The composition and use of the system involve aspects that impact 

consumption, in particular the brightness of the display, the power 

draw of sirens and of any peripherals wired to the system. These 

factors must be taken into account in relation to the power supply’s 

power rating, which must be able to guarantee correct charging of all 

the connected batteries. The table indicates the current draw levels 

of the 3 control unit models and the relative batteries. For each sys-

tem the following elements must be calculated:

a)

 the maximum current draw, calculated by adding to the con-

sumption of the control unit that of other devices wired to it, must 

not exceed the power supply’s capacity (the current draw should be 

contained to 80% of the nominal capacity).

b) 

the minimum autonomy, in the absence of 230 V power supply, 

taking into account 80% of the battery’s nominal capacity.

Warning!

 If there is no mains power, the display and Wi-Fi module of 

the control unit will be disabled. Connection to the network must be 

made through the GSM/GPRS module.

Warning!

 Control units with touch screen (MNCUT/MNCUTC): take 

into account the indicated consumption differences, linked to the 

brightness of the touch screen – good visibility can be obtained even 

at 35%.

Technical characteristics

Current draw

Table 1

Code

MNCUT

MNCUTC

MNCUC

Power supply

110 V–240 V

110 V–240 V

110 V–240 V

Surveillance

18’

18’

18’

Radio transmission

GFSK dual band 433.54-

433.92 MHz; 868.30-

868.94 MHz

GFSK dual band 433.54-

433.92 MHz; 868.30-

868.94 MHz

GFSK dual band 433.54-

433.92 MHz; 868.30-

868.94 MHz

Open-field radio range,  

without disturbances

> 100 m

> 100 m

> 100 m

Insulation (class)

II

II

II

Environmental class 

 in accordance with EN 50131-1

2

2

2

Operating temperature

–10°C ... +40°C

–10°C ... +40°C

–10°C ... +40°C

Dimensions (WxDxH)

265 x 265 x 40 mm

265 x 265 x 85 mm

265 x 265 x 85 mm

Weight

1,250 g

1,850 g

1,650 g

IP

40

40

40

Table 2

Code

MNCUT MNCUTC MNCUT MNCUTC MNCUT MNCUTC MNCUT MNCUTC MNCUTC and MNCUC

MNCUT

Power supply 

110–240V

110–240V

BLACK-OUT

BLACK-OUT

Touch screen bright-

ness

100%

50%

10%

-

-

-

Mains power

7.5 V

2 A

14.5 V

1.6 A

7.5 V

2 A

14.5 V

1.6 A

7.5 V

2 A

14.5 V

2 A

14.5 V 

1.6 A

7.5 V 

2 A

-

-

Battery pack

1 x 6 V 

1.2 Ah

1–2 x 12 V 

2.2 Ah

1 x 6 V  

1.2 Ah

1–2 x 12 V 

2.2 Ah

1 x 6 V  

1.2 Ah

1–2 x 12 V 

2.2 Ah

1–2 x 12 V 

2.2 Ah

1 x 6 V 

1.2 Ah

1–2 x 12 V 

2.7 Ah

1 x 6 V 

1.2 Ah

Current draw in stand-by
CPU 

(mA)

720

390

520

300

350

200

150

270

30

45

Wi-Fi 

(mA)

40

40

40

40

40

40

40

40

-

-

Circuit board 

(mA)

-

20

-

20

-

20

20

-

20

-

MNGSM 

(mA)

10

10

10

10

10

10

10

10

10

10

MNPSTN 

(mA)

0

0

0

0

0

0

0

0

0

0

Total 

(mA)

770

460

570

370

400

270

220

320

60

55

5

Содержание MNCUC

Страница 1: ...Nice MNCUT MNCUTC MNCUC EN Instructions and warnings for installation and use MyNice control unit...

Страница 2: ......

Страница 3: ...rdy Do not place the system s components close to sources of strong heat as this may damage them Each sensor has its own operating principle check the suitability of the intended positioning against t...

Страница 4: ...aining from 1 to 99 detectors Depending on the type and size of the system there are 3 control unit models to choose from MNCUT MyNice control unit 99 zones in 6 areas dual band two way radio with 7 c...

Страница 5: ...h screen good visibility can be obtained even at 35 Technical characteristics Current draw Table 1 Code MNCUT MNCUTC MNCUC Power supply 110 V 240 V 110 V 240 V 110 V 240 V Surveillance 18 18 18 Radio...

Страница 6: ...l unit after carefully considering the following aspects the control unit without the display must be positioned at least 1 metre above the floor to favour the Wi Fi communication Place the versions w...

Страница 7: ...in the outdoor area subsequently activating the siren at full power and making phone calls in case of attempted break ins involving the inner areas Example of block subdivision Fig 3 Area 1 Garden de...

Страница 8: ...5 The electrical connections 6 The installation of the control unit see Installing the control unit Since the system components communicate via radio it is advisable to first configure the system on a...

Страница 9: ...1 3 5 6 4 5 2 1 2 3 4 7 5 mm 5 mm 9 1 2...

Страница 10: ...reply with 1 beep Interruption of alarm calls Enter the indicated codes and wait for the reply the control unit will reply with the recorded voice messages or if none are recorded with acoustic signal...

Страница 11: ...rom any telephone number by entering after the reply signal the User PIN code followed by If the voice messages have been recorded correctly the control unit will reply with the following voice messag...

Страница 12: ...y detectors sirens equipped with the appropriate input The fault input if used triggers the ANOMALY signal and the rela tive warning messages All unused inputs may be left without any connection they...

Страница 13: ...alarm inputs alarm inputs tamper inputs only with inputs used in NC mode Warning Not conforming to EN 50131 close on GND R22k balanced fault input EN 50131 close on GND 12 V for supplementary sirens g...

Страница 14: ...tdoors with voice messages and LED flashing light MNSC Wired siren for outdoors with voice messages and LED flashing light for MNCUTC and MNCUC only MNSI Two way dual band radio siren for indoors with...

Страница 15: ...stance or physical obstacles lying in between the radio range between the control unit and certain devices must be extended The repeater must be placed at an equal distance from the control unit and f...

Страница 16: ...ge 2 of the sirens Specific parameters of MNMC and MNGB magnetic contact detectors Door open signal normally enabled EN 50131 but can be disa bled If active it signals any open doors windows when the...

Страница 17: ...It is obtained by adding 1 to the last digit of the PIN for example PIN 11111 duress function activation code 11112 or PIN 11119 duress function activation code 11110 In case of error calls can be dis...

Страница 18: ...aid panic and aggression aid GSM calls periodic messages Internet connection Contact ID digital protocols Other communication parameters To activate and manage reception of alerts via e mail Email To...

Страница 19: ...hat the smartphone is connected to the Wi Fi or is nonetheless enabled to exchange data if the control unit is connected in Access Point mode connect the smartphone to the WLAN of the control unit Acc...

Страница 20: ...IS0602A01EN_22 12 2017 www niceforyou com Nice S p A Via Pezza Alta 13 31046 Oderzo TV Italy info niceforyou com...

Отзывы: