Rev. 0 - 05/11/2020
OPERATING MANUAL
OPERATING MANUAL
EN
EN
54/60
Holding Register 42:
Min Airflow [m3/h]
This register can be used to set the min constant airflow.
Allowed values
= [Default Value, Max Airflow]
Default value
= table below
7/7T
7/7
7/9 8/7T 9/7 8/9T 225/240 9/9 10/8 10/10 12/9 12/12 15/11 15/15
1.05kW
1-Phase
1000 500 1000 750 1000 1000
1000 1000 1000 1000
-
-
-
-
2.1kW
1-Phase
-
-
-
-
-
-
-
1000 1000 1000 1500 1500
-
-
2.65kW
3-Phase
-
-
-
-
-
-
-
1000 1000 1000 1500 1500
-
-
4kW
3-Phase
-
-
-
-
-
-
-
-
-
-
-
*
*
*
Holding Register 43:
Max Airflow [m3/h]
This register can be used to set the min constant airflow.
Allowed values
= [Default Value, Max Airflow]
Default value
= table below
7/7T
7/7
7/9 8/7T 9/7 8/9T 225/240 9/9 10/8 10/10 12/9 12/12 15/11 15/15
1.05kW
1-Phase
1950 3000 3500 2750 3000 3250
3250 3250 3750 4000
-
-
-
-
2.1kW
1-Phase
-
-
-
-
-
-
-
5000 4500 5000 4500 5000
-
-
2.65kW
3-Phase
-
-
-
-
-
-
-
5000 4500 5000 5000 5000
-
-
4kW
3-Phase
-
-
-
-
-
-
-
-
-
-
-
*
*
*
Holding Register 45:
Modbus Address [Adim]
This register can be used to change the Modbus address of a driver.
Allowed values
= [1, 247]
Default value
= 1
Holding Register 46:
Tachometric / Alarm / Threshold [Adim]
This register can be used to set the digital output function.
Allowed values
= table below
Default value
= 0
The possible settings are:
0
Tachometric
The digital output indicates the measured speed through a PWM signal
1
Alarm
The digital output indicates when an alarm occurs
2
Threshold
The digital output indicates when the speed set in the Holding Register 55 is overtaken
3
Out of Functioning Range
The digital output indicates when the fan is working in a defined range of speeds
Holding Register 47:
Modbus Speed [10
−1
kbps]
This register can be used to set the Modbus speed.
Allowed values
= table on the following page
Default value
= 96
*
The value is under development.
*
The value is under development.