• Start Close after photo (0x7a)

This parameter determines which safety device restarts closing after a trip. You can choose between:
- Photocells and Loop (0x40). Default setting
- Loop only (0x41).
- Photocells only (0x42).

• wait time (0x85)

This parameter is expressed in seconds and can be set with a value from 0 to 250 sec.; the factory setting is 5 sec. This function enables programming on 
the Control unit of the required wait time to pass between the end of an Opening manoeuvre and the start of a Closing manoeuvre.

Always close (0x87)

• 

active (0x88)

This parameter is ON/OFF; the factory setting is “OFF”. This function is useful in the event of a power failure, even brief. During an Opening manoeuvre if the 
automation shuts down due to a power failure and the function is active (ON), the Closure manoeuvre is performed normally when power is restored. On 
the contrary, if the function is not active (OFF), the automation remains stationary when power is restored. 

Note 

– For reasons of safety, when the function is 

active, the Closure manoeuvre is preceded by a wait time as programmed in the function “pre-flash time”.

• 

mode (0x8a)

This parameter is factory set on the mode “always close”. The function has 2 operating modes:

standard 

– For this mode, refer to the function “active” under the item “always close”;

save automatic closure 

– With this mode active, when power is restored after a power failure, two results are possible: 

a) 

execution of automatic closure, 

observing the time as programmed in the function “pre-flashing time”, if the timeout interval of this time was in progress at the time of the power failure; b) 
execution of closure manoeuvre if the automatic closure was in progress at the time of the power failure and the manoeuvre had not been completed.

Note 

– If the automatic closure manoeuvre was cancelled before the power failure (for example, by sending the Halt command), the Closure manoeuvre is 

not performed when the power is restored.

• 

wait time (0x89)

This parameter is expressed in seconds and can be set with a value from 0 to 20 sec.; the factory setting is 5 sec. This function enables programming on the 
Control unit of the required wait time to pass between the end of an Opening manoeuvre and the start of a Closing manoeuvre.

Force (0x47)

• 

opening force (0x4a)

This parameter can be set with a value from 10% to 100%; the factory setting depends on the version of barrier. The function adjusts the maximum force the 
motor can absorb during an opening manoeuvre.

Important

 – Setting this value too high can damage the gearmotor and overheat the control unit.

• 

opening deceleration force (0x4d)

This parameter can be set with a value from 10% to 100%; the factory setting depends on the version of barrier. The function enables control of the maximum 
force absorbed by the motor during the deceleration phase of an Opening manoeuvre. 

Important 

– Setting this value too high can damage the gearmotor 

and overheat the control unit.
• 

closing force (0x4b)

This parameter can be set with a value from 10% to 100%; the factory setting depends on the version of barrier. The function enables control of the force 
absorbed by the motor during a Closing manoeuvre. 

Important 

– Setting this value too high can damage the gearmotor and overheat the control unit.

• 

closing deceleration force (0x4d)

This parameter can be set with a value from 10% to 100%; the factory setting depends on the version of barrier. The function enables control of the maximum 
force absorbed by the motor during the deceleration phase of a Closing manoeuvre. 

Important 

– Setting this value too high can damage the gearmotor and 

overheat the control unit.
• 

action time (0x37)

This parameters sets the action time when the set level of force is exceeded. It is expressed in multiples of 30ms and can be set from 6 (=180ms) to 32 
(=960ms). Increasing this setting increases the action time of the amperometric obstacle detection function.

Sensitivity (0x38)

The sensitivity parameter is linked with the encoder and, together with the force function, is used to limit the obstacle detection time following an impact. The 
greater the sensitivity, the shorter the time between encoder pulses. The lower the sensitivity, the longer the time between encoder pulses.
• 

opening sensitivity (0x3a)

This parameter takes values from 0 to 200, and is used during opening manoeuvres; the factory setting depends on the version. 

Important 

– a too high 

setting can cause false positives due to the oscillation of the barrier itself.
• 

opening deceleration sensitivity (0x3d)

This parameter takes values from 0 to 200, and is used during the opening deceleration cycle; the factory setting depends on the version. 

Important 

– a too 

high setting can cause false positives due to the oscillation of the barrier itself.
• 

closing sensitivity (0x3b)

This parameter takes values from 0 to 200, and is used during closing manoeuvres; the factory setting depends on the version. 

Important 

– a too high setting 

can cause false positives due to the oscillation of the barrier itself.
• 

closing deceleration sensitivity (0x3d)

This parameter takes values from 0 to 200, and is used during the closing deceleration cycle; the factory setting depends on the version. 

Important 

– a too 

high setting can cause false positives due to the oscillation of the barrier itself.

Exclusion position (0xa4)

This parameter is expressed in seconds and can be set with a value from 0 to 250 seconds; the factory setting is 5 seconds. 

Note 

– The value “0” is consid-

ered to be the fully closed position of the automation

. This function enables the programming of the maximum limit, over which the control unit automatically 

disables the inversion manoeuvres envisaged in the obstacle detection functions, if the latter are active.

Speed (0x40)

• 

opening speed (0x42)

This parameter can be set with a value from 15% to 100%; the factory setting depends on the version. The function enables programming of the required 
motor speed during an Opening manoeuvre. 

Important 

– This parameter also affects the impact forces.

• 

opening deceleration speed (0x45)

This parameter can be set with a value from 5% to 100%; the factory setting depends on the version. The function enables programming of the required 
motor speed during the deceleration phase of an opening manoeuvre. 

Important 

– This parameter also affects the impact forces.

Содержание LBar

Страница 1: ...Programmable functions using the Oview programmer MBar LBar STF XBA3 Rev00 Firmware XB02a XU01 XF01 ...

Страница 2: ... a programming session followed by the log out procedure on completion of the programming procedure Note the log out procedure enables the user to prevent access by unauthorised personnel by re activating the existing password Caution In programming the password on multiple devices for example on the Oview control unit receiver etc it is advisable to use the same password for all devices including...

Страница 3: ... at the end of the wait time programmed in the function pause time If the function is not active OFF the Control unit operation mode is semiautomatic Pause time 0x81 This parameter is expressed in seconds and can be set with a value from 0 to 250 sec the factory setting is 20 sec This function enables programming on the Control unit of the required wait time which must pass between the end of an O...

Страница 4: ...n of barrier The function enables control of the force absorbed by the motor during a Closing manoeuvre Important Setting this value too high can damage the gearmotor and overheat the control unit closing deceleration force 0x4d This parameter can be set with a value from 10 to 100 the factory setting depends on the version of barrier The function enables control of the maximum force absorbed by t...

Страница 5: ...n be set with a value from 0 to 10 sec the factory setting is 3 sec This function programs the flashing time which indicates the imminent start of a Closing manoeuvre it is associated with the pre flashing function Stand by 0x8b active 0x8c This parameter is ON OFF the factory setting is OFF When this function is set to ON automation power consumption can be reduced mode 0x8e The function has 3 op...

Страница 6: ...ration opening mode This command is factory assigned to Input 2 in mode open When this command is sent the control unit activates the ap plication to complete the Opening manoeuvre until the position is reached as set in the function opening Control unit func tions installation positions opening Input configured as normally open Close Closure Program the desired mode from those listed in table 1 B...

Страница 7: ...de apartment block 1 open When this command is sent the control unit activates the ap plication to perform the opening manoeuvre only until the limit switch is reached Note This command is useful when using control photocells or a magnetic detector loop Input configured as normally open Photo Safety function Photo Program the desired mode from those listed in Table 1 F command configuration photo ...

Страница 8: ...iation of the metal body required to start a manoeuvre Note set a high sensitivity to detect small metal bodies set a low sensitivity to detect large metal bodies Loop activation 0xe7 This parameter type is ON OFF the factory setting is ON Activating the loop means that the barrier will react as programmed when it is tripped If the function is DEACTIVATED the status of the loop is available if one...

Страница 9: ...er command is sent after this one the application executes the Closing manoeuvre with the same sequence Apartment block 2 step by step This executes the sequence close stop partial open 1 partial open 1 until the position is reached as pro grammed in the function Partial Open 1 Note If another command is sent after this one the application executes the Closing manoeuvre with the same sequence Impo...

Страница 10: ...lication to perform a brief inversion in the opposite direction Closing Caution During execution of the Opening manoeuvre this command is ignored Stop When the control unit receives the command it stops the Opening manoeuvre in progress Caution During execu tion of the Opening manoeuvre this command is ignored temporary stop When the control unit receives the command it stops the Closing manoeuvre...

Страница 11: ...er TABLE 2 OUTPUT CONFIGURATION FUNCTION DESCRIPTION sca 0x01 The programmed light indicates the operating status of the control unit light off application in maximum Closing position slow flashing application Opening manoeuvre execution phase quick flashing application Closing manoeuvre execution phase light permanently on application in maximum Opening position SCA1 0x14 The programmed light ind...

Страница 12: ...nnel is not free on the control unit s receiver due to having been previously memorised with a command when the chan nel is activated by the transmitter the control unit only activates the programmed output and ignores the motor command Radio channel 4 0x12 When a transmitter sends a command this output is activated This mode is useful if installing external devices for example an auxiliary light ...

Страница 13: ...tem to be controlled with a single transmitter CAUTION If this channel is not free on the control unit s receiver due to having been previously memorised with a command when the channel is activated by the transmitter the control unit only activates the programmed output and ignores the motor command Output active 24 V DC max 10 W radio channel no 2 If this radio channel is set for the configurati...

Страница 14: ... to occupation by a metal body Loop2 Indicates when the loop is activated due to occupation by a metal body BOARD KEYS no 1 Indicates when key 1 is pressed OPEN on the control unit no 2 Indicates when key 2 is pressed STOP on the control unit no 3 Indicates when key 3 is pressed CLOSE on the control unit DIRECTION SELECTION Indicates the status of the direction selector for a manoeuvre INPUT STATU...

Страница 15: ...ata is useful to understand whether the encoder is in an overtravel position i e outside the operating zone of the absolute encoder bluebus device diagnostics This function displays the type operating status and configuration of devices connected ot the Bluebus output These parameters are described in Table 6 TABLE 6 DIAGNOSTICS of bluebus devices PARAMETER DESCRIPTION Bluebus PHOTOCELLS PHOTO Ind...

Страница 16: ...s required after performing mainte nance on the automation ADVANCED FUNCTIONS event log This function enables the display of the events generated or received by the control unit An event is a condition which changes the operating status of the control unit such as activation of an input end of a manoeuvre photocell or stop input tripped etc This section displays the date and type of an event firmw...

Отзывы: