Rev. 0 - 05/11/2020
OPERATING MANUAL
OPERATING MANUAL
EN
EN
32/60
Make sure that a differential switch (circuit breaker) has been installed upstream the line and that it functions properly.
Before carrying out any intervention on the electrical system, disconnect the power supply by means of main switch.
Work on the driver/fan by unqualified personnel or failure to comply with warnings can result in severe personal injury or serious
damage to material.
Only suitably qualified personnel trained in the set-up, installation, commissioning and operation of the product should carry
out work on the driver/fan. This driver must be grounded.
The power supply terminals L, N (1-Phase) or R, S, T (3-Phase) and the motor terminals U, V, W can carry dangerous voltages
even if the driver is inoperative.
WARNING
WARNING
9.6.1 Power supply
The end user must connect the power supply cable and the command signal to the control board, while the motor connection is
already done by
Nicotra Gebhardt
.
DDMP 1.05kW 1-Phase
Single Phase 220/240V ±10% @ 50/60Hz
The performance in the range [200V-264V] @ 50Hz/60Hz is always the same
due to the PFC module inside the driver.
DDMP 2.1kW 1-Phase
Single Phase 220/240V ±10% @ 50/60Hz
The performance in the range [200V-264V] @ 50Hz/60Hz is always the same
due to the PFC module inside the driver.
Min. and max. wire section:
Spring-loaded push-in clamp, suitable for
•
0.2 mm² - 24 AWG up to 2.5 mm² - 12 AWG (stranded) or 4 mm² (solid) wire
Use a bladed screwdriver, 0.6x3.5 mm max, to unlock.
DDMP 2.65kW 3-Phase
Three Phase 400V ±10% @ 50/60Hz
The maximum fan performance, within the nominal range of sup
-
ply-voltage [360-440V], may be sensitive to the actual supply voltage.
Whether the fan maximum speed is related to the supply voltage
depends on the fan size and duty point.
Min. and max. wire section:
Spring-loaded push-in clamp, suitable for
•
0.2 mm² - 24 AWG up to 6 mm² - 8 AWG (stranded) or 10 mm²
(solid) wire
Use a bladed screwdriver, 0.6x3.5 mm max, to unlock.
As concerns the cable minimum section, check the requirements issued by the country of installation.