9.6.3.5 +24V AUX Power supply (for RDP 2.65kW - 3-Ph only)
The +24V output can supply a max current of 50mA and it is able to drive the
Nicotra Gebhardt
pressure transducer (code K43198).
Use an available ground pin on the board for powering devices.
9.6.3.6 +12V AUX Power supply (for RDP 2.1kW - 1-Ph only)
The 12V power supply can be used to provide power to the pressure transducer K43198, where
a 24V supply is not available.
An auxiliary power supply of 12V is available on the 2.1kW Single-Phase drivers.
The max current absorbed must be lower than 200mA.
Use an available ground pin on the board for powering devices.
This power is not stabilized and it decreases when the current absorption exceeds
the above indicated limit.
The FAN pin is not active.
If the transducer has its own PID control, the signal must be connected to the standard ANALOG INPUT.