8) Perform final testing of system

8.1) Final testing

Each component of the automation, such as the sensitive
edges,  photocells,  emergency  stop,  etc.,  requires  a  spe-
cific  testing  phase;  for  these  devices  the  specific  proce-
dures in the respective instruction manuals must be per-
formed. To test SOON proceed as follows: 

1. Ensure  that  all  specifications  in  chapter  1  “WARNINGS”  have

been observed.

2. Release  the  door  from  the  motor  by  pulling  the  release  cord

down. Check that the door can be moved manually in opening
and closing with a maximum force of 225N.

3. Lock the door to the motor by pulling the locking cord down.
4. Using  the  selector  or  radio  transmitter,  perform  door  opening

and closing tests and ensure that the movement corresponds to
specifications.

5. Test several times to assess smooth operation of the door and

check for any defects in assembly or adjustment and any possi-
ble points of friction.

6. Check operation of all system safety devices one at a time (pho-

tocells, sensitive edges, etc.) In particular, each time a device is
activated the “BlueBUS” led on the control unit must flash rapid-
ly twice to confirm acknowledgement of the event.

7. To check the photocells, and in particular to ensure there is no

interference with other devices, pass a cylinder with diameter of
5cm and length 30cm on the optical axis, first close to the TX,
then  close  to  the  RX  and  lastly  at  the  centre  between  the  two
and ensure that in all cases the device engages, changing from
the  active  status  to  alarm  status  and  vice  versa,  and  that  the
envisaged action is generated on the control unit, for example: in
the closing manoeuvre it inverts movement.

8. If  hazardous  situations  generated  by  the  moving  door  are  pro-

tected by means of impact force limitation, measure the force as
specified  in  the  standard  EN  12445.  If  speed  and  motor  force
controls  are  used  as  auxiliary  functions  with  the  system  for
reduction  of  impact  force,  test  and  identify  the  setting  that
obtains the best results.

8.2) Commissioning

Commissioning  can  only  be  performed  after  positive
results  of  all  test  phases  on  Soon  and  the  other  devices
present.  Partial  or  “makeshift”  commissioning  is  strictly
prohibited.

1

The  prepared  automation  technical  documentation  should  be
conserved for at least ten years and must contain at least the fol-
lowing:  overall  drawing  of  the  automation,  electrical  wiring  dia-
gram, risk assessment and relative solutions adopted, manufac-
turer's declaration of conformity for all devices used (in the case
of Soon, use the EC declaration of conformity en-closed); copy
of the operation instruction manual and mainte-nance schedule
for the automation. 

2. Affix  a  dataplate  on  the  door,  specifying  at  least  the  following

data:  type  of  automation,  name  and  address  of  manufacturer
(responsible  for  commissioning),  serial  number,  year  of  con-
struction and CE mark

3. Permanently affix a label or plate in the vicinity of the door, indi-

cating the operations for door release and manual manoeuvres.

4. Permanently affix a label or plate on the door, bearing this image

(min. height 60 mm).

5. Prepare  and  provide  the  owner  with  the  declaration  of  confor-

mity of the automation.

6. Prepare and provide the owner with a the manual “Automation

operation instructions and warnings”.

7. Prepare and provide the owner with the automation maintenan-

ce schedule (containing all prescriptions for maintenance of indi-
vidual devices).

8. Before commissioning the automation, ensure that the owner is

adequately  informed  in  writing  (such  as  in  the  automation
instruction  and  warning  manual)  of  all  associated  risks  and
hazards.

Содержание Soon

Страница 1: ...ings for the fitter Istruzioni ed avvertenze per l installatore Instructions et recommandations pour l installateur Anweisungen und Hinweise f r den Installateur Instrucciones y advertencias para el i...

Страница 2: ...utomation The various sub jects are divided into three sections SECTION 1 is a step by step guide illustrating the phases re quired for physical installation of the product and operation start up SECT...

Страница 3: ...menta tion Before starting installation check whether other devices or mate rials are required to complete automation with Soon evaluating the specific application and associated risks for example co...

Страница 4: ...ell 3 Key operated selector switch 4 Post for photocell 5 Flashing light 6 Transmitter 7 Main edge Key to electric cables in Fig 3 A Electric power line B Flashing light with aerial C Photocells D Key...

Страница 5: ...1 Fig 4 a Insert the Soon outlet shaft in the sectional door drive shaft coupling them using the keys provided in the pack Perform this operation with the door CLOSED 2 Fig 4 b Secure the bracket to...

Страница 6: ...anual requires locking or release of the SOON mechanism Note The release or locking manoeuvres of the mechanism must be per formed exclusively with the gearmotor completely stationary The manual opera...

Страница 7: ...electric lock the FLASH output can be con nected to a 24V max 10W electric lock with latch versions with electromagnet only without electronic devices During the opening manoeuvre the electric lock is...

Страница 8: ...detec tors even not synchronised and enables the addition of other photo cells for example in the case of transit of heavy vehicles where a sec ond photocell is normally positioned at 1 m from the gr...

Страница 9: ...before proceeding Perform the following operations as specified and cross off the points as conformity of results is verified 6 Initial system start up checks 7 Memorising devices and positions 6 1 Op...

Страница 10: ...1 Led L2 remains lit Led L4 flashes Position RINT programming 7 If the intermediate slowdown position programming is not required press the key Set twice quickly to skip to the next programming led L4...

Страница 11: ...moving door are pro tected by means of impact force limitation measure the force as specified in the standard EN 12445 If speed and motor force controls are used as auxiliary functions with the syste...

Страница 12: ...the opening manoeuvre stops immediately after release of the photocells and automatic closure is activated with a pause of 5s The function Close After Photo is always disabled in manoeuvres interrupte...

Страница 13: ...e before automatic closure Applied only when auto matic closure function is enabled Sets the sequence of commands associated with the SS input or the 1st radio command Sets the motor speed during norm...

Страница 14: ...e not recommended to compensate for the fact that the leaf has anomalous points of friction excessive force may impair the safety system and damage the leaf If the Motor force control is used in suppo...

Страница 15: ...to L8 i e the input led associated with the parameter Fault log 4 Press and hold Set during steps 5 and 6 5 Wait approx 3s after which the leds corresponding to the manoeuvres subject to faults will...

Страница 16: ...erial terminal Fig 14 14 2 Move anyway function In the event that a safety device malfunctions or is out of service the gate may still be moved in hold to run mode For details refer to the paragraph C...

Страница 17: ...If no voltage is present this means that there is an electric overload on the output Check that there are no short circuits on the cable during the position memorisation phase led L1 or led L8 flashes...

Отзывы: