Rev. 0 - 05/11/2020
OPERATING MANUAL
OPERATING MANUAL
EN
EN
45/52
Holding Register 33:
Avoid Range End [RPM]
This register combined with the Avoid Range Start can be used to skip some resonance frequencies of the fan.
Allowed values
= [Avoid Range Start, 20000]
Default value
= 20000
Holding Register 34:
Input Type [Adim]
This register defines all the possible operating modes:
Allowed values
= [0,12]
Default value
= 1
0
Modbus Speed Control
The speed is set by modifying the register 66
1
Analog Speed Control
The speed is set through the analog signal
2
Modbus Fixed Speed Control
The speed is set by modifying the register 21
3
Master&Slave
The fan is configured as slave and follows the master
4
Analog Constant Airflow
The constant airflow is set through the analog signal
(1)
5
Modbus Temporary Constant Airflow
The constant airflow is set by modifying the register 66
(1)
6
Modbus Fixed Constant Airflow
The constant airflow is set by modifying the reg. 39
(1)
7
Analog Asynchronous Emulation
The emulation is set through the analog signal
(2)
8
Modbus Temporary Asynchronous Emulation
The emulation is set by modifying the register 66
(2)
9
Modbus Fixed Asynchronous Emulation
The emulation is set by modifying the register 30
(2)
10
Analog Ref. PID Closed Control Loop
The PID ref. is set through the analog signal
11
Modbus Temporary Ref. PID Closed Control Loop
The PID ref. is set by modifying the register 66
12
Modbus Fixed Ref. PID Closed Control Loop
The PID ref. is set by modifying the register 50
Holding Register 36:
Maximum Power [W]
This register can be set to reduce the power out to the motor.
Allowed values
= [10, Default Value]
Default value
= table below
Value
1.05kW
1-Phase
1050
2.1kW
1-Phase
2100
2.65kW
3-Phase
2650
4kW
3-Phase
4100
(1)
The operating mode “Constant Airflow” is not available for RDPs. Setting the fan in one of the three Constant Airflow modes
could make it turn in an unknown and/or uncontrollable manner.
(2)
The algorithm related to the operating mode "Asynchronous Emulation" does not produce significant differences
on RDPs in comparison to the operating mode "Speed control". Therefore, its use is not recommended.
WARNING
WARNING
Holding Register 45:
Modbus Address [Adim]
This register can be used to change the Modbus address of a driver.
Allowed values
= [1, 247]
Default value
= 1
Holding Register 46:
Tachometric / Alarm / Threshold [Adim]
This register can be used to set the digital output function.
Allowed values
= table below
Default value
= 0