Rev. 0 - 05/11/2020
OPERATING MANUAL
OPERATING MANUAL
EN
EN
36/52
10.4.4 Modbus positive/negative feedback
Depending on the application it could be necessary to
invert the feedback behavior.
Through the
Holding Register 31
it is possible to multiply
by -1 the PID error.
When the register is set to 0 -> Error = (R
eference
- M
easure
);
When the register is set to 1 -> Error = (M
easure
- R
eference
).
10.5 Changing the operation mode
Here are shown the actions passing from one operation mode to another one.
ACTION
ACTIONS A
ACTIONS B
Temporary Setting
-> Fixed Setting
The fan must follow the target corresponding to the value
stored the related register.
Fan is put in stop mode and after the data are saved the fan follows the
target corresponding to the value stored into the related register.
Fixed Setting ->
Temporary Setting The fan must stop waiting for a new register 66 value.
The fan must stop waiting for a new register 66 value.
Temporary Setting
-> Analog Signal
The fan must follow the target corresponding to the analog
value at the inputs.
Fan is put in stop mode and after the data are saved the fan follows the
target corresponding to the analog value.
Analog Signal ->
Temporary Setting The fan must stop waiting for a new register 66 value.
The fan must stop waiting for a new register 66 value.
Fixed Setting ->
Analog Signal
The fan must follow the target corresponding to the analog
value at the inputs.
Fan is put in stop mode and after the data are saved the fan follows the
target corresponding to the analog value.
Analog Signal ->
Fixed Setting
The fan must follow the target corresponding to the value
stored the related register.
Fan is put in stop mode and after the data are saved the fan follows the
target corresponding to the value stored into the related register.
Increasing the fan speed
The probe voltage
increases
The probe voltage
decreases