threshold low The register is active when the register 46 is set to the value 3 Allowed values 0 Speed Threshold High Default value 0 Holding Regis...

Страница 53: ...orary Constant Airflow The constant airflow is set by modifying the register 66 6 Modbus Fixed Constant Airflow The constant airflow is set by modifying the reg 39 7 Analog Asynchronous Emulation The...

Страница 54: ...000 4500 5000 4500 5000 2 65kW 3 Phase 5000 4500 5000 5000 5000 4kW 3 Phase Holding Register 45 Modbus Address Adim This register can be used to change the Modbus address of a driver Allowed values 1...

Страница 55: ...olding Register is set to the value 12 Holding Register 51 Kp Adim This register can be used to set the Proportional Gain of the PID control Allowed values 0 32767 Default value 0 Holding Register 52...

Страница 56: ...ster 3 Measured Speed rpm This register indicates the speed during the functioning Input Register 9 Bus Voltage 10 1 V This register indicates the rectified voltage after the PFC stage Input Register...

Страница 57: ...lied by 10V 216 to have the corresponding voltage value Input Register 31 Measured Power W This register indicates the absorbed power Input Register 32 Input Current mA This input indicates the input...

Страница 58: ...er 10 and Input Register 17 are indicated 18 2 Modbus registers Alarm description Alarm 1 Alarm 2 Description Actions Type 0 0 Default operation No Errors No Actions ALARM 1 1 0 Memory error Blocking...

Страница 59: ...Temporary Modbus mode it is necessary to reset the fan by setting the Holding Register 0 to value 1 instead of setting to 0 the Register 66 Temporary 0 5 8 11 Register 0 set to 1 The Holding Register...

Страница 60: ...Rev 0 05 11 2020 OPERATING MANUAL OPERATING MANUAL EN EN 60 60 Regal Beloit Italy S p A Via Modena 18 24040 Ciserano BG ITALY Phone 39 035 873 111 Fax 39 035 884 319 www regalbeloit com...

Отзывы: