16

14) Further details: special functions

14.1) “Always open” function

The “always open” function is a feature of the control unit that enables continuous activation of an opening manoeuvre when the “Step-by-
step” command lasts more than 2 seconds; this can be useful for example to connect the SS terminal with the contact of a programme clock
to keep the gate open during a specific time band. This feature is valid regardless of the setting of the input SS with exception of the setting
as “Apartment block 2”, see parameter “Function SS” in Table 4.

15) Automation operation by means of transmitter and “SM” radio receiver 

The Control unit is fitted with a connector specially for the installation
of a radio receiver with “SM” type connection (Fig. 13), to control the
automation  using  a  radio  transmitter  (receiver  and  transmitter  are
optional accessories). The four Outputs of the Receiver enable deliv-
ery of the following commands to the control unit:

If the aerial incorporated in LUCYB or other type of external aerial is
not used, screw the rigid cable supplied with the receiver onto the
aerial terminal (Fig. 14).

14.2) “Move anyway” function

In the event that a safety device malfunctions or is out of service, the gate may still be moved in “hold-to-run” mode. For details, refer to the
paragraph “Control with safety devices out of service” in the enclosure “Instructions and warnings for the SOON gearmotor user”.

Output N°1

“SS” command (Step-Step)

Output N°2

“Partial open” command

Output N°3

“Open” command

Output N°4

“Close” command

Table 6: commands with receiver SMXI, SMXIS

16) Automatic fault finding and diagnostics

During normal operation, the control unit constantly monitors the automation processes and is designed to indicate any faults that arise, by
means of a pre-set sequence of flashes emitted by the flashing light, courtesy light and the “BlueBUS Led” (the diagnostics flashes always
refer to the last action performed by Soon) For an explanation of the number of flashes and associated cause, refer to the table below:

Table 7: diagnostics flash signals

13

14

n° flash

Cause

1

BlueBUS synchronisation error

2

Activation of Photocell or Phototest error

3

Gearmotor force insufficient or obstacle detected during travel

4

Stop device activation

5

Memory parameter error

6

Internal manoeuvre limiter activation

7

Power failure on motor circuits

8

Overcurrent on motor circuits

Содержание Soon

Страница 1: ...ings for the fitter Istruzioni ed avvertenze per l installatore Instructions et recommandations pour l installateur Anweisungen und Hinweise f r den Installateur Instrucciones y advertencias para el i...

Страница 2: ...utomation The various sub jects are divided into three sections SECTION 1 is a step by step guide illustrating the phases re quired for physical installation of the product and operation start up SECT...

Страница 3: ...menta tion Before starting installation check whether other devices or mate rials are required to complete automation with Soon evaluating the specific application and associated risks for example co...

Страница 4: ...ell 3 Key operated selector switch 4 Post for photocell 5 Flashing light 6 Transmitter 7 Main edge Key to electric cables in Fig 3 A Electric power line B Flashing light with aerial C Photocells D Key...

Страница 5: ...1 Fig 4 a Insert the Soon outlet shaft in the sectional door drive shaft coupling them using the keys provided in the pack Perform this operation with the door CLOSED 2 Fig 4 b Secure the bracket to...

Страница 6: ...anual requires locking or release of the SOON mechanism Note The release or locking manoeuvres of the mechanism must be per formed exclusively with the gearmotor completely stationary The manual opera...

Страница 7: ...electric lock the FLASH output can be con nected to a 24V max 10W electric lock with latch versions with electromagnet only without electronic devices During the opening manoeuvre the electric lock is...

Страница 8: ...detec tors even not synchronised and enables the addition of other photo cells for example in the case of transit of heavy vehicles where a sec ond photocell is normally positioned at 1 m from the gr...

Страница 9: ...before proceeding Perform the following operations as specified and cross off the points as conformity of results is verified 6 Initial system start up checks 7 Memorising devices and positions 6 1 Op...

Страница 10: ...1 Led L2 remains lit Led L4 flashes Position RINT programming 7 If the intermediate slowdown position programming is not required press the key Set twice quickly to skip to the next programming led L4...

Страница 11: ...moving door are pro tected by means of impact force limitation measure the force as specified in the standard EN 12445 If speed and motor force controls are used as auxiliary functions with the syste...

Страница 12: ...the opening manoeuvre stops immediately after release of the photocells and automatic closure is activated with a pause of 5s The function Close After Photo is always disabled in manoeuvres interrupte...

Страница 13: ...e before automatic closure Applied only when auto matic closure function is enabled Sets the sequence of commands associated with the SS input or the 1st radio command Sets the motor speed during norm...

Страница 14: ...e not recommended to compensate for the fact that the leaf has anomalous points of friction excessive force may impair the safety system and damage the leaf If the Motor force control is used in suppo...

Страница 15: ...to L8 i e the input led associated with the parameter Fault log 4 Press and hold Set during steps 5 and 6 5 Wait approx 3s after which the leds corresponding to the manoeuvres subject to faults will...

Страница 16: ...erial terminal Fig 14 14 2 Move anyway function In the event that a safety device malfunctions or is out of service the gate may still be moved in hold to run mode For details refer to the paragraph C...

Страница 17: ...If no voltage is present this means that there is an electric overload on the output Check that there are no short circuits on the cable during the position memorisation phase led L1 or led L8 flashes...

Отзывы: